Air-Blast Load Break Switch-Fuse Combination Apparatus

Price $2000.00 Compare
Min Order 1 Piece
Shipping From Zhejiang, China
Popularity 227 people viewed
Quantity
+-
 

Zhejiang Beidian Technology Co., Ltd.

VIP   Audited Supplier 1 year
Profile Certified by SGS/BV
FKN12-12D
Low Voltage Circuit Breakers
Electric Type
Normal Type Circuit Breaker
Air
Fixed
ACB
1
Circuit Breaker
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection, OVP(Overvoltage Protection)
ISO9001-2000, CCC
12
50
630
2000
BDN
Carton
medium
China
85353000
Product Description

General

 

These series are especially applicable in rural, urban terminal substation and prefabricated substations, as well as ring network power supply.FKN12A-12D Series air-blast load break switch can break and make load current and over-current.FKRN12A-12D Series air-blast load break switch can break and make over-current, load current and short-circuit current(limited current fuse).This product is featured with impact structure, aesthetic appearance reliable interlock and high insulating level. In the spring storage operating mechanism, ON/OFF speed is free from the influence of the manpower. For the arc-extinguish electric arc-extinguish inside the insulating cover, the free gas occurs at sparking do not cause descend of insulating level between phases and phase to earth. The insulating cover clapboard separates electrified part thus boost protection grade of ring main unit. The copper-tungsten contact and main contact brings along reliable conductivity and long life. This product achieves sound fame due to easy maintenance and operations as well as reliable performance. It is in compliance with per IEC62271-105.

Service environment

 
  • Ambient temperature-25ºC-+40ºC

  • Elevation≤1000m

  • Humidity; daily average humidity≤95%, monthly≤90%

  • The earthquake does not exceed degree 8

  • No fire, explosion, chemical errosion

  • Pollution: level 2

Key Feature

 

  • Load switch, ground switch, fuse and mechanism on a frame, flexible combination, compact structure, small size easy to install.

  • The fracture is arranged in direct motion, the dynamic and thermal stable current parameters are high, and the operation is completed at one time.

  • With static contact insulation cover, the ring network cabinet is isolated in the structure, eliminating the insulation partition between the phase and the fracture insulation board, and can prevent the internal arc short circuit accident.

  • With a unique valve structure, after the load switch is opened, the valve will automatically isolate the fracture, and the protection performance is good.

  • There is a reliable mechanical locking device between the load switch and the ground switch and the fuse, which meets the requirements of "five defenses".

  • It has two forms of manual operation and electric operation of AC and DC dual operation power supply, which is convenient to realize the "three remote" requirements of power system.

Product Parameters

 

NameUnitData
Rated voltageKV12
Rated frequencyHz50
Rated current A630
Rated insulation level 1min power frequency withstand voltagePhase to phase, to earthKV42
Isolation fracture48
lightning impulse withstand voltage (peak) Phase to phase, to earth75
Isolation fracture85
Rated short-time withstand currentLoad switchKA20
earthing switch20
Rated short-circuit durationLoad switchS4
earthing switch2
Rated short-circuit closed current(peak)KA50
Rated breaking current active load breaking currentA630
closed-loop breaking current630
5% active load breaking current31.5
cable charging current10
capacity of no-load transformer for breakingKVA1250
Rated short-circuit breaking current(Current limiting fuse) KA-
Rated transfer currentA-
Mechanical lifetimes2000
The impactor outputs energyJ-

Certifications

 