JXF
Distribution Metering Box
Protection
ISO9001:2000
All- packaged Type
Low Voltage
3 Uint
High-rise Buildings
Steel Plate
IP56
380 (660)V
Ui 660 (1000)V
50 (60) Hz
IP40
Senda
Wooden Box
Standard Specifications
China
Product Description
MLS Low Voltage Switchgear

Product Advantages
1.Compact structure: it can accommodate more functional units in a small space, and a single cabinet can accommodate up to 36 drawer circuits, saving the area of comrades in arms.
2.Flexible assembly: the C-shaped profile with 25mm module can meet various structural forms and can be combined and configured arbitrarily.
3.Standard module: it can form standard units such as protection, operation, conversion, control, adjustment, measurement and indication, and can be freely combined according to drawer type and fixed type as required.
4.Safe and reliable: the device to prevent the occurrence and spread of fault arc is carefully designed to ensure the safety of equipment and operators.
1.Compact structure: it can accommodate more functional units in a small space, and a single cabinet can accommodate up to 36 drawer circuits, saving the area of comrades in arms.
2.Flexible assembly: the C-shaped profile with 25mm module can meet various structural forms and can be combined and configured arbitrarily.
3.Standard module: it can form standard units such as protection, operation, conversion, control, adjustment, measurement and indication, and can be freely combined according to drawer type and fixed type as required.
4.Safe and reliable: the device to prevent the occurrence and spread of fault arc is carefully designed to ensure the safety of equipment and operators.
MLS Low Voltage Switchgear | |
Rated voltage Ue | 380 (660)V |
Rated insulation voltage | Ui 660 (1000)V |
Rated impulse withstand voltage | Uimp 8kV |
Rated frequency | 50 (60) Hz |
Main bus rated current | In ≤6300A |
Main bus short-time (1S) withstand current | Icw ≤100kA |
Main bus peak withstand current | Ipk ≤220kA |
Distribution bus (vertical bus) rated current | In 630, 800, 1000, 1250, 1600A |
Distribution bus (vertical bus) short-time (1S) withstand current | Icw ≤50kA |
Distribution bus (vertical bus) peak withstand current | Ipk ≤105kA |
Protection level | IP40 |
Height (H) 2200 mm (effective installation space for a single unit is 1800 mm) | |
Width (W) 400, 600, 800, 1000, 1200 mm (cannot be used as an MCC cabinet when it is 400 mm) | |
Depth (D) 600, 800, 1000, 1200 mm (cannot be used as an MCC cabinet when it is 600 mm) Module E=25 mm |