Air-Cooled
Screw
Split
380-415V 3n-50Hz
2 or 4
Ultra Low
Food Processing
CE
New
30.2-55 Kw
50-100 a
125-300 a
0-50-100 %
11.4-22.4 M3/H
30-60 Kpa
28000-48000 M3/H
Evi Compressor
TICA
Heat Pump Chiller Machine for Central Air Conditio
China
Product Description
Heat Pump Air Cooled Chiller For Central Air Conditioner



(1) High Efficiency. Eneray Saving And Environmental Protection.
(2) Excellent Capacity
(3) Free master Module Design
(4) Intelligent Defrosting Technology, Non-stop When Defrosting
(5) Intelligent Air Volume Requlation
(6) Intelligent Energy Requlation Technology
(7) Widely Operation Range
(8) Compact Desian And Less Occupied Area
(9) Famous Hermetic Scroll Compre
(10) V-Shaped Condenser
(11) Efficient Shell And Tube Heat Exchanger
(12) Saw-shaped Impeller
(13) High Precision Electronic Expansion Valve
(14) Self-developed Microcomputer Control Panel
(15) Multiple Protection Functions. Providing Safety And Stability
TICA R&D INSTITUTE JAPAN



>>Product Features
(1) High Efficiency. Eneray Saving And Environmental Protection.
(2) Excellent Capacity
(3) Free master Module Design
(4) Intelligent Defrosting Technology, Non-stop When Defrosting
(5) Intelligent Air Volume Requlation
(6) Intelligent Energy Requlation Technology
(7) Widely Operation Range
(8) Compact Desian And Less Occupied Area
(9) Famous Hermetic Scroll Compre
(10) V-Shaped Condenser
(11) Efficient Shell And Tube Heat Exchanger
(12) Saw-shaped Impeller
(13) High Precision Electronic Expansion Valve
(14) Self-developed Microcomputer Control Panel
(15) Multiple Protection Functions. Providing Safety And Stability
Air-Cooled-Modular-Chiller | |||||||
Model | 66KW | 100 KW | 130 KW | 165 KW | 260 KW | ||
Cooling capacity | kW | 66 | 100 | 130 | 165 | 260 | |
TR | 18.8 | 28.4 | 37 | 46.9 | 73.9 | ||
Heating capacity | kW | 70 | 110 | 140 | 180 | 280 | |
TR | 19.9 | 31.3 | 39.8 | 51.2 | 79.6 | ||
Capacity adjustment | % | 0-50-100 | 0-25-50-75-100 | ||||
Power supply* | - | 380-415V 3N-50Hz | 380V-3ph-50Hz | ||||
Power input | Cooling | kW | 21.29 | 32.25 | 41.9 | 53.2 | 83.8 |
Heating | kW | 21.85 | 34.37 | 43.7 | 56.2 | 87.4 | |
Current | Cooling current | A | 41.5 | 59.7 | 82.3 | 101.7 | 168.12 |
Heating Current | A | 41.9 | 60.4 | 83.2 | 102.4 | 170.5 | |
Max input current | A | 50 | 80 | 100 | 130 | 234.9 | |
Refrigerant | Type | - | R410A | ||||
Compressor | Type | - | Scroll/Danfoss | ||||
Quantity | - | 2 | 4 | 4 | 4 | 4 | |
Water side heat exchanger | Type | - | High-efficient Shell and tube heat exchanger | High Efficient Shell & Tube Heat Exchanger | |||
Water flow | m3/h | 11.4 | 17.2 | 22.4 | 28.4 | 44.8 | |
Pressure drop | kPa | 45 | 30 | 45 | 45 | 45 | |
Pipe connection dimension | - | DN65(flanged joint) | DN80(Flange) | DN100(Flange) | |||
Air side heat exchanger | Type | - | High-efficient aluminum fin-copper Tube heat exchanger | ||||
Fan type | - | Axial-flow | |||||
Number of fans | - | 2 | 4 | ||||
Total fan air flow | m3/h | 28000 | 43000 | 48000 | 60000 | 112000 | |
Sound pressure level | dB(A) | 65 | 68 | 69 | 70 | 73 | |
Dimension | Unit(LxWxH) | mm | 2200×860×2000 | 2200×1100×2205 | 2200×1100×2205 | 2200×1720×2100 | 2200×2400×2235 |
Package(LxWxH) | mm | 2240×900×2000 | 2240×1140×2205 | 2240×1140×2205 | 2240×1760×2100 | 2240×2440×2235 | |
Net weight | kg | 580 | 900 | 1000 | 1420 | 2025 | |
Gross weight | kg | 585 | 905 | 1005 | 1425 | 2030 | |
Operating weight | kg | 640 | 980 | 1100 | 1550 | 2250 | |
Optional auxiliary electric heating | kW | 18 | 27 | 32 | 43 | 63 |