LF5A/LF8A/LF10A/LF12A/LF15A/LF20A/LF25A/LF30A/LF40
1 Year
1 Year
Air-Cooled
Air-cooled
Integral
380V/50HZ
1
Ultra Quiet
Plastic
Combination machine
New
Japan Panasonic
Emerson
German Siemens
BEIERMAN
Wooden Case
Zhangjiagang, China
847780000
Product Description
Product Pictures




Product Description
Model Features
1.No need to fit the cooling tower.
2.Japan Panasonic compressor, high efficiency, low noise, quiet operation.
3.Emerson imported refrigeration parts.
4.Electrical parts are German SIEMENS genuine, to ensure stable operation of the machine.
5.Take a large capacity condenser and heat it can run easily.
6.Minimize floor space and ease of installation.
7.All pipe insulation design, to prevent local convection of the pipeline.
8.Finned condenser, better heat transfer, faster heat dissipation.
9.Box type evaporator is provided with an automatic water replenishing device.
10.Our company is based on high product quality, and developing on in-novative technology.
Pay attention to the development of new productsand new technologies. Continue to enhance the quality of products,reduce costs to meet the needs of the market.
Safety System
1.Compressor Overload Protection
2.Pump Overload Protection
3.Heat-Exchange Fail Protection
4.Refrigerant Safety Valve
5.Freeze Protection
6.High Pressure Protection
7.Low Pressure Protection
8.Phase Failure Protection
9.Buzzer
Technical Data












Model Features
1.No need to fit the cooling tower.
2.Japan Panasonic compressor, high efficiency, low noise, quiet operation.
3.Emerson imported refrigeration parts.
4.Electrical parts are German SIEMENS genuine, to ensure stable operation of the machine.
5.Take a large capacity condenser and heat it can run easily.
6.Minimize floor space and ease of installation.
7.All pipe insulation design, to prevent local convection of the pipeline.
8.Finned condenser, better heat transfer, faster heat dissipation.
9.Box type evaporator is provided with an automatic water replenishing device.
10.Our company is based on high product quality, and developing on in-novative technology.
Pay attention to the development of new productsand new technologies. Continue to enhance the quality of products,reduce costs to meet the needs of the market.
Safety System
1.Compressor Overload Protection
2.Pump Overload Protection
3.Heat-Exchange Fail Protection
4.Refrigerant Safety Valve
5.Freeze Protection
6.High Pressure Protection
7.Low Pressure Protection
8.Phase Failure Protection
9.Buzzer
Technical Data
Model | LF5AH | LF8AH | LF10AH | LF12AH | LF15AH | LF20AH | LF25AH | LF30AH | LF40AH | LF50AH | ||
Cooling Capacity | kw/h | 50Hz 60Hz | 13 16 | 21 25 | 26 31 | 30 36 | 42 50 | 55 66 | 60 71 | 84 100 | 111 133 | 119 143 |
kcal/h | 50Hz 60Hz | 11180 13760 | 18060 21500 | 22360 26660 | 25800 30960 | 36120 43000 | 47300 56760 | 51600 61060 | 72240 8600o | 95460 114380 | 102340 122980 | |
Input Power | kw | 6 | 10 | 12 | 16 | 20 | 23 | 33 | 41 | 48 | ||
Voltage | 3PH-38OV-5OHz(Or 200V/220V/415V50Hz/60Hz) | |||||||||||
Refrigerant | Name | R22(Or R134a/R407c) | ||||||||||
Control Method | Outside The Balanced Thermal Expansion Valve | |||||||||||
Compressor | Types | Fully Enclosed Scroll Compressor | ||||||||||
(kw) Power | 3.73 | 5.97 | 7.46 | 8.95 | 11.19 | 14.92 | 18.64 | 22.38 | 29.84 | 37.28 | ||
Evaporator | Types | Tank Coil | ||||||||||
(m/h) Chilled Water | 2.24 2.68 | 3.52 4.22 | 4.47 5.37 | 5.12 6.15 | 7.20 8.63 | 9.52 1142 | 10.25 12.29 | 14.39 17.37 | 19.05 29.86 | 20.50 24.60 | ||
(L) Water Tank | 50 | 120 | 120 | 120 | 200 | 250 | 330 | 450 | 600 | 720 | ||
Water Pipe | 1 | 1-1/2 | 1-1/2 | 1-1/2 | 1-1/2 | 2 | 2 | 2 | 3 | 3 | ||
Condenser | Types | Efficient Aluminum Finned Copper Jacket+Low Noise External Rotor Fan | ||||||||||
(m/h) AirCooling | 5000 | 8000 | 10000 | 12000 | 15000 | 20000 | 25000 | 30000 | 40000 | 50000 | ||
Pump | (kw) Power | 0.37 | 0.75 | 0.75 | 0.75 | 1.5 | 2.25 | 2.25 | 2.25 | 4 | 5.5 | |
H(m) | 20 | 22 | 22 | 22 | 24 | 30 | 30 | 30 | 40 | 52 | ||
Heating equipment | Types | Heating pipe | ||||||||||
(kw)Power | 6 | 9 | 12 | 18 | 24 | 30 | 40 | 60 | 90 | 120 | ||
Dimensions | L(mm) | 1360 | 1600 | 1570 | 1570 | 1910 | 2230 | 2230 | 2350 | 3070 | 3070 | |
w (mm) | 645 | 860 | 860 | 860 | 88o | 1100 | 1100 | 1170 | 1200 | 1200 | ||
H(mm) | 1130 | 1555 | 1580 | 1580 | 1560 | 1680 | 1680 | 1980 | 2040 | 2040 | ||
Weight | kg | 300 | 400 | 450 | 450 | 600 | 880 | 980 | 1100 | 1250 | 1400 | |
Unit Conversion | 1KW=860KCAL/HR | 1RT=3024KCAL/HR | 1BTU/HR=0.252KCAL/HR |