UEHMVX
Insulated
Solid
Underground, Transformer
Copper, Aluminum
Plastic
Polymeric
ISO9001, RoHS, VDE, Kema, Enel
Gca / United Electric
35-630mm2
Copper Wire, Copper Tape
3
GCA / United Electric
Carton Box
China
8546900000
Product Description
Medium Voltage Heat Shrinkable Outdoor Termination kits up to 36kV for polymeric insulated cable
Suitable for 1-core, 3-core polymeric insulated cable with or without
armour. Rated voltage comply with IEC 60183 and CELENEC HD 629.1 S2, HD 629.2 S2. Such as 3.6/6(7.2)kV, 3.8/6.6(7.2)kV, 6/10(12)kV, 6.35/11(12)kV, 8.7/15(17.5)kV, 12/20(24)kV, 12.7/22(24)kV, 18/30(36)kV, 19/33(36)kV.
• We adopt the same design for the products of 24kV and below rated voltage.
• Consists of indoor & outdoor termination for polymeric insulated cable.
• Wide range of conductor cross section is available.
• Excellent electrical stress release property achieved by heat shrinkable stress control tubing at the screen cut.
• High electrical insulation value and unrestricted shelf life.
• Water & moisture proof and good mechanical strength.
• Good resistance against UV-radiation and chemicals.
• Quick and easy installation.
• Outstanding environmental resistance & good performance in polluted area.
• The products are fully in accordance with IEC 60502-4, CELENEC HD 629.1 S2, HD 629.2 S2 and other standards such as BS, DIN and VDE.
armour. Rated voltage comply with IEC 60183 and CELENEC HD 629.1 S2, HD 629.2 S2. Such as 3.6/6(7.2)kV, 3.8/6.6(7.2)kV, 6/10(12)kV, 6.35/11(12)kV, 8.7/15(17.5)kV, 12/20(24)kV, 12.7/22(24)kV, 18/30(36)kV, 19/33(36)kV.
• We adopt the same design for the products of 24kV and below rated voltage.
• Consists of indoor & outdoor termination for polymeric insulated cable.
• Wide range of conductor cross section is available.
• Excellent electrical stress release property achieved by heat shrinkable stress control tubing at the screen cut.
• High electrical insulation value and unrestricted shelf life.
• Water & moisture proof and good mechanical strength.
• Good resistance against UV-radiation and chemicals.
• Quick and easy installation.
• Outstanding environmental resistance & good performance in polluted area.
• The products are fully in accordance with IEC 60502-4, CELENEC HD 629.1 S2, HD 629.2 S2 and other standards such as BS, DIN and VDE.

Features
• Joints & Splice Technology: Heat Shrink
• Power Cable Termination Voltage Class(kV): ≤ 36
• Cable Shield Style: Copper wire, copper tape
• Insulation: Polymeric
• Number of Cores: 1, 3
• Application Type: Outdoor
• Industry Standards: Design Specification GB/T 12706.4, IEC 60502-4
Main components
(Following can be selected respectively to meet your local technical requirements)
Stress control tubing, Anti-tracking tubing, Lug sealing tubing, Anti-tracking rain sheds, Anti-tracking breakout (black or red), Filler mastic, Stress release mastic, Sealing mastic, Silicone grease, Phase color, Cleaning tissue, Solder & solder flux, Copper braid, Copper binding wire, Abrasive paper, Gloves, Roll spring, Jubilee clip, Armour clip, Armour support ring, Installation instruction.
Aluminum or Copper or Bi-metal lug, Support insulator, Tee bracket can be supplied as specification respectively.
Specification


Technical Data
Test item | Voltage Um (kV) | Result | ||||
7.2 | 12 | 17.5 | 24 | 36 | ||
D.C. voltage dry withstand,15min | 23 | 38 | 52 | 78 | 125 | No failure or flashover |
A.C. voltage dry withstand,5min | 17 | 28.5 | 39 | 57 | 93.6 | No breakdown or flashover |
A.C. voltage wet withstand,1min | 15 | 25.5 | 35 | 51 | 83 | No breakdown or flashover |
Partial discharge at ambient temperature | 6.5 | 11 | 15 | 22 | 36 | <5pC |
Impulse voltage at elevated temperature (10 positive and 10 negative 1.2/50μs) | 60 | 95 | 95 | 125 | 200 | No breakdown or flashover |
Heat cycling in air, 3 cycles 5hrs heating, 3hrs cooling, at 95°C | 9.5 | 16 | 23 | 32 | 52 | Pass |
Partial discharge at elevated and ambient temperature | 6.5 | 11 | 15 | 22 | 36 | <5pC |
Heat cycling in air, 113 cycles 5hrs heating, 3hrs cooling, at 95°C | 9.5 | 16 | 23 | 32 | 52 | Pass |
Partial discharge at elevated and ambient temperature | 6.5 | 11 | 15 | 22 | 36 | <5pC |
Impulse voltage at elevated temperature (10 positive and 10 negative 1.2/50μs) | 60 | 95 | 95 | 125 | 200 | No breakdown or flashover |
A.C. voltage dry withstand 15min | 9.5 | 16 | 23 | 32 | 52 | No breakdown or flashover |
Salt fog, 1000h | 5.0 | 8 | 11 | 16 | 26 | No failure or flashover |