Bvvb
Free
PVC
PVC
Round Wire
ISO, CCC, CE, RoHS
Copper Core
GUOWANG
Wooden Drum/According to Your Requirement
1.5-300 mm2
China
8544492100
Product Description
Application
Range System
This product is suitable for AC 50Hz, voltage does not exceed 300/500V power line transmission power.
Occasions
AC voltage 300/500V and below power plants, fixed wiring, household appliances, meters, lighting and telecommunications equipment. Features Good insulation performance, with a certain degree of acid and alkali resistance, oil resistance, moisture-proof characteristics; Stable structure, simple manufacturing process, low price.
Compliance with standard Implementation
Standard
JB/T 8734-1998
Rated voltage
450/750V and below PVC insulated cables, wires and cords Additional standard Usage characteristics Rated voltage 0.3/0.5kV
Operating temperature
The maximum allowable operating temperature of the cable conductor for a long term is 70 ° C.
Ambient temperature
The ambient temperature of the cable should not be lower than 0 ° C.
Laying temperature
The laying temperature of the cable should not be lower than 0 ° C. Bending radius
The bending radius of a cable with an outer diameter (D) smaller than 25mm should be not less than 4D.
The bending radius of a cable with an outer diameter (D) larger than 25mm should be not less than 6D. Core color identifier: two-core cable: light blue, brown; Three core cable: light blue, brown, black. 1. The cable should have continuous identification of the manufacturer's name, product model and rated voltage, and the manufacturer's name identification can be repeated identification of the manufacturer or trademark; 2. The distance between the end of one complete sign and the beginning of the next sign shall not exceed 275mm; The printed logo should be erasable and not easy to fall off, and the printed content on the surface should be clearly recognizable.

specification | conductor structure | Outer diameter of conductor(mm) | insulation thickness(mm) | sheath thickness(mm) | Reference outside diameter(mm) | Reference weight(kg/km) | 20ºC maximum DC resistance(Ω/km) | Minimum insulation resistance at operating temperature(MΩ·km) | testing voltage(kV/min) | Maximum allowable tractive force of conductor(N) |
2×0.75 | 1/0.97 | 0.97 | 0.6 | 0.9 | 4.2×6.5 | 45.6 | 24.5 | 0.012 | 2/5 | 105 |
2×1.0 | 1/1.13 | 1.13 | 0.6 | 0.9 | 4.4×6.9 | 53.1 | 18.1 | 0.011 | 2/5 | 140 |
2×1.5 | 1/1.38 | 1.38 | 0.7 | 0.9 | 4.8×7.7 | 69.8 | 12.1 | 0.011 | 2/5 | 210 |
2×2.5 | 1/1.78 | 1.78 | 0.8 | 1 | 5.6×9.1 | 103.1 | 7.41 | 0.01 | 2/5 | 350 |
2×4 | 1/2.25 | 2.25 | 0.8 | 1 | 6.1×10.1 | 138.6 | 4.61 | 0.0085 | 2/5 | 560 |
2×6 | 1/2.76 | 2.76 | 0.8 | 1.1 | 6.8×11.3 | 188.6 | 3.08 | 0.007 | 2/5 | 840 |
2×10 | 7/1.35 | 4.05 | 1 | 1.2 | 8.8×15.1 | 314.1 | 1.83 | 0.0067 | 2/5 | 1400 |
3×0.75 | 1/0.97 | 0.97 | 0.6 | 0.9 | 4.2×8.8 | 65.3 | 24.5 | 0.012 | 2/5 | 158 |
3×1.0 | 1/1.13 | 1.13 | 0.6 | 0.9 | 4.4×9.4 | 76.5 | 18.1 | 0.011 | 2/5 | 210 |
3×1.5 | 1/1.38 | 1.38 | 0.7 | 0.9 | 4.8×10.6 | 101.5 | 12.1 | 0.011 | 2/5 | 315 |
3×2.5 | 1/1.78 | 1.78 | 0.8 | 1 | 5.6×12.6 | 150.9 | 7.41 | 0.01 | 2/5 | 525 |
3×4 | 1/2.25 | 2.25 | 0.8 | 1.1 | 6.3×14.3 | 209.9 | 4.61 | 0.0085 | 2/5 | 840 |
3×6 | 1/2.76 | 2.76 | 0.8 | 1.1 | 6.8×15.8 | 278.5 | 3.08 | 0.007 | 2/5 | 1260 |
3×10 | 7/1.35 | 4.05 | 1 | 1.2 | 8.8×21.4 | 467 | 1.83 | 0.0067 | 2/5 | 2100 |