XBD-L KYK
Cast Iron
Single-stage Pump
Booster Pump
Electric
Electric Pump
Fire Pump
Clarified Water Pump, Fire Pump
Mechanical Pump
Water Transfer
Automatic Pump
Centrifugal Pump
5-140L/S
0.3 1~1.5mpa
0.75-1 60kw
Dn25-Dn200mm
KAIYUAN
Wood Case
ISO9001, SGS
Shanghai China
8413810090
Product Description
XBD-L Fire Pump With KYK Control Panel
Product overview:
XBD-L vertical single stage fire pump is used to deliver non-grain clean water and fluids similar with water in physiochemical property. It is mainly used for pressuring water supply in fire system; Also it can be used for water drainage in factories and mines.
1. It is low cost with attractive outlook. Its vertical structure guarantees that it is less space demand and the gravity point is in the center of the pump legs, which improves the performance more smooth and longer service life.
2. The suction inlet and the discharge opening are at the same level, which simplifies the installation of the pipelines.
3. The pump head range can be changed by cutting the pump impeller to meet the special needs. There is no need to change the installation area, as easier as the KYL.
Parameters:
Flow range of the medium fluid: 5-140L/S
Pressure range: 0.3 1~1.5mpa
Motor power range: 0.75-1 60kw
Inlet/outlet caliber: Dn25-dn200mm
Model Meaning:
XB: Fire pump mark of engineering-oriented application
D: Fire pump mark of electric-driven engine
4.9: Fire pump mark of working pressure (mpa)
25: Fire pump mark of flow (L/S)
100: Fire pump mark of caliber (mm)
L: Fire pump mark of vertical position


Product overview:
XBD-L vertical single stage fire pump is used to deliver non-grain clean water and fluids similar with water in physiochemical property. It is mainly used for pressuring water supply in fire system; Also it can be used for water drainage in factories and mines.
1. It is low cost with attractive outlook. Its vertical structure guarantees that it is less space demand and the gravity point is in the center of the pump legs, which improves the performance more smooth and longer service life.
2. The suction inlet and the discharge opening are at the same level, which simplifies the installation of the pipelines.
3. The pump head range can be changed by cutting the pump impeller to meet the special needs. There is no need to change the installation area, as easier as the KYL.
Parameters:
Flow range of the medium fluid: 5-140L/S
Pressure range: 0.3 1~1.5mpa
Motor power range: 0.75-1 60kw
Inlet/outlet caliber: Dn25-dn200mm
Model Meaning:
XB: Fire pump mark of engineering-oriented application
D: Fire pump mark of electric-driven engine
4.9: Fire pump mark of working pressure (mpa)
25: Fire pump mark of flow (L/S)
100: Fire pump mark of caliber (mm)
L: Fire pump mark of vertical position


Model | Capacity Q(L/s) | Pressure P(MPa) | Speed (r/min) | Power N(kW) | Eff. η(%) | NPSH r(mm) | Weight kg |
XBD3.2/5-65L-160 | 5 | 0.32 | 2900 | 4 | 61 | 2.5 | 76 |
XBD5.0/5-65L-200 | 5 | 0.5 | 2900 | 7.5 | 56 | 2.5 | 108 |
XBD6.0/5-65L-250B | 5 | 0.6 | 2900 | 7.5 | 56 | 2.5 | 170 |
XBD8.0/5-65L-250 | 5 | 0.8 | 2900 | 15 | 48 | 2.5 | 179 |
XBD3.2/10-80L-160 | 10 | 0.32 | 2900 | 7.5 | 69 | 3 | 104 |
XBD5.0/10-80L-200 | 10 | 0.5 | 2900 | 15 | 65 | 3 | 176 |
XBD6.0/10-80L-250B | 10 | 0.6 | 2900 | 15 | 60 | 3 | 185 |
XBD8.0/10-80L-250 | 10 | 0.8 | 2900 | 22 | 57 | 3 | 239 |
XBD4.4/15-80L-200A | 15 | 0.44 | 2900 | 11 | 65 | 3 | 115 |
XBD6.0/15-80L-200B | 15 | 0.6 | 2900 | 7.5 | 58 | 3 | 185 |
XBD7.0/15-80L-250A | 15 | 0.7 | 2900 | 18.5 | 60 | 3 | 240 |
XBD8.0/15-80L-315A | 15 | 0.8 | 2900 | 30 | 53 | 3 | 340 |
XBD2.8/20-100L-160A | 20 | 0.28 | 2900 | 11 | 74 | 3 | 180 |
XBD4.4/20-100L-200A | 20 | 0.44 | 2900 | 18.5 | 72 | 3 | 215 |
XBD7.0/20-100L-25OA | 20 | 0.7 | 2900 | 30 | 66 | 3 | 330 |
XBD8.0/20-100L-315C | 20 | 0.8 | 2900 | 37 | 63 | 4.5 | 385 |
XBD3.2/25-100L-160 | 25 | 0.32 | 2900 | 15 | 74 | 4 | 190 |
XBD5.0/25-100L-200 | 25 | 0.5 | 2900 | 22 | 72 | 4 | 246 |
XBD6.0/25-100L-250B | 25 | 0.6 | 2900 | 30 | 67 | 4 | 330 |
XBD8.0/25-100L-250 | 25 | 0.8 | 2900 | 37 | 76 | 5 | 345 |
XBD3.2/40-125L-160 | 40 | 0.32 | 2900 | 22 | 75 | 5 | 264 |
XBD5.0/40-125L-200 | 40 | 0.5 | 2900 | 37 | 73 | 5 | 395 |
XBD6.0/40-125L-250B | 40 | 0.6 | 2900 | 37 | 75 | 5 | 430 |
XBD8.0/40-125L-250 | 40 | 0.8 | 2900 | 55 | 74 | 5 | 581 |
XBD3.2/50-150L-315 | 50 | 0.32 | 1480 | 30 | 77 | 3.5 | 411 |
XBD5.0/50-150L-400 | 50 | 0.5 | 1480 | 45 | 75 | 3.5 | 490 |
XBD3.2/100-200L-315 | 50 | 0.32 | 1480 | 30 | 75 | 3.5 | 418 |
XBD5.0/100-200L-400 | 100 | 0.5 | 1480 | 75 | 75 | 3.5 | 491 |