3 Phase Voltage Monitoring Relay LCD Display Voltage Protection Relay With Multi Protective Function
Technical parameters:
Rated supply voltage | M415(3-phase 3-wire)AC200V~500V M240(3-phase 4-wire)AC125V~300V |
Rated supply frequency | 50Hz/60Hz |
Voltage measurement error | ≤1% (Entire setting range) |
Delay error | ±10%+0.1s |
Measurement accuracy | 1%, RMS |
Phase failure and phase sequence | ≤0.2s |
Rated insulation voltage | 415V |
Contact configuration capacity(A) | 10A |
IP Class | IP20 |
Class of pollution | 3 |
Electrical Life | 105 |
Mechanical life | 106 |
Altitude | ≤2000m |
Allowable relative humidity | ≤50%(40ºC)(No condensation) |
Use category | AC-15 |
Short circuit protector type | RT36-00 5A |
Contact capacity | Ue/le:240V/1.5A,415V/0.95A |
Output type | 1C/O |
DIN rail Standard | Width 35mm(IEC/EN60715) |
Function Setting Table
Parameters | Setting range | Step amount | Factory setting | Remarks |
Over-voltage action value | OFF-381V~500V | 1V | 437V | M415 |
OFF-221V~300V | 1V | 253V | M240 | |
Over-voltage delay | 0.1~20S | 0.1s | 2s | |
Under-voltage action value | 260V~379V-OFF | 1V | 323V | M415 |
150V~219V-OFF | 1V | 187V | M240 | |
Under-voltage delay | 0.1~20s | 0.1s | 2s | |
Unbalance rate | OFF-5%~20% | 1% | 8% | |
Asymmetry Delay time | 0.1~20s | 0.1s | 2s | |
Phase sequence protection | ON-OFF | ON | ||
Start/reset delay | 0.3~30S | 0.1s | 0.3s | |
Automatic reset | ON-OFF | ON |

Features:
Built-in microprocessors, true RMS voltage measurement, voltage measurement accuracy ≤1%.Measuring frequency 45Hz~64Hz,button setting, LCD display voltage and fault information, protection can be turned on or off. Check phase voltage value by button, with N-phase phase failure protection, DIN rail mounting.
Built-in microprocessors, true RMS voltage measurement, voltage measurement accuracy ≤1%.Measuring frequency 45Hz~64Hz,button setting, LCD display voltage and fault information, protection can be turned on or off. Check phase voltage value by button, with N-phase phase failure protection, DIN rail mounting.
Applications:
Used in air conditioning units, elevator machine room, pumps, fans and other motor control applications, as protection of over-voltage. Under-voltage, phase failure, phase sequence and phase unbalance. When the power supply is abnormal, turn off power supply to protect the equipment.
Used in air conditioning units, elevator machine room, pumps, fans and other motor control applications, as protection of over-voltage. Under-voltage, phase failure, phase sequence and phase unbalance. When the power supply is abnormal, turn off power supply to protect the equipment.

Function diagram

Wiring Diagram

Dimensions(mm)

More Products





A:We are a factory founded in 2010 and have over 10 years'OEM and international trading experience .
Q2.What's your main product?
A:Our main products are time Relay, voltage Relay, motor protector, current relay,solid state relay
Q3.Do you accept OEM or ODM?
A:Of course.
Q4.What's your main payment term?
A:T/T ,LC ,D/P.
Q5.Any quality guarantee or after-sales service?
A:All the products have 2 years' Guarantee. If any quality complaint , we will give out solution within 5 days
Q6.Can sample fee be returned back to me ?
A:Sample amount can be deducted from your bulk order payment when order quantity is over 1000 pieces at the first time.