AC 800V, 1000V, 1140V BAW5hu, Molded Case Circuit Breaker, MCCB, Breaker switch, Wind Engergy MCCB, PV AC Molded Case Circuit Breaker

Price $200.00 Compare
Min Order 500 Pieces
Shipping From Zhejiang, China
Popularity 281 people viewed
Quantity
+-
 

Yueqing Yisi Electric Co., Ltd.

VIP   Audited Supplier 7 years
Profile Certified by SGS/BV
BAW5HU
High Voltage Circuit Breakers
Manual Type
High-Speed Circuit Breaker
Air
Fixed
MCCB
3
Circuit Breaker
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection, OVP(Overvoltage Protection)
ISO9001-2000, CE, CB
TELEHAN
Carton Box
China
8536200000
Product Description
AC 800V, 1000V, 1140V BAW5HU, Molded case circuit breaker, MCCB, Breaker siwtch,  Wind engergy MCCB, PV AC molded case circuit breaker 
Application:
BAW5HU series high-voltage circuit breakers (hereinafter referred to as circuit breakers) are used in high-voltage power grid circuits with rated voltages of 800V, 1000V, 1140V, and rated operating currents of 63A to 800A. This circuit breaker has overload and short circuit instantaneous protection functions, used to distribute electrical energy and protect lines and power equipment from overload, short circuit, and other fault hazards.

Working Conditions and Installation:
Altitude:
The altitude of the installation site shall not exceed 2000m;

Ambient temperature:
The allowable ambient temperature is not higher than+70C and not lower than - 45C; (If the capacity is reduced by more than+40, the details must be negotiated with the manufacturer);

Atmospheric conditions
When the ambient temperature is 40C, the relative humidity of the atmosphere does not exceed 50%, and higher relative humidity is allowed at lower temperatures;
For example, 90% at 20C, taking into account the condensation on the product surface due to temperature changes;

Class of pollution: Class 3
Installation Category: III
Magnetic field for installation:
1, The magnetic field at the installation position shall not exceed 5 times than the geomagnetic field in any direction;
2, In a medium without explosion risk, and without gas and conductive dust sufficient to corrode metal and damage insulation;
3, Where there is no wind or snow erosion:

Installation conditions
Can be installed horizontally and vertically;
The installation site should be free of significant impact and vibration, and should not be installed in flammable and explosive places.

Technical Details:
ModelBAW5HU
Breaker Current Frame250315400630800
Rated Current(A) In63 80 100 125 160 180 200 225 250280 300 315225 250 315 350 400400 500 630630 700 800
Rated Voltage(V) UeAC 800AC 1000AC 1140AC 800AC 1000AC 1140AC 800AC 1000AC 1140AC 800AC 1000AC 1140AC 800AC 1000AC 1140
Rated Insulation Votage(V) Ui1150
Rated Impulse withstand Voltage(KV) Uimp12
Rated Limit Short Current Breaking Capacity(KA) Icu502015502015502015502015502015
Rated Short Current Breaking Capacity(KA) Ics35151535151537.5151537.5151537.51515
Isolation FunctionYES
Using Cartegry Cat.A
Mechanism Life (times)200004000
Electrical Life (times)15001000
Arcing Distance(mm)>50>100>50
Overview Dimension(mm)200*107*135270*182*156
Environment Temperature(C)40

Model&Spec.OVER DIMENSION(MM)INSTALLATION DIMENSION
LWHL1L2W1H1H2ab4-φd
BAW5HU-25020010713510.59.522982635160φ4
BAW5HU-315
BAW5HU-4002701821561818411182958200φ7
BAW5HU-630
BAW5HU-800

BAW5HU seriers MCCB installation section area:
Current(A)6380100125/140160180/200/225250280/300/315350/400500/630700/800
Section Area(mm2)16253550709520x520x5x240x540x840x5x2




 
Model&Spec.DISTANCE (MM)
ABCDEFGHIJ4-φd
BAW5HU-25030303030188138028094532-φ4.5
BAW5HU-315
BAW5HU-400303030301851350320118604-φ4.5
BAW5HU-630
BAW5HU-800
Produnction Line Display:


Shippment  and Payment:


 
Brand Strategy:


Message Type
* Message Content
* Name  
* Phone
* Email
* CAPTCHA