SCB(9 ) SCB(10)
Three
Transformer
JSM
Export Wooden Packing
IEC60076 GB/6450-1986 GB/T 10228-1997
China
Product Description
1) 23 years' manufacturing experience with three subsidiaries
2) Welcome customized products
3) CHT and HIT (The Container Port) supplier in Hongkong
2) Welcome customized products
3) CHT and HIT (The Container Port) supplier in Hongkong
Technical Data of 33kV, 35kV SCB(9) SCB(10)Cast Resin F Insulation Class Dry Type Power Transformer | |||||||||||||||||
Loss(kW) | Insulation Level | Weight (kg) | Outline Dimension (mm) | Outline dimension with protective casing | |||||||||||||
Rated Capacity | Voltage Group(kV) | Connection | (120) | No-load current | Impedance Voltage | (L) | (W) | (H) | (L) | (W) | (H) | ||||||
(kVA) | HV | LV | No-load | Load | % | % | |||||||||||
50 | 0.5 | 1.5 | 2.8 | 610 | 1000 | 870 | 1160 | 1700 | 1400 | 1330 | |||||||
100 | 0.7 | 2.2 | 2.4 | 915 | 1100 | 870 | 1350 | 1800 | 1400 | 1500 | |||||||
160 | 0.88 | 2.96 | 1.8 | 1200 | 1500 | 870 | 1380 | 2200 | 1500 | 1600 | |||||||
200 | 0.98 | 3.5 | 1.8 | 1400 | 1530 | 870 | 1420 | 2250 | 1500 | 1650 | |||||||
250 | 1.1 | 4 | 1.6 | 1600 | 1550 | 870 | 1450 | 2300 | 1500 | 1700 | |||||||
315 | 1.31 | 4.75 | 1.6 | F/F | 1800 | 1580 | 870 | 1550 | 2300 | 1600 | 1800 | ||||||
400 | 33 | Dyn11 | 1.53 | 5.7 | 1.4 | 2200 | 1740 | 870 | 1710 | 2450 | 1600 | 1950 | |||||
500 | ~ | 0.4 | Yd11 | 1.8 | 7 | 1.4 | 6 | 2500 | 1740 | 870 | 1900 | 2450 | 1600 | 2100 | |||
630 | 38.5 | Yyn0 | 2.07 | 8.1 | 1.2 | 2900 | 1860 | 870 | 1980 | 2550 | 1700 | 2250 | |||||
800 | 2.4 | 9.6 | 1.2 | 3500 | 1860 | 870 | 2180 | 2550 | 1700 | 2400 | |||||||
1000 | 2.7 | 11 | 1 | 4200 | 1900 | 1120 | 2265 | 2600 | 1800 | 2500 | |||||||
1250 | 3.15 | 13.4 | 0.9 | 4900 | 1950 | 1120 | 2355 | 2650 | 1800 | 2600 | |||||||
1600 | 3.6 | 16.3 | 0.9 | 5800 | 2000 | 1120 | 2380 | 2700 | 1800 | 2650 | |||||||
2000 | 4.25 | 19.2 | 0.9 | 6600 | 2100 | 1120 | 2480 | 2800 | 1800 | 2700 | |||||||
2500 | 4.95 | 23 | 0.9 | 7500 | 2200 | 1120 | 2550 | 2900 | 1800 | 2800 | |||||||
(Note): (Tapping range of high voltage) ± 5%; ± 2× 2.5%, Frequency: 50Hz. |