HCLN-36
Cold Shrink
Silicone Rubber
Insulation Protection
Insulation
Terminal
Cold Pressing
Rectangular
ISO, IEC, GB
Hifuture
50-630 Sq.M.
Single-Core, Three-Core
Cu, Al, Cual
Excellent Insulation, Anti-Tracking, etc
HiFuture
1 Set/ Carton
12kV, 24kV, 36kV
Shenzhen, China
8538900000
Product Description
36kV cold shrinkable indoor cable termination





Cold Shrink Cable Accessories:
1. Hifuture cold shrinkable cable accessories adopt world renowned brand liquid/solid silicone rubber material. The products are with excellent insulation, anti-tracking, rebound resistance, heat/cold resistance, ozone resistance, anti-aging, and good dielectric properties, and can be used under various harsh conditions.
2. Geometric stress control method.
3. Standards compliance: IEC60502, GB/T12706.4, EN50180& EN50181(C type bushing)
4. Cold installation, easy and safe without using fire, just by pulling the spiral.
Technical Data:





Cold Shrink Cable Accessories:
1. Hifuture cold shrinkable cable accessories adopt world renowned brand liquid/solid silicone rubber material. The products are with excellent insulation, anti-tracking, rebound resistance, heat/cold resistance, ozone resistance, anti-aging, and good dielectric properties, and can be used under various harsh conditions.
2. Geometric stress control method.
3. Standards compliance: IEC60502, GB/T12706.4, EN50180& EN50181(C type bushing)
4. Cold installation, easy and safe without using fire, just by pulling the spiral.
Technical Data:
Rated Voltage | 8.7/15(17.5)kV | 12/20(24)kV | 18/30(36)kV | 26/35(40.5)kV |
Running Temperature | 17.5kV | 24kV | 36kV | 40.5kV |
AC Withstand Voltage and DC Withstand Voltage | 39kV, 5min or 35kV, 15min, no flashover, no breakdown | 54kV,5min, or 48kV, 15min, no flashover, no breakdown | 81kV, 5min, or 72kV, 15min, no flashover, no breakdown | 117kV, 5min or 104kV, 15 min no flashover, no breakdown |
Partial Discharge | 15kV, PD≤5pC | 20kV, PD≤5pC | 30kV, PD≤5pC | 45kV, PD≤5pC |
Impulse Voltage Test | 95kV, ±10 times | 125kV, ±10 times | 170kV, ±10 times | 200kV, ±10 times |
Short Circuit Thermal Stability (Conductor) | 24kA, 2s twice, no visible damage | 25kA, 2s twice, no visible damage | 23kA, 2s twice, no visible damage | 25kA, 2s twice, no visible damage |
Short Circuit Dynamic Stability | 83kA, not less than 10ms, no visible damage | 63kA, not less than 10ms, no visible damage | 83kA, not less than 10ms, no visible damage | 88kA, not less than 10ms, no visible damage |
Constant Voltage Load Cycle | apply voltage 1.25U0 to conductor and heat to(90-95)ºC heat for 5h and cool for 3h, total 3 times | |||
Salt Spray Test | 1.25U0 1000h, no flashover, no breakdown, trip not more than 3 times, no obvious damage | |||
Humidity Test | 1.25U0 300h, no flashover, no breakdown, trip not more than 3 times, no obvious damage | |||
Long-time Running Temperature | -40ºC to 95ºC | |||
Short Circuit Temperature | 250ºC, lasting time less than 5s | |||
Cable Accessories Conductor Material | copper, aluminum, copper&aluminum |