Power Transformer
Power transformers are a core component of power transmission system. The substation transformer used for power transmission and transformation in a unit or substation, and is also the core part of the substation. Transformers are the core equipment of the traction power supply system of electric locomotives, and also the key equipment to ensure the safe and stable operation of the traction power supply system.


Product Description
Design and Manufacture Standard ANSI-IEEE 57. 12/CSA/EN/BS/GOST/AS,IEC 600761
Design | Sealed-tank system /Inert-gas pressure system or Conservator-tank system without diaphragm On load or no load voltage tap changer
ONAN/ONAF/ODAF/OFAF/OFWF/KNAN/KNAF |
Insulation |
Mineral Oil Inhibited I Not Inhibited I Vegetable oil |
Primary voltage |
Up to 230kv, up to 900kv BIL |
Capacity |
Up to 240MVA |
Frequency |
50/60 HZ |
Operating Condition
Suitable for indoor and outdoor application.
Ambient temperature: | -50 ºC~40 ºC |
Relative humidity: | ambient air relative humidity should be below93%, |
Altitude: | ≤1000m |
Max wind speed: | ≤35 m/s |
Earthquake acceleration: | horizontal acceleration ≤0.3g |
vertical acceleration | ≤0. 15g |
Special conditions: | customized products are available. |
STANDARD FEATURES
ratings through 230 kV (900 kV BIL)
Service Location: Outdoor
Core: Regular grain-oriented; mitered cruciform with step-lap construction
Coils: Cylindrical construction; all copper windings, custom tempered per design requirements; circular windings with rectangular or continuously-transposed conductor; helical low-voltage windings; continuous disc medium-voltage windings; shielded disc high-vollage windings
Radiators: Detachable panel type with shut-off valves; mild steel
Insulating oil: mineral oil type I & typell
Tank Cover.Welded,
Bolted Manholes: On cover or tank
Tank Base: Flat bottom or Skid under base
Tank Material: Mid Steel
Frequency: 60 Hertz Winding
Tem rise: 55 ºC
HV Taps; DETC, ETC in tank or out
- Above rated volts: 2 x2- 1/2% off load taps of full capacity
-Below rated volts: 2 x 2- 1/2% off load laps of full capacity
Valve: Drain and Fiter Valves, w/Sampler
Lifting, Moving, and Jacking Facilities

Technical Data
Technical Data for 69KV Class Three Phase Two Winding OLTC Power Transformer
(KVA) Rated Power | (KV) High Voltage | (KV) Low Voltage | Connection Symbol | Short Circuit Impendence (%) | No-load Loss (KW) | On-load Loss (KW) | No load Current (%) |
10000 | 69 | 6.3 6.6 10.5 11 | YNd11 | 9 | 12.1 | 47.6 | 0.75 |
12000 | 12.6 | 56.5 | 0.53 | ||||
15000 | 15.1 | 69.5 | 0.49 | ||||
20000 | 17.9 | 84.2 | 0.49 | ||||
25000 | 21.1 | 99.5 | 0.42 | ||||
30000 | 25.1 | 120 | 0.42 | ||||
37500 | 30 | 140.3 | 0.39 | ||||
50000 | 35.4 | 174.3 | 0.39 | ||||
60000 | 42.1 | 210 | 0.39 |
Technical Data for 69KV Class Three Phase Two Winding NLTC Power Transformer
(KVA) Rated Power | (KV) High Voltage | (KV) Low Voltage | Connection Symbol | Short Circuit Impendence (%) | No-load Loss (KW) | On-load Loss (KW) | No load Current (%) |
10000 | 69 | 6.3 6.6 10.5 11 | YNd11 | 9 | 11.6 | 47.6 | 0.75 |
12000 | 13.6 | 56.5 | 0.53 | ||||
15000 | 16.3 | 69.5 | 0.49 | ||||
20000 | 19.2 | 84.2 | 0.49 | ||||
25000 | 22.6 | 99.5 | 0.42 | ||||
30000 | 26.8 | 120 | 0.42 | ||||
37500 | 31.9 | 140.3 | 0.39 | ||||
50000 | 38.6 | 174.3 | 0.39 | ||||
60000 | 44.4 | 210 | 0.39 |
Technical Data for 115KV Class Three Phase Two Winding OLTC Power Transformer
(KVA) Rated Power | (KV) High Voltage | (KV) Low Voltage | Connection Symbol | Short Circuit Impendence (%) | No-load Loss (KW) | On-load Loss (KW) | No load Current (%) |
10000 | 115 138 161 | 6.3 6.6 10.5 11 | YNd11 | 10.5 | 11.8 | 51.2 | 0.82 |
12000 | 13.7 | 59.5 | 0.82 | ||||
15000 | 16.3 | 73.1 | 0.76 | ||||
20000 | 19.5 | 88.4 | 0.76 | ||||
25000 | 22.7 | 105 | 0.69 | ||||
30000 | 27.4 | 126 | 0.69 | ||||
37500 | 32.9 | 148 | 0.63 | ||||
50000 | 38.9 | 184 | 0.63 | ||||
60000 | 46.4 | 221 | 0.57 |
Technical Data for 115KV Class Three Phase Two Winding NLTC Power Transformer
(KVA) Rated Power | (KV) High Voltage | (KV) Low Voltage | Connection Symbol | Short Circuit Impendence (%) | No-load Loss (KW) | On-load Loss (KW) | No load Current (%) |
10000 | 115 138 161 | 6.3 6.6 10.5 11 | YNd11 | 10.5 | 10.5 | 50.2 | 0.64 |
12000 | 12.4 | 59.5 | 0.64 | ||||
15000 | 15 | 73.1 | 0.59 | ||||
20000 | 17.8 | 88.4 | 0.59 | ||||
25000 | 21 | 105 | 0.54 | ||||
30000 | 25 | 126 | 0.54 | ||||
37500 | 29.9 | 148 | 0.56 | ||||
50000 | 35.3 | 178.5 | 0.52 | ||||
60000 | 41.9 | 221 | 0.48 |
Technical Data for 230KV Class Three Phase Two Winding OLTC Power Transformer
(KVA) Rated Power | (KV) High Voltage | (KV) Low Voltage | Connection Symbol | Short Circuit Impendence (%) | No-load Loss (KW) | On-load Loss (KW) | No load Current (%) |
30000 | 230 | 6.3 6.6 10.5 11 34.5 66 | YNd11 | 12 | 30 | 128 | 0.69 |
37500 | 36 | 149 | 0.63 | ||||
50000 | 43 | 180 | 0.63 | ||||
60000 | 50 | 209 | 0.57 |
Technical Data for 230KV Class Three Phase Two Winding NLTC Power Transformer
(KVA) Rated Power | (KV) High Voltage | (KV) Low Voltage | Connection Symbol | Short Circuit Impendence (%) | No-load Loss (KW) | On-load Loss (KW) | No load Current (%) |
30000 | 230 | 6.3 6.6 10.5 11 34.5 66 | YNd11 | 12 | 28 | 128 | 0.7 |
37500 | 33 | 149 | 0.7 | ||||
50000 | 39 | 180 | 0.65 | ||||
60000 | 46 | 209 | 0.65 |
Transformer Test
Winding resistance | Winding insulation resistance |
Core insulation resistance | Ratio |
Polarity and phase relation | Insulation power factor |
Control(auxiliary) cooling losses | Single-phase excitation tests |
Noload losses and excitation current | Impedance voltage and load losses |
Zero-phase sequence impedance voltage | Temperature rise |
Low frequency dielectric tests | Low frequency dielectric tests on axiliary devices |
control, and current transformer circuits | Lightning impulse |
Front of wave impulse | Swithing impulse |
Partial discharge | Audible sound level |
Operational tests (all devices) | Dissolved gases in oil |
Leak test |

Sales Record
Daelim's transformers are sold to nearly 100 countries including the United States, Canada, Mexico, Ecuador, Chile, and Australia. The picture below is part of the sales record.


DAELIM BELEFIC
Daelim Belefic builds power translormers that deliver power to the consumer efficiently and reliably.

Daelim's transformers have been exported to America, Canada, Mexico, Australia, Chile, Ecuador, Venezuela, Honduras, El Salvador, Panama and other countries. DAELIM have helped many international customers to successfully obtain transformer projects and continue to carry out in-depth cooperation.
DAELIM have 20 years of transformer export experience, moreover DAELIM have after-sales installation teams overseas, so if you also have transformer business, we can develop together.
Daelim Transformer High Quality Service
a.pre-sales
Daelim has a very serious quality control system, strictly controlling every detail from transformer design to raw material procurement, assembly, testing, packaging and delivery.
b.after sales
1.Up to 24 months quality guarantee period. If there is any problem in the operation of your transformer, Daelim's after-sales team will solve it promptly and quickly;
2.Local after-sales installation service team. Whether you are in North America, South America or other regions, Daelim's local team can provide you with professional transformer installation, commissioning, maintenance and other services;
3.Daelim provides remote video guidance for transformer installation.
Thank you for reading. If you need inquiries, please contact us.