EP-4000
LCD
Computer Control
AC220V
RS232
Various Types of Vacuum Switch Tubes.
The New Excitation Coil Is Used for The Measuremen
This Instrument Is a Multi-Purpose Machine, Which
10-5 ~10-1 PA
10-5~10-4 PA, 10% 10-4~10-3 PA, 10% 10-3~10-2 PA,
1700V
30kv
Normal Use Opening Distance.
-20 Degree ~40 Degree
Magnetron Coil
410*320*370 (mm)
24kg
LCD English
Yes
EP Hipot Electric
Plywood Case
410*320*370 (mm)
Wuhan, China
9031809090
Product Description
Vacuum Circuit Breaker Test Equipment VCB Testing Kit High Voltage Circuit Breaker Vacuum Degree Tester Vacuity Tester
General Information:
Vacuum circuit breaker is a common method for judging whether the vacuum degree of the vacuum tube has deteriorated is the power frequency withstand voltage method. This method is only an arc extinguishing chamber that can judge the serious deterioration of the vacuum degree. When the vacuum degree deteriorates to 10-2----10-1 Pa, although the breakdown voltage does not decrease, the arc extinguishing chamber has already failed. EP-4000 vacuum switch vacuum degree tester adopts a new excitation coil, and uses the magnetron discharge method to test the vacuum degree of the arc extinguishing chamber without disassembling the arc extinguishing chamber. At the same time, the microcomputer is used for synchronous control and data acquisition and processing, so that the field test sensitivity of the vacuum degree of the arc extinguishing chamber reaches 10-5Pa. The most prominent feature of this instrument is the use of a new excitation coil and data processing method to achieve the measurement of vacuum without disassembly. This instrument has the advantages of convenient use, simple operation, no disassembly measurement and high test accuracy. It is a practical testing instrument widely used in power, steel, petrochemical, textile, coal, railway and other departments that use vacuum switches.
Features:



More details on Vacuum Degree Tester EP-4000, please contact EP Hipot Electric, we have professional tech team to design correctly designed products and systems.



General Information:
Vacuum circuit breaker is a common method for judging whether the vacuum degree of the vacuum tube has deteriorated is the power frequency withstand voltage method. This method is only an arc extinguishing chamber that can judge the serious deterioration of the vacuum degree. When the vacuum degree deteriorates to 10-2----10-1 Pa, although the breakdown voltage does not decrease, the arc extinguishing chamber has already failed. EP-4000 vacuum switch vacuum degree tester adopts a new excitation coil, and uses the magnetron discharge method to test the vacuum degree of the arc extinguishing chamber without disassembling the arc extinguishing chamber. At the same time, the microcomputer is used for synchronous control and data acquisition and processing, so that the field test sensitivity of the vacuum degree of the arc extinguishing chamber reaches 10-5Pa. The most prominent feature of this instrument is the use of a new excitation coil and data processing method to achieve the measurement of vacuum without disassembly. This instrument has the advantages of convenient use, simple operation, no disassembly measurement and high test accuracy. It is a practical testing instrument widely used in power, steel, petrochemical, textile, coal, railway and other departments that use vacuum switches.
Features:
- To measure quantitatively on vacuum degree of various vacuum switches interrupters.
- To measure the vacuum interrupter without dismounting.
- Test result is accurate and reliable.
- LCD English display, easy to operate.
- RS232 port, can communicate with computer easily.
- Light weight and portable, it's suitable for on-site test.
Test object: | Various types of vacuum switch tubes. |
Detection method: | The new excitation coil is used for the measurement of the vacuum tube without disassembly. |
Scope of application: | This instrument is a multi-purpose machine, which can measure various types of vacuum switches. |
Detection range: | 10-5-10-1 Pa |
Measurement accuracy: | 10-5-10-4 Pa, 10% 10-4-10-3 Pa, 10% 10-3-10-2 Pa, 10% 10-2-10-1 Pa, 10% |
Magnetic field voltage: | 1700V |
High voltage of pulse electric field: | 30kV |
The opening distance of the switch tube when testing the vacuum degree: | Normal use opening distance. |
Operation Temperature | -20ºC~40ºC |
Sampler: | Magnetron coil |
Dimensions: | 410×320×370 (mm) |
Weight (N.W.) | 24kg |



More details on Vacuum Degree Tester EP-4000, please contact EP Hipot Electric, we have professional tech team to design correctly designed products and systems.