VL17-63 2P
Low Voltage Circuit Breakers
Electric Type
Normal Type Circuit Breaker
Air
Fixed
ELCB
2
Circuit Breaker
Conventional Circuit Breaker, RCCB
ISO9001-2000, CE, CCC
Yes
VeKON
Carton
2P
China
8536300000
Product Description
2P 4P 30mA 100mA 300mA 16A 25A 32A 40A 63A ELCB RCCB Residual Current Device Circuit Breaker RCD








General Introduction
Function
VL17-63 series RCCB(without overcurrent protection)applies to AC 50Hz, rated voltage 240V 2 poles, 415V 4 poles, rated current up to 63A. When electric shock occurs to human or leakage current in grid exceeds stipulated values, RCCB cuts off the fault power in a very short time to protect the safety of human and electrical equipments. It can also function as non frequently switching of circuits.
Application: Industry and commercial buildings, high-rise buildings and residential houses, etc.
Conforms to standard: IEC/EN 61008-1
Main parameters
Overall and mounting sizes(mm)

Main parameters
Types | Values |
Rated voltage Un | 240V~1P+N,415 V~3P+N |
Rated current In | 16A,20A,25A,32A,40A,50A,63A |
Rated residual operated current I△n | 0.03A,0.1A,0.3A |
Poles | 1P+N, 3P+N |
Duty type as per DC component | AC, A |
Rated limited short circuit current Inc | 6000A |
Rated limited residual short circuit current I△c | 6000A |
Rated making and breaking capacity Im | 500A(In≤50A), 630A(In=63A) |
Rated residual making and breaking capacity I△m | 500A(In≤50A), 630A(In=63A) |
Rated residual non-operated current I△no | 0.5I△n |
Rated insulation voltage Ui | 500V |
Rated impulse withstand voltage Uimp | 4000V |
Tightening torque | 3.0N.m |
Electrical life | 1000 times |
Mechanical life | 2000 times |
Operated ambient temperatureºC | -25~+40 |
Stored ambient temperatureºC | -25~+70 |
Pollution level | 2 |
Protection level | IP20 |
Mounting type | 2 |
Overall and mounting sizes(mm)