10kv Numeric Multifunction Substation Power System Protection Device

Price $518.10 Compare
Min Order 1 Piece
Shipping From Jiangsu, China
Popularity 304 people viewed
Quantity
+-
 

Jiangsu Acrel Microgrid Institute Co., Ltd

VIP   Audited Supplier 4 years
Profile Certified by SGS/BV
AM4
Power
Protection
ISO9001:2000
All- packaged Type
High Voltage
1 Uint
Substation
Plastic
IP30
Acrel
Voltage Protection
Current Protection
Acrel
Carton
AM4
China
8536300000
Product Description
10kv Numeric Multifunction Substation Power System Protection Device
AM4 series protection relay is applicable to the user substation which the input voltage is 35kv and below. We adopt mature technology solutions to ensure the quality of the AM relay. The AM relay is widely used in substations, subsection posts and ring main units for office buildings, commercial buildings, communication buildings, mine buildings, and so on.

 

Product Parameters

 
Rated ParameterPower SupplyPower supply: AC/DC220V, or AC/DC110V, or DC48V(Reference the wiring diagram)
Range: Power supply x (1±20%)
Maximum power consumption:≤10W(DC)
Rated VoltageRated Voltage: AC100V
Range:1-120V
Accuracy:±0.5%
Power Consumption:≤0.5VA(Single phase)
Overload capacity:1.2 times rated voltage for continuous work;2 times for 10 seconds
Rated CurrentRated current: AC 5A/1A(See the device wiring diagram)
Range:0.04In~15In
Power consumption:≤0.5VA(Single phase)
Over capacity:2 times rated current for continuous work;40 times for 1 second
FrequencyRated frequency:50Hz or 60 Hz
Range:45~55Hz
Accuracy:±0.1Hz
Digital InputRated Voltage: AC/DC220V, AC/DC110V, DC48V(Similar to the power supply)
Voltage Range: Rated voltage x (1±20%)
Power Consumption:≤1W(DC220V)(Single channel)
Digital OutputMechanical life:≥10000 times
Switching capacity:≥1000W, L/R=40ms
On current:continuous≥5A short time(200ms)≥30A
Interrupting capacity:≥30W,L/R=40ms
Normal Working ConditionsAmbient temperature:-10ºC~+55ºC
Device storage, transport allows the ambient temperature is -25ºC~+70ºC
Relative humidity:5%~95%(The product does
Altitude:≤4000m
FunctionCurrent TypeVoltage Type
AM4-IAM4-U1
Current collection40
Voltage collection44
Switch value collection1212
Relay output55
Protection Function
Overcurrent (three stages, inverse time limit) 
Zero sequence overcurrent (two stages, inverse time limit) 
Negative sequence overcurrent (two stages, inverse time limit) 
Reclosing 
Overload trip/alarm 
Low-frequency load shedding 
After accelerating overcurrent 
Overvoltage trip 
Low voltage trip 
FC blocking 
Control failure alarm 
Non-electricity trip/alarm 
Low voltage alarm
Overvoltage alarm
Zero sequence overvoltage alarm (self-produced/external)
PT disconnection alarm
Self-produced zero-sequence overvoltage alarm 
Communication protocol
Modbus-RTU
IEC60870-5-103
Auxiliary function
Fault recording 

Dimension

Display

Wiring

Networking

 

FAQ

Q: How to set the CT and PT ratio of the protection device?

A: The protection device can set the CT and PT ratio through the fixed value menu. For example, the current transformer is 75/5 and the voltage transformer is 10/0.1, then the CT ratio is set to 15 and the PT ratio is set to 100.


Q: For AM5, if you want to place single circuit protection and transformer protection, how to distinguish the model?

A: AM5-F is suitable for line protection and transformer protection.No need to distinguish between models when placing orders


Q: When the voltage is a three-phase three-wire system, does the current have to be connected with 2CT?

A: The voltage wiring mode and current wiring mode of the protection device can be set independently, and can be connected freely.


Q: How to confirm whether the anti-trip function is configured?

A: If the circuit breaker is equipped with anti-trip, the device does not must be equipped with anti-trip; if the circuit
breaker does not have anti-trip, you need to configure the AM5-FT anti-trip module. (If DC48V is selected as the
operating power supply, the anti-trip box is not optional, and the circuit breaker must be equipped with anti-trip
function; if you choose AC anti-trip, please note that AC and DC general anti-tripping)


Q: How to purchase suitable protection devices?

A: Before ordering, it is recommended to consult related engineers, select the appropriate protection model,
and then fill in the corresponding selection table, and place the order after confirmation by the engineers.

Related Products

SpecificationAM2SEAM3SEAM4AM5AM5SE
HardwareProtect Current3 channels3 channels3 channels3 channels3 channels
Measure Current×××3 channels3 channels
zero-sequence current1 channel2 channels1 channel2 channels2 channels
Measure Voltage3 channels3 channels4 channels4 channels4 channels+ backup 2 channels
Switch Value Input8 channels11 channels12 channels16 channels20 channels
Switch Value Output5 channels5 channels5 channels10 channels10 channels
RS485 Interface1 channels1 channel1 channel2 channels2 channels
RS232 Interface××111
USB×
CE×optional 2
GPS time synchronization××
4-20mA×optional 2
Anti-jumpOptional external anti-hop modulebuilt-in
operation circuit×
ProtectionMain transformer differential protection××××
Main transformer backup protection××××
Three-stage overcurrent
With direction with a voltage blocking
×××
Three-stage overcurrent
with directional locking
×
Three-stage overcurrent
Zero sequence overcurrent protection
Overvoltage protection
Low voltage protection
Zero sequence overvoltage protection
High-power motor differential protection
(>2000KW)
××××
High Voltage Motor Protection×××
Capacitor Protection×××
Overcurrent after acceleration
Low-frequency load shedding
Grid-connected reverse power protection×××
PT disconnection alarm
Fault alarm
FC blocking
Incoming line of high voltage single busbar system
/Mother-joint prepared self-injection
×××
Low-voltage standby self-switching(400V)××××
PT monitoring and parallel functions××××
PT monitoring functions
Non-electrical protection
(temperature, gas, etc.)
Synchronization function××××
Fault recorder
Electrical parameter measurementU, I, Fr, P, Q, PF, Ep, Eq, Es