11kV 12kV 15kV 24kV 25kV 250A EPDM Silicone Rubber Dead Break Screened Elbow Straight Separable Connector (Interface A)

Price $1.20 Compare
Min Order 1 Piece
Shipping From Guangdong, China
Popularity 342 people viewed
Quantity
+-
 

United Electric Co., Ltd.

VIP   Audited Supplier 5 years
Profile Certified by SGS/BV
CB20, CBZ20, EILT24, EELT24
Type A (EN50181)
10kV, 20kV
250A
Compression Type
Silicone Rubber, EPDM
Yes
GCA
Carton Box
China
8546900000
Product Description

EPDM / Silicone Rubber 24kV 250A Dead Break Screened Separable Connector(Interface A)
 

Interface A bushing (250A)
CB20-250 is made of silicone rubber, suit for connecting with type A bushing as described by CENELEC EN 50180, 50181 and DIN 47636.
CB20-250 Silicone Rubber Straight Connector 
The screened separable elbow connector CB20-250 is designed to connect the polymeric cable to transformers, switchgears, other equipment.
CBZ20-250 Silicone Rubber Elbow Connector
The screened separable straight connector CBZ20- 250 is designed to connect the polymeric cable to transformers, switchgears, other equipment.

 


Selection guide
 
Product type and size for diameter over XLPE insulation Ø (mm) Suitable cable size (sq.mm)
Um=12kV cable Um=17.5kV cable Um=24kV cable Um=36kV cable
Size 1 Ø17~Ø22 70~120 35~70 25~50  
Size 2 Ø22~Ø26 150~185 95~150 70~120 25~50
Size 3 Ø26~Ø29 240 185~240 150~185 70~95


Technical Data
 
Test Item Test value
AC voltage withstand 54kV, 5min
AC voltage withstand 30kV, 15min
Partial discharge 20kV, ≤10pC
Heating cycles voltage test 30 cycles in air, 30 cycles under water at 95-100°C, 30kV
Thundering impulse voltage withstand 125kV at 10 positive and 10 negative
Disconnect / connect Five complete operations, no visible damage to contact
Screen resistance Not exceed 5000Ω
Thermal short-circuit test No visible deterioration at 12.2kA, 2s
Dynamic short-circuit test No visible deterioration at 44.3kA, 60ms
Type test was performed in Quality Inspection and Test Center for Equipment of Electric Power (in Wuhan), which is accredited in accordance with ISO/IEC17025 General Requirements for the Competence of Testing and Calibration Laboratories. Type test reference standard: IEC60502-4:2005.


EPDM 24kV 250A Dead Break Screened Straight Separable Connector  (Interface A)

• EILT24-250-1 EPDM Straight Connector is screened separable in-line connector made of EPDM rubber, designed to connect the polymeric cable to transformers, switchgears, cable branch box and other equipment.
• Rated current 250A, for max. voltage up to 24kV.
• The connected bushing is type A, the interface designed according to DIN 47636, CENELEC EN 50180, EN 50181, IEC 60137.
• Electrical specification according to standard of IEC 60502-4, CENELEC HD 629.1 S2. Each separable connector is tested for AC withstand and partial discharge prior to leaving the factory.
• EELT24-250-1 EPDM Elbow Connector is screened separable elbow connector made of EPDM rubber, designed to connect the polymeric cable to transformers, switchgears, cable branch box and other equipment.
• Rated current 250A, for max. voltage up to 24kV.



• EILT24-250-1 
Product type and size
 
for diameter over XLPE insulation Ø (mm)
 
Suitable rated voltage and recommended cable conductor size
Um=17.5kV, (sq.mm) Um=24kV, (sq.mm)
EILT24-250-1, Size 1 Ø16.8~Ø19.2 35, 50 35
EILT24-250-1, Size 2 Ø19.7~Ø22.5 70 50
EILT24-250-1, Size 3 Ø21.5~Ø24.6 95, 120 70, 95
EILT24-250-1, Size 4 Ø23.9~Ø27.3 150 120
EILT24-250-1, Size 5 Ø26.2~Ø28.1 185 150
 

• EELT24-250-1
Product type and size
 
for diameter over XLPE insulation Ø (mm)
 
Suitable rated voltage and recommended cable conductor size
Um=17.5kV, (sq.mm) Um=24kV, (sq.mm)
EELT24-250-1, Size 1 Ø16.8~Ø19.2 35, 50 35
EELT24-250-1, Size 2 Ø19.7~Ø22.5 70 50
EELT24-250-1, Size 3 Ø21.5~Ø24.6 95, 120 70, 95
EELT24-250-1, Size 4 Ø23.9~Ø27.3 150 120
EELT24-250-1, Size 5 Ø26.2~Ø28.1 185 150
 

Technical data
 
Test Item Test value
AC voltage withstand 54kV, 5min
AC voltage withstand 30kV, 15min
Partial discharge 20kV, ≤10pC
Heating cycles voltage test 30 cycles in air, 30 cycles under water at 95-100°C, 30kV
Thundering impulse voltage withstand 125kV at 10 positive and 10 negative
Disconnect / connect Five complete operations, no visible damage to contact
Screen resistance Not exceed 5000Ω
Thermal short-circuit test No visible deterioration at 12.2kA, 2s
Dynamic short-circuit test No visible deterioration at 44.3kA, 60ms

 




Message Type
* Message Content
* Name  
* Phone
* Email
* CAPTCHA