KDZG
Yes
1 Year
<500mm
<900kg
Universal Testing Machine
<1000KN
0.5
Electronic Load
Dynamic Load
Digital
Computer Control
0-100Kg
AC220V
Under
Signal Phase AC 50Hz 220V±10%
OEM, ODM, Obm, Software Reengineering
-10~40ºC
Capacitance Od Tested Is Unlimited
Electronic
≤1%
Below 1500m
Digital Display Meter
KDZD
Wooden Case
25*28*40cm
Hubei, China
9030332000
Product Description

Integrated machine | ||||||||
Specifications | 40/3(kV/mA) | 60/2(kV/mA) | 60/3(kV/mA) | 60/5(kV/mA) | 80/2(kV/mA) | 100/2(kV/mA) | 120/2(kV/mA) | 120/5(kV/mA) |
Technical parameter | ||||||||
Rated voltage (kV) | 40 | 60 | 60 | 60 | 80 | 100 | 120 | 120 |
Rated current (mA) | 3 | 2 | 3 | 5 | 2 | 2 | 2 | 5 |
Rated power (W) | 120 | 120 | 180 | 300 | 160 | 200 | 240 | 600 |
Chassis weight (kg) | 7 | 10.5 | 10.5 | 10.5 | 11 | 11.2 | 11.2 | 11.2 |
Double pressure weight (kg) | Integrated 2.5 | 2.7 | 2.7 | 2.7 | 3 | 3.3 | 3.3 | 3.3 |
Double pressure height (mm) | Integrated 400 | 400 | 400 | 400 | 400 | 500 | 500 | 500 |
Voltage measurement accuracy | Digital display meter ± (1.0% reading ± 2 characters) | |||||||
Current measurement accuracy | Digital display meter ± (1.0% reading ± 2 characters) | |||||||
Ripple coefficient | ≤1% | |||||||
Voltage stability | Random fluctuation, ≤ 1% when the power supply voltage changes ± 10% | |||||||
Overload capacity | The no-load voltage can exceed the rated voltage by 10% for the mintes | |||||||
The maximum charging current is 1.5 times of the rated current | ||||||||
Power supply | Signal phase AC 50Hz 220V±10% | |||||||
Operation mode | Intermittent use | |||||||
The maximum continue time is 30 minutes | ||||||||
Working emviroment | temperature:-10~40ºC | |||||||
Relative humidity : no more than 85% at room temperature of 25ºC(no condensation) | ||||||||
Altitude: below 1500m | ||||||||
With capacitance | Capacitance od tested is unlimited | |||||||
Load capacity | It can be charged with 1.5 times of rated current | |||||||
Structural characteritics | Epoxy glass fiber reinforecd plastic electrical insulated double pressure cylinder | |||||||
Air insulation, no leakage | ||||||||
Feature of opeartion box | High precision 0.75UDC1mA one touch button(precision ≤1.0%)zinc oxide arrester test | |||||||
The over-voltage protection is set at a glance | ||||||||
An aluminum alloy box is placed at the double pressure of the chassis, and the whole machine can be lifted by one hand |
Splitter machine | ||||||||
Specifications | 200/3 (kV/mA) | 200/2 (kV/mA) | 250/3(kV/mA) | 300/2(kV/mA) | 300/5(kV/mA) | 400/3(kV/mA) | 400/5(kV/mA) | Other levels |
Technical parameter | ||||||||
Rated voltage (kV) | 200 | 200 | 250 | 300 | 300 | 400 | 400 | 500~1000KV customized |
Rated current (mA) | 3 | 2 | 3 | 2 | 5 | 3 | 5 | |
Rated power (W) | 400 | 1000 | 750 | 600 | 1500 | 1200 | 2000 | |
Chassis weight (kg) | 4.5 | 4.5 | 4.5 | 4.5 | 5.5 | 5.5 | 5.8 | |
Double pressure weight (kg) | 11.5 | 11.5 | 13 | 16 | 16 | 22 | 22 | |
Double pressure height (mm) | 965 | 965 | 1030 | 1250 | 1250 | 1900 | 1900 | |
Voltage measurement accuracy | Digital display meter ± (1.0% reading ± 2 characters) | |||||||
Current measurement accuracy | Digital display meter ± (1.0% reading ± 2 characters) | |||||||
Ripple coefficient | ≤1% | |||||||
Voltage stability | Random fluctuation, ≤ 1% when the power supply voltage changes ± 10% | |||||||
Overload capacity | The no-load voltage can exceed the rated voltage by 10% for the mintes | |||||||
The maximum charging current is 1.5 times of the rated current | ||||||||
Power supply | Signal phase AC 50Hz 220V±10% | |||||||
Operation mode | Intermittent use | |||||||
The maximum continue time is 30 minutes | ||||||||
Working emviroment | temperature:-10~40ºC | |||||||
Relative humidity : no more than 85% at room temperature of 25ºC(no condensation) | ||||||||
Altitude: below 1500m | ||||||||
With capacitance | Capacitance od tested is unlimited | |||||||
Load capacity | It can be charged with 1.5 times of rated current | |||||||
Structural characteritics | Epoxy fiberglass electrical insulation pressure doubling cylinder | |||||||
Air insulation, no leakage | ||||||||
Feature of opeartion box | High precision 0.75UDC1mA one touch button(precision ≤1.0%)zinc oxide arrester test | |||||||
The over-voltage protection is set at a glance | ||||||||
The control box is small and convenient for on-site use |