3.6kV Vacuum Interrrupter Arc Extinguishing Chamber For Contactor

Price $60.00 Compare
Min Order 3 Pieces
Shipping From Hubei, China
Popularity 254 people viewed
Quantity
+-
 

Wuhan Feite Electric Co., Ltd.

VIP   Audited Supplier 5 years
Profile Certified by SGS/BV
TJ340TA(3.6kV,2000A,10kA)
Vacuum
3
High Voltage
2000A
DC/AC Vacuum Contactor
Vacuum Interrupter
20years
Silver, Copper
Yes
ISO9001-2000
Feite Brand
Pallet, Carton(Ploy Bags, Foam)
ceramic&metal components ect
China
8535900090
Product Description
Product Description

Vacuum Interrupter for Contactor

Vacuum arc extinguishing chamber, also known as vacuum switch tube, is the core component of the high voltage power switch, its main role is to cut off the arc and inhibit the electric current by its high inside insulation performance to avoid accidents.

Wuhan Feite Electric brand vacuum arc extinguishing chamber adopts a corrugated ceramic insulation shell, copper tungsten tungsten carbide alloy materials contact, using advanced one exhuast technology process makes the vacuum interrupter has the advantages of small volume, high insulating level, low closure value, long service lifetime, easy-maintenance, explosion-free, low noise, low maintenance costs, reliable operation and non-pollution etc.. The vacuum arc extinguishing chamber mainly been used in power transmission and distribution control system. It is also can be used in metallurgy, mine, petroleum, chemical industry, railway, broadcasting, communications, industrial high frequency heating power distribution system.

Wuhan Feite Electric vacuum arc extinguishing chamber for vacuum contactor rated voltage is 1.14~40.5kV, rated current is 630A~1250A



Main Technical Date--ZKTJ2500/3.6-10

Parameter itemUnitData
Rated VoltagekV3.6
Rated CurrentA2500
Rated FrequencyHz50
Rated Short-time Power Frequency Withstand Voltage(1min)KV21
Rated Lighting Impulse Withstand VoltagekV40
Rated Making CurrentkA10
Rated Breaking Current,MaxkA8.0
Rated Breaking Current,MinkA250
Rated Making Current,LimitkA10
Rated Short-time Withstand currentkA8.0
Rated Duration of Short-circuits4
Mechanical Lifetimes30000
Electricity Life AC-3times250000
Electricity Life AC-4times100000
Rated Contactl Strokemm3±0.5
Contact Closing Force Due to bellows and atmosphereN150±30
Counterforce at rated contact strokeN200±40
Circuit resistance at rated contact atmosphere forceµ≤50
Shelf lifeyear20
Contact erosion limitmm3
Weight of moving partskg≤0.8

Specifications required for matched switchgear
Parameter itemUnitData
Added contact forceN2000±100N
Average opening speedm/s0.6±0.2
Average closing speedm/s0.3±0.1
Contact Bouncing Duration at closing operationm/s≤2
Contact Bouncing Bank Amplitude of Opeing Operationmm≤2
Three-pole simultaneityms≤1

 

Company Profile

ABOUT OUR COMPANY

Wuhan Feite Electric Co.,Ltd is located at Wuhan city, Hubei Province which is the Eastcenter part of China. lt is specialized in producing vacuum interrupter and vacuumembedded poles.The company has developed 1.14KV-40.5KV vacuum switch tubes morethan 300 types,which can be widely used for various vacuum circuit breaker, vacuumcontactors, vacuum load breaker switches, auto re-closers,RMU etc.The company has full sets vacuum producing and testing equipment,with annualproduction of 600,000 vacuum tube production capacity, As an ISO09001:2008 certifiedcompany,our production process strictly conforms to quality management system.Wuhan Feite Electric Co.,Ltd is always supply you good quality products with reasonableand competitive prices.



vacuum interrupter for vacuum contactor voltage 1.14kv/3.6kv/7.2kv/12kv/24kv, rated current is 400A/630A/1250A, 10ka vacuum switchgear/vacuum circuit breaker


vacuum interrupter for vacuum contactor voltage 1.14kv/3.6kv/7.2kv/12kv/24kv, rated current is 400A/630A/1250A, 10ka vacuum switchgear/vacuum circuit breaker


3> Different Types Vacuum Interrupter and Embedded Poles
vacuum interrupter for vacuum contactor voltage 1.14kv/3.6kv/7.2kv/12kv/24kv, rated current is 400A/630A/1250A, 10ka vacuum switchgear/vacuum circuit breaker

 
Certifications

 


vacuum interrupter for vacuum contactor voltage 1.14kv/3.6kv/7.2kv/12kv/24kv, rated current is 400A/630A/1250A, 10ka vacuum switchgear/vacuum circuit breaker

Vacuum Interrupter and Embedded Poles Stock
vacuum interrupter for vacuum contactor voltage 1.14kv/3.6kv/7.2kv/12kv/24kv, rated current is 400A/630A/1250A, 10ka vacuum switchgear/vacuum circuit breaker


6> Company Introduction
vacuum interrupter for vacuum contactor voltage 1.14kv/3.6kv/7.2kv/12kv/24kv, rated current is 400A/630A/1250A, 10ka vacuum switchgear/vacuum circuit breaker
 
Packing

 

FAQ

1. Precheck before putting it into use.
Check id packing is in good condition. Check the appearance of vacuum interrupter and
Whether it corresponds to the test certificate after uppacking. When shaking the interrupter, the ceramic envelop should be integrated.Power frequency withstand voltage should be tested before operating vacuum interrupter. Clean the surface with a dry colth or alcohol damped cloth before testing. The normal way for testing is an follows: when in the clearance between open contacts applies with 70 percent of rated power frequency withstand voltage within 1 min. The vacuum interrupter will be qualified if there is no sudden change and trip phenomena in the pointer of the vacuum interrupter.

 
2. Mounting of vacuum interrupter
a.Clean the surface of vacuum interrupter with cotton or alcohol dipped silk cloth before mounting. Meanwhile clean the conducting pole and surface of electric connection in order that the vacuum interrupter can have good electric contact with the equipment.b.The interrupter should be adjusted in the line with the equipment after mounting. The mechanical date related to the interrupter must meet the given specification.

3.In mounting, attention should be paid to the following:
a.When operating, guide unite unit must be provided for the interrupter. The coaxality of moving conducting pole and axial line of interrupter must meet the requirement. There should not be torque force applied on the bellow.
b. When mounting, it is forbidden to beat or strike the interrupter envelop with hard things in case crack may occur to cause air leakage.
c.Take care to assure that the conducting pole must be coaxial with interrupter, and that the conducting pole must be vertical on the face of fixed end
d.Take care not to disassemble the interrupter repeatedly to prevent screw from slipping. There should not be twisting on the moving conducting pole and over press on bellow to avoid that any torque force and scratch may occur to bellow to reduce its service life.
e.During mounting, the force applied on the face of both ends should not go beyond the static relief pressure stipulated in the specification.

 

4. Application.
a. Check the vacuum interrupter periodically by the way power frequency withstand voltage. For this, please see subclause
b. Periodically check how burnout is going on for contacts. When it comes to the burnout mark of moving conducting pole, it shows that the vacuum interrupter has finished its electrical endurance, and it should be replaced.