DZ30-32
Low Voltage Circuit Breakers
Manual Type
Normal Type Circuit Breaker
Air
Fixed
MCB
2
Circuit Breaker
Circuit-Breaker Failure Protection
ISO9001-2000, CE
ELECAL
Carton
Wenzhou
85362000
Product Description
1.Application
DZ30-32 is used in the single phase circuit of AC 50Hz/60Hz, rated voltage 230V or below for protecting circuit from overload and short circuit. This product has advantages of high breaking capacity, small volume, width is only 18mm. It conforms with the standards of IEC60898.
2. Main Technical Parameter
3. Applicable conducting wire:
4. The over-current protection property
DZ30-32 is used in the single phase circuit of AC 50Hz/60Hz, rated voltage 230V or below for protecting circuit from overload and short circuit. This product has advantages of high breaking capacity, small volume, width is only 18mm. It conforms with the standards of IEC60898.
2. Main Technical Parameter
Type | DZ30-32 |
Pole | 1P+N |
Rated current (A) | 6,10,16,20,25,32 |
Rated voltage(V) | 230 |
Type of instantaneous release | C |
Rated making/breaking capacity Im(A) | 4500 |
3. Applicable conducting wire:
Rated current(A) | Norminal cross section of wire mm2 |
In ≤ 6 | 1 |
6 < In ≤ 13 | 1.5 |
13 < In ≤ 20 | 2.5 |
20 < In ≤ 25 | 4 |
25 < In ≤ 32 | 6 |
4. The over-current protection property
Ambient Temperature | Initial Status | Test Current | Expected Result | Expected Result | Note |
Cold position | 1.13In | t ≥ 1h | Non-release | - | |
30 ± 2oC | Carried out immediately after previous test | 1.45In | t<1h | Release | - |
Cold position | 2.55In | 1s < t < 60s | Release | Current smoothly rises to specified value within 5s | |
-5~+40oC | Cold position | 5In | t ≥ 0.1s | Non-release | Type C |
Cold position | 10In | t < 0.1s | Release | Type C |