363kV series T·GCB/GIS/HGIS
Two kinds of 363kVT·GCB:single break and doublebreak structure,of which single break T· GCB may break short circuit rated current and duration of 50kA/3s while double break TGCB may break short circuit rated current and duration of 50kA/3s or 63kA/3s.There is a parallel capacitor between breaks on 363kV 63kA double break product,closing resistance may be added according to user's requirement.
1 .Circuit breakerwith reasonable design,high reliability,simply structure and long-term overhaul
2 .Performance and parameters satisfied GB1984,IEC62271-100 and technical documents.All type tests passed according to national standard and IEC standard.
3.363kVT·GCB may operate under extreme lowtemperature below-40ºC.Successfully operated in high altitude,low temperature area as Qinghai Province.






2. The same structure as 363kVT·GCB is adopted on the circuit breaker.There are horizontal and vertical arrangements;
3.Compact structure and reduced footprint in circuit breaker stand arrangement;whole bay transport and short period of site installation and commissioning
4. Circuit breaker is provided with hydraulic or pneumatic operating mechanism
5. provided with motor spring operation mechanism
6 Mechanisms of disconnector and earthing switch are three-pole ganged operated straightly with body.
6. Spacer with metal loop is adopted.
7. Modular arrangement is adopted to meet requirements of various main wiring
8. Minimum distance between centers oftwo bays is 2600mm while distance between phases is 800mm.The product is small in volume and compact in structure as well as reduced area occupied

Main Technical Data of 363 T GCB/GIS/HGIS.
ltem | Unit | Data | ||
Rated voltage | kV | 363 | ||
Rated current | A | 4000,5000,6000 | ||
Rated frequency | Hz | 5,060 | ||
Rated short circuit breaking current | kA | 50 | 63 | |
Rated short-time withstand current and dur ation | kA/s | 50/3 | 63/3 | |
Rated peak withstand current | kA | 125 | 160 | |
Rated short circuit making current | kA | 125 | 160 | |
Number of breaks | EA | 1 | 2 | |
Rated lightning impulse withstand voltage | To earth | kV | 1175 | |
Across breaks | kV | 1175+295 | ||
Rated short time power frequency withstand voltage | To earth | kV | 520 | |
Across breaks | kV | 520+210 | ||
Rated switching impulse withstand voltage | To earth | kV | 950 | |
Across breaks | kV | 950+295 |
1.Our company provides you with project design and process design, and designs and manufactures products according to your equipment purchase plan and specific needs. And train technical and operating personnel for you.
2.The newly purchased products are provided with online assistance for installation and debugging. The products are under the lifelong service system. If problems occur in normal use, we will provide solutions within one working day after receiving user's feedback. We will try our best to get the product up and running as soon as possible. And there are regular visits by professional technicians to ensure the long-term, safe and reliable use of our products.
3.We use quality authentic materials, process and manufacture in strict compliance with ISO9001:2000 international quality management to ensure the quality of excellence and the smooth installation!