HWL20-3#
Construction, Overhead, Underground, Industrial, Power Station
High Voltage Cable
DC & AC
XLPE
PVC
Round Wire
Copper or Aluminium
KEMA, Enel, ENDESA
HWL20-3#
United Electric/GCA
25-800 sq. mm2
Copper Wire, Copper Tape
3
Armored and Unarmored Cable
IEC60502-4
CENELEC HD629
IEEE-48
26mm-33mm
GCA / United Electric
Carton Box
HWL20-3#
China
8546900000
Product Description
Medium Voltage Cold Applied Outdoor Termination for up to 52kV for XLPE Cable





Features
• Power Cable Termination Technology: Stress Cone
• Power Cable Termination Voltage Class(kV): ≤ 42
• Cable Shield Style: Copper wire, copper tape
• Number of Cores: 1, 3
• Application Type: Indoor
• Industry Standards: Design Specification GB/T 12706.4, IEC 60502-4
Characteristics
• Easy/convenient installation: Stress cone wholly composed inside the silicone rubber body greatly releases the electric stress at the screen cut edge. Pre-expanding with removable plastic spiral tube inside, the elastic silicone rubber body will shrink automatically and tightly onto the needed position by removing the plastic spiral tube without heating or special tools.
• Reliable insulation: Adopting Germany liquid silicone rubber, serving the utilities and industry successfully for 20 years.
• Superior moisture sealing: Triplex sealing design and hydrophobic performance of silicone rubber ensure environmental stability.
• Safety for installing fault: Considerate design reduces the incidence of installing faults which likely occur.
• Wide usage: Possessing a series of superior performances, the cold shrink accessories can be widely used in various regions, especially fire forbidden area, high sea level, cold weather, high-humidity, salt-fog and heavy polluted regions.
Specification
Voltage | Cable cores | Cable conductor size (mm2) | Suitable insulation dia. range (mm) |
12/20(24)kV and below | 1-core or 3-core | 25-800 | 15-49 |
18/30(36)kV | 1-core or 3-core | 35-630 | 23-49 |
26/35(40.5)kV | 1-core or 3-core | 50-800 | 31-57 |
Technical Data
Test item | 12/20(24)kV | 18/30(36)kV | 26/35(40.5)kV |
A.C. voltage withstand test | No flashover, no breakdown at 54kV for 5min. | No flashover, no breakdown at 81kV for 5min. | No flashover, no breakdown at 117kV for 5min. |
Partial discharge test | 20kV, <10pC | 30kV, <10pC | 45kV, <10pC |
Heating cycles voltage test | 60 cycles at the temperature of 95-100°C, 30kV | 60 cycles at the temperature of 95-100°C, 45kV | 60 cycles at the temperature of 95-100°C, 65kV |
Impulse voltage withstand test at 95-100°C | No flashover, no breakdown at 10 positive and 10 negative impulses at 125kV | No flashover, no breakdown at 10 positive and 10 negative impulses at 170kV | No flashover, no breakdown at 10 positive and 10 negative impulses at 200kV |
15min, A.C. voltage withstand test | 30kV, 15min. no flashover, no breakdown | 45kV, 15min. no flashover, no breakdown | 65kV, 15min.no flashover, no breakdown |













