- Altitude: ≤2000m
- Ambient temperature: -25°C~+40°C
- Relative humidity: Monthly average≤90% (25ºC);Daily average≤95%
- Vapor data: Monthly average≤1.8kPa; Daily average≤2.2kPa
- Wind speed: ≤35m/s
- No operating in such places as subject to explosives, inflammables, corrosives and severe vibration
1.Energy storage motor adopt unidirectional permanent DC motor, technical parameter as Table:
Item | ZYJ220-53-216 | ZYJ220-53-216 | ZYJ220-53-216 | ZYJ220-53-216 |
Rated operate voltage (V) | DC220 | DC110 | DC48 | DC24 |
Rated power (W) | 40 | 40 | 40 | 40 |
Normal operating voltage range | 85%-110% | 85%-110% | 85%-110% | 85%-110% |
Rated operating current(A) | 0.5 | 1.0 | 2.3 | 4.6 |
Motor energy storage time (S) | ≤8 | ≤8 | ≤8 | ≤8 |
2.Closing/Opening electromagnet adopt solenoid electromagnet, technical parameter as Table:
Rated operate voltage (V) | AC220 | AC110 | DC200 | DC110 | DC48 | DC24 |
Rated operating current(A) | 1.36 | 3.60 | 2 | 4 | 6.7 | 13 |
Rated power (W) | 299 | 396 | 440 | 440 | 320 | 320 |
Coil resistance at 20°C (Ω) | 54 | 10.3 | 106 | 27.5 | 7.2 | 2 |
Normal operating voltage range | Open at 65%~120% rated operate voltage; do not open when less than 30% rated operate voltage | |||||
Close at 80%~110% rated operate voltage; do not close when less than 30% rated operate voltage |
3.Manual energy storage is operated by the handle allocated with the mechanism, the operating force less than 100 (N.m)
4.Mechanism output angle 43 degree
5.Mechanism net weight: CTW-D: 25kg CTW-S: 20kg
6.The auxiliary switch contacts with the mechanism can pass through continuous current 10A (AC220V) and 3A (DC220V)
7.Limit switch adopt CSK11-A-33 magnetic blowout switch. The continuous current through that the contact can pass: 8A (AC380V); 3A (DC220V)