DAM3-1000
Low Voltage Circuit Breakers
Manual Type
Normal Type Circuit Breaker
Arc Chamber
Fixed
MCCB
3
Circuit Breaker
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection
ISO9001-2000, CE, CB, CCC, RoHS
BMC Unflaming Material
Min:0.7-Max:1in
Min:5-Max:10in
CDADA, OEM, ODM
Carton
800, 1000A
Shanghai, China
8536200000
Product Description
Overview
The rated current of DAM3-1000 molded case circuit breaker can up to 1000A, it's generally used in the power distribution circuit to distribute power and protect circuit and power equipment from overloaded, short circuit, under voltage failure damage, in which alternating current 50-60Hz, rated direct-current 1000A.
Compared to the DAM1 series, the DAM3 series are designed for smaller volume, higher breaking capacity, offering better energy savings.
Electrical parameters of DAM3-1000 molded case circuit breakerRated current of frame size Inm [A] | 1000 | |||
Rated current[A] | 630 800 1000 | |||
Number of poles | 3 / 4 | |||
Rated operating voltage | (AC)50-60HZ [V] | 400/690 | ||
DC[V] | 250/1000 | |||
Rated impulse withstand voltage Uimp[KV] | 8 | |||
Rated insulation voltage Ui [V] | 750 | |||
Test voltage at industrial frequency for 1 min [V] | 3000 | |||
Rated ultimate short-circuit breaking capacity Icu [KA] | N | S | H | |
(AC)50-60HZ 220/230V [KA] | 55 | 80 | 105 | |
(AC)50-60HZ 400/415V [KA] | 36 | 55 | 70 | |
(AC)50-60HZ 690V [KA] | 15 | 20 | 25 | |
(DC)250V-2 Poles in series | 35 | 50 | 65 | |
(DC)500V-2 Poles in series | 18 | 22 | 30 | |
(DC)750V-4 Poles in series | 30 | 42 | 55 | |
(DC)1000V-4 Poles in series | 25 | 35 | 45 | |
Rated service short-circuit breaking capacity, Ics [KA] | ||||
(AC)50-60HZ 220/230V [%Icu] | 60% | 60% | 60% | |
(AC)50-60HZ 400/415V [%Icu] | 60% | 60% | 60% | |
(AC)50-60HZ 690V [%Icu] | 60% | 60% | 60% | |
Category of utilisation(EN 60947-2) | A | |||
Isolation condition | Bitmap | |||
Reference standard | IEC/EN 60947-2/GB 14048.2 | |||
Interchangeability | Bitmap | |||
Versions | Fixed | Bitmap | ||
Plug-in | Bitmap | |||
Draw-out | Bitmap |
Physical parameters of DAM3-1000 molded case circuit breaker
Endurance | Total cycles | 5000 |
Electrical endurance | 1000 | |
Mechanical endurance | 4000 | |
Basic dimensjons-fixed version | 3/4 Poies W[mm] | 210/280 |
3/4 Poies H[mm] | 108.5 | |
H1[mm] | 167 | |
3/4 Poies L[mm] | 268 |
Introduction
The DAM3-1000 molded case circuit breaker automatically cuts off the current when the current exceeds the release setting. The molded case refers to the plastic insulator used as the frame of the device to insulate the conductor and the metal grounding component.