Main Specification | ||||
Rated voltage | kV | 24 | ||
1minVoltage at rated power frequency | Alternate/to the ground65, fracture65 | |||
Lightning impulse withstand(peak) | Alternate/to the ground125, fracture145 | |||
Rated current | A | 630,1250 | ||
Rated frequency | Hz | 50 | ||
Rated short-circuit breaking current(peak) | kA | 20 | 25 | 31.5 |
Rated short-circuit withstand current | 50 | 63 | 80 | |
Rated peak withstand current | 50 | 63 | 80 | |
4SRated short-time withstand current | kA | 20 | 25 | 31.5 |
Rated operating sequence |
| O-0.3s-CO-180s-CO | ||
Closing time | ms | 25~60 | ||
Opening time | 18~45 |
Parameter | Unit | Value |
Rated short-circuit breaking current breaking times | Second-rate | 30 |
Mechanical life | 10000 | |
Secondary circuit1minPower frequency withstand voltage | V | 2000 |
Rated power of energy storage motor | W | 40 |
Rated voltage of energy storage motor | V | DC220,110,DC24 |
Rated closing operating voltage | AC/DC220,110;DC24 | |
Rated opening operating voltage | AC/DC220,110; DC24 | |
Motor energy storage time | S | ≤8 |
Contact Spacing | mm | 12±1 |
Overtravel | 3 ±1 | |
Phase center distance | 395 ±2 | |
Contact closing bounce time | ms | 22 |
Synchronization between three-phase switching | w2 | |
Average dividing speed | m/s | 1.1-1.7 |
Average closing speed | 0.5-1.0 | |
Main circuit resistance | μΩ | ≤100 |


1.Working temperature:-40 ºC~+60 ºC
2.Operating humidity:0-95%
3.The working environment of solar radiation:≤1.1kW/m
4.The wind speed does not exceed 35m/s(equivalent to 700pa on the cylindrical surface)
5.Pollution Level:IV grade
6.ice thickNess:≤10mm
7.seismic intensity:≤8°