1kVA, 2kVA, 3kVA, DC 48V to AC 220 / 230 V Telecom Power Inverter

Price $600.00 Compare
Min Order 1 Piece
Shipping From Shandong, China
Popularity 435 people viewed
Quantity
+-
 

Qingdao Powtech Electronics Co., Ltd.

VIP   Audited Supplier 17 years
Profile Certified by SGS/BV
TI -1000, TI-2000, TI-3000
Active Inverter
CCC, ISO9001, RoHS, CE, SAA
>500W
off-Grid Inverter
Single
Full-Bridge Type
Sine Wave Inverter
DC/AC Inverters
-48VDC
-40~-58VDC
220VAC, 1phase
True Sine Wave
1kVA-5kVA
2u
Electric Power
Telecom
450*430*90mm/90mm
JETPOWER
Plywood Case
CE
China
85044030
Product Description
 1kVA, 2kVA, 3kVA, DC 48V to AC 220 / 230 V Telecom Power Inverter



48VDC inverter Features:
(1) Pure sine wave output
(2) High efficiency conversion
(3) Primary DC input and secondary AC input available
(4) Tower or rack-mount convertible
(5) 2U height design
(6) High power, Low profile
(7) Advanced Microprocessor control
(8) Design Provides High Reliability and Efficiency
(9) Over load protection and alarm
(10) Low audible noise: < 55 dB
(11) EMI meet VDE0871 Class A
(12) RS 232 communication
(13) MTBR<1hrs
(14) Dry Contact alarm interface
(15) Fax/ Modem surge Suppression ports
(16) RJ45 Network surge suppression ports


Product images





Specifications for TI Series Inverter (1-8K)
ModelTI-1000TI-2000TI-3000
StructureLow Frequency SPWM
Capacity1kVA / 0.7kW2kVA / 1.4kW3kVA / 2.1kW 
DC Input
Normal voltage-48Vdc
Voltage range-40~-57Vdc
Wide band noise current<10%
Psophometric noise  current<2‰  
AC Bypass Input (Optional)
Normal voltage115V/230Vac230Vac
Voltage range80~135Vac160~270Vac
160~270Vac
Frequency range50/60Hz±5%
Output
Normal voltage115V/230Vac230Vac
Voltage Stability±2%(Typical)
Frequency stability 
Wave styleSine Wave
Overload Capacity110~150% for 20sec ; >150% Protect at once
Indicators
LCD Front panel Battery capacity;Output voltage ;Load size .
 Audible AlarmsBattery low, overload, abnormity
Communications
Intelligent InterfaceRS232 and contact closure signal or RS485
Compatible O/SWindows XP/NT,Linux,Novell,Unix,SNMP,HTTP
Safety Meet UL 1012,EN 60950,EN 50091-1-1
EMIMeet FCC Part 15,Class A
EN 55022,Class A/EN 50091-2,Class A
EMCIEC 801-1,2,3,4,5/EN 61000-4-1,2,3,4,5
Environment
Ambient Operation3000 Meters Max,0~40ºC,0~95% Humidity ( Non-Condensing )
Audible noise (1 meter from surface )<45dB<60dB
Physical
Size (D×W×H )mm450×430×90
Net Weight15kg20kg24kg