General Information
GDYD series AC/DC hipot test set is composed of manual control unit and AC/DC Dry testing transformer(HV unit) which output AC/DC voltage smoothly.Meanwhile,it has many monitoring and protection functions.
Features
- Digital display meters mounted on the panel.
- Monitoring HV side voltage, HV side current, LV side current and indicator of zero, power, working start, timing.
- Over-current protection, zero-starting protection, sound and light alarm.
- With new type time relay, time range is more wider (1S ~ 99H).
- Using the latest current relay, more accurate and reliable.
- Light weight, small size, easy to move.
Technical Specifications
A. Control unit specifications
Power | AC220V±10%,50Hz |
Capacity | 5kVA |
Output voltage | AC 0-250V |
Rated output current | 25A |
Rated current rectified range | 0-25A |
HV voltmeter range | 0-75kV Accuracy: 1.5% of the reading±1digit(F.S) |
HV ammeter range | 0-105mA Accuracy: 1.5% of the reading±1 digit(F.S) |
LV ammeter range | 0-30A Accuracy: 2.0% of the reading±1 digit(F.S) |
Timing range | 1s-99h |
Weight | 21kg |
Dimension | 440mm (L)*340mm (W)*240mm (H) |
B. Testing transformer (HV unit) specifications
LV side voltage (Input voltage) | 0-200V |
LV side current (Input current) | AC 0-25A |
HV side voltage(Output voltage) | AC 0-50kV, DC 0-70kV |
HV side current(Output current) | AC 100mA, DC 71.4mA |
Capacity | 5kVA |
HV side/LV side turns ratio | 250:1 |
Measuring voltage | AC 0-100V Accuracy: 1.5% of the reading±1 digit(F.S) |
No-load current | <10% |
Impedance voltage | <10% |
Weight | 35kg |
Dimension | 260mm(L)*240mm(W)*540mm(H) |
Working conditions
- Working place: No gas, steam, chemical dust and explosive and corrosive medium which will influence insulation.
- Environment temperature: -20--50ºC
- Environment humidity: ≤85% RH (no condensing)