33kv/69kv/138kv 60Hz/50Hz Outdoor Capacitor Voltage Transfroemr with Grouping Box

Price $3000.00 Compare
Min Order 1 Piece
Shipping From Zhejiang, China
Popularity 387 people viewed
Quantity
+-
 

Ningbo Hyuan Power Industry Co., Ltd.

VIP   Audited Supplier 8 years
Profile Certified by SGS/BV
TYD
Instrument
Voltage Transformer
Single
Outdoor
Protection, Measurement
Multilayer Honeycomb Type
Capacitor
Busbar Type
Combined Type
Capacitive Type
HEMG
Carton with Wooden
33KV/72.5KV/123KV/132KV/145KV
China
Product Description


 
CAPACOTR Voltage Transformer 138 kV
DescriptionUnitValue Required
 
Guaranteed
 
1.0.0General Data   
1.1.0Manufacturer IndicateHEMG
1.2.0Model IndicateCapacitive
1.3.0Year of fabrication Indicate2016
1.4.0Country of origin IndicateCHINA
1.5.0Reference IndicateIEC61869-5:2011
1.6.0Altitude of operationmsnm20002000
1.7.0Location ForestForest
1.8.0Type of installation ExteriorExterior
1.9.0Standard of manufacture IEC 60044-5, IEC 60358IEC 60044-5, IEC 60358
1.10.0Type of casing Brown porcelain, IEC 61264Brown porcelain, IEC 61264
1.11.0Pollution levelmm/kV3131
 
 
 System Parameters   
2.0.0Operating voltageKV138138
2.1.0Maximum voltage of material (Um)KV170170
2.2.0Rated withstand voltage at industrial frequency (Ud)KV325325
2.3.0Rated withstand voltage by lightning impulseKV750750
2.40Assigned frequency (Fr)Hz6060
2.5.0Assigned voltage factor   
a) Permanent 1.21.2
b) During 30 sec 1.51.5
2.6.0Total capacitypF1250012500
2.7.0High voltage capacitor (C1)pFIndicate14937
2.8.0Intermediate voltage capacitor (C2)pFIndicate76625
2.9.0Rated intermediate voltage in open circuit for HF coupling boxKVIndicate13
2.10.0Number of secondary windings 3 (A measurement core and two for protection)3
2.11.0Transformation ratio 138/3 : 100/3: 100/3: 100/3138/√3/0.1/√3/0.1/√3/0.1/√3 kV
2.12.0Reference frequency range Indicate60+-1.5HZ
a) Precision class of measurement%<= 0.20.2
b) Precision class of protection%5P3P
2.13.0BurdenVA3030
2.14.0Accuracy class between 25% and 100% of the precision load 0.8 power factor lag  Indicate0.2/3P
a) between 5% and 80% of the rated voltage 5P3P
b) between 80% and 120% of the rated voltage <= 0.20.2
c) between 120% and 150% of the rate voltage 5P3P
2.15.0Precision load    
a) Winding 1 - measureVA3030
b) Winding 2 - ProtectionVA3030
c) SimultaneousVA3030
d) Thermal power limitVAIndicate800
2.16.0Rated voltage of the system   
a) Primary (Upn)KV138/√3138V3  
b) Secondary (Usn)V100/√3100V3
2.17.0Arcing distanceMm 1860
2.18.0Creepage distance according to IEC 60815   
a) For heavy pollution levelmm/kv3131
2.19.0Short-circuit current 1 sec characteristicskA4040
2.20.0Dynamic current peakkAIndicate80
 3.0..0MECHANICAL PARAMETERS   
3.1.0Total weightKgIndicate700
3.2.0Internal insulation for capactive bodies Synthetic oilSynthetic oil
3.3.0Total isolation quantity in electromagnetic unitLIndicate90
Internal insulation for electromagnetic unit Mineral oil Mineral oil
3.4.0Packaging used for mounting electromagnetic unit IndicateExporting Package
3.5.0Diaphragm type Indicatepolypropylene film
3.6.0Protection grade IP65 for each terminal siYES
3.7.0Seismic data (high condition) Indicate138KV/2000M
a) Natural frequency (high condition)HzIndicate60HZ+-1.5HZ
b) Critical damping coefficient (high condition)%Indicate0.3
c) Horizontal accelerationg0.50.5
d) Vertical accelerationg0.20.2
3.8.0Permissilbe load on terminals   
a) StaticNIndicate2000
b) DynamicNIndicate2000
3.9.0Maximum allowed load by mounting pedestal-type wave trapNIndicate30
3.10.0Maximum allowed effort in porcelaindaN/mm2Indicate20
3.11.0Mean time between failure (MTBF)DaysOffer value1825
3.12.0Mean time to repair (MTTR)DaysOffer value365
 4.0.0ACCESSORIES FOR ASSEMBLY   
4.1.0Grouping box secondary circuit and electrical system included YesYES
4.2.0Central box of circuits for three voltage transformers YesYES
4.3.0Micro switch for secondary ciruit protection (MCB) Yes, needs to be suppliedYES
a) Rated currentA66
b) Type curve ZZ
c) Auxiliary contact for position indication and tripping YesYES
4.4.0Protection device ferroresonance YesYES
4.5.0Sampling valve for mineral oil in electromagnetic box Gate typeGATE TYPE
4.6.0Oil gauge YesYES
4.7.0Type of plate for alternative corrosive area, low relief Anodized aluminiumALUMINIUM
4.8.0Ground terminal YesYES
4.9.0Connecting elements for communication system (carrier system)   
a) Coil drain NoNo
b)Descargador  NoNo
c) Grounding blade high frequency signal NoNo
4.10.0Grounding blade of medium voltage to measure capacitance C1, C2 YesYes
4.11.0Mounting pedestal for wave trap NoNo
 
 
SPECIFIATION OF  CAPACITOR Voltage Transformer 60 kV
DescriptionUnitValue Required
 
Guaranteed
 
1.0.0General Data   
1.1.0Manufacturer IndicateHEMG
1.2.0Model IndicateCapacitive
1.3.0Serial numbers IndicateCVT2015001
1.4.0Country of origin IndicateCHINA
1.5.0Reference IndicateIEC61869-5:2011
1.6.0Altitude of operationmsnm20002000
1.7.0Location ForestForest
1.8.0Type of installation ExteriorExterior
1.9.0Standard of manufacture IEC 60044-5, IEC 60358IEC 60044-5, IEC 60358
1.10.0Type of casing Brown porcelain, IEC 61264Brown porcelain, IEC 61264
1.11.0Pollution levelMm/kv3131
 
 
 Parameters of system   
2.0.0Operating voltageKV6060
2.1.0Maximum voltage of material (Um)KV72.572.5
2.2.0Rated withstand voltage at industrial frequency (Ud)KV140140
2.3.0Rated withstand voltage by lightning impulseKV350350
2.40Assigned frequency (Fr)Hz6060
2.5.0Assigned voltage factor   
a) Permanent Indicate1.2
b) During 30 sec Indicate1.5
2.6.0Total capacitypFIndicate20000
2.7.0High voltage capacitor (C1)pFIndicate32012
2.8.0Intermediate voltage capacitor (C2)pFIndicate53300
2.9.0Rated intermediate voltage in open circuit for HF coupling boxKVIndicate13
2.10.0Number of secondary windings 3 (A measurement core and two for protection)3
2.11.0Transformation ratio 60/3 : 100/3: 100/3: 100/360/√3/0.1/√3/0.1/√3/0.1/√3 kV
2.12.0Reference frequency range Indicate 
a) Precision class of measurement%<= 0.20.2
b) Precision class of protection%5P3P
2.13.0BurdenVA3030
2.14.0Accuracy class between 25% and 100% of the precision load 0.8 power factor lag  Indicate0.2/3P
a) between 5% and 80% of the rated voltage 5P3P
b) between 80% and 120% of the rated voltage <= 0.20.2
c) between 120% and 150% of the rate voltage 5P3P
2.15.0Precision load    
a) Winding 1 - measureVAIndicate30
b) Winding 2 - ProtectionVAIndicate30
c) SimultaneousVAIndicate30
d) Thermal power limitVAIndicate800
2.16.0Rated voltage of the system   
a) Primary (Upn)KV60/√360V3  
b) Secondary (Usn)V100/√3100V3
2.17.0Arcing distanceMm 930
2.18.0Creepage distance according to IEC 60815   
a) For heavy pollution levelmm/kv31.531.5
2.19.0Corriente  de corto circuito a 1 SkA31.531.5
2.20.0Dynamic current peakkAIndicate80
 3.0..0MECHANICAL PARAMETERS   
3.1.0Total weightKgIndicate450
3.2.0Internal insulation for capactive bodies Synthetic oilSynthetic oil
3.3.0Total isolation quantity in electromagnetic unitLIndicate90
Internal insulation for electromagnetic unit Mineral oil Mineral oil
3.4.0Packaging used for mounting electromagnetic unit IndicateExporting Package
3.5.0Diaphragm type Indicatepolypropylene film
3.6.0Protection grade IP65 for each siYES
3.7.0Seismic data (high condition) Indicate60KV/2000M
a) Natural frequency (high condition)HzIndicate60HZ+-1.5HZ
b) Critical damping coefficient (high condition)%Indicate0.3
c) Horizontal accelerationgIndicate0.5
d) Vertical accelerationgIndicate0.2
3.8.0Permisible load on terminals   
a) StaticNIndicate2000
b) DynamicNIndicate2000
3.9.0Maximum allowed load by mounting pedestal-type wave trapNIndicate30
 
 
    
3.10.0Maximum allowed effor in porcelaindaN/mm2Indicate20
3.11.0Mean time between failure (MTBF)DaysOffer value1825
3.12.0Mean time to repair (MTTR)DaysOffer value365
 4.0.0ACCESSORIES FOR ASSEMBLY   
4.1.0Grouping box secondary circuit and electrical system included YesYES
4.2.0Central box of circuits for three voltage transformers YesYES
4.3.0Micro switch for secondary circuit protection (MCB) Yes, needs to be suppliedYES
a) Rated currentAIndicate6
b) Type curve ZZ
c) Auxiliary contact for position indication and tripping YesYES
4.4.0Protection device ferro-resonance YesYES
4.5.0Sampling valve for mineral oil in electromagnetic box Gate typeGATE TYPE
4.6.0Oil gauge YesYES
4.7.0Type of plate for alternative corrosive area, low relief Anodized aluminiumALUMINIUM
4.8.0Ground terminal YesYES
4.9.0Connecting elements for communication system (carrier system)   
a) Coil drain NoNo
b)Descargador  NoNo
c) Grounding blade high frequency signal NoNo
4.10.0Grounding blade of medium voltage to measure capacitance C1, C2 YesYes
4.11.0Mounting pedestal for wave trap NoNo
 

Message Type
* Message Content
* Name  
* Phone
* Email
* CAPTCHA