Zc-Kvvp2-22
Industrial, Power Station, Telecommunication, Computer
Low and Medium Voltage Cable
AC Cable
PVC
PVC
Round Wire
Red Copper Wire
ISO, CCC, CE, RoHS
Zr-Kvvp2-22
Guowang
Free
GUOWANG
Wooden Drum/According to Your Requirement
1.5-300 mm2
China
8544492100
Product Description
Application
The products are suitable for the wiring of electrical controlling equipments and instrument,monitoring and controlling return circuit,electrical protection and measurement in power distribution unit under the circumstance that the rated voltage is up to 450/750V AC.
The tough armour protects against the effects of light mechanical and environmental stresses.
Standard
GB/T 9330
Structure
Conductor:Copper
Insulation:PVC
Armour:Steel Tape Armour
Sheath:PVC
Using characteristic
Rated voltage: 450 / 750V
Cable Working temperature not higher than 70 ºC.
Short (the longest duration of no more than 5s) of the conductor temperature does not exceed 160 ºC.
Cabling ambient temperature should not be below 0 ºC, or need preheated.
Installation bending radius
A) non-armored cable layer shall be not less than 6 times the cable diameter;
B) with armor or copper screened cable, not less than 12 times the cable diameter;
C) with a shield layer flexible cable, not less than 6 times the cable diameter.
The products are suitable for the wiring of electrical controlling equipments and instrument,monitoring and controlling return circuit,electrical protection and measurement in power distribution unit under the circumstance that the rated voltage is up to 450/750V AC.
The tough armour protects against the effects of light mechanical and environmental stresses.
Standard
GB/T 9330
Structure
Conductor:Copper
Insulation:PVC
Armour:Steel Tape Armour
Sheath:PVC
Using characteristic
Rated voltage: 450 / 750V
Cable Working temperature not higher than 70 ºC.
Short (the longest duration of no more than 5s) of the conductor temperature does not exceed 160 ºC.
Cabling ambient temperature should not be below 0 ºC, or need preheated.
Installation bending radius
A) non-armored cable layer shall be not less than 6 times the cable diameter;
B) with armor or copper screened cable, not less than 12 times the cable diameter;
C) with a shield layer flexible cable, not less than 6 times the cable diameter.
Nominal cross sectional area of conductor | Approximate Overall Diameter | Max DC resistance of conductor at 20ºC | Min DC resistance of insulation at 70ºC |
No×mm2 | mm | Ω/km | Ω/km |
4×0.75 | 10.56 | 24.5 | 0.012 |
4×1.0 | 10.93 | 18.1 | 0.011 |
4×1.5 | 12.02 | 12.1 | 0.011 |
4×2.5 | 14.07 | 7.41 | 0.010 |
4×4.0 | 15.16 | 4.61 | 0.0085 |
4×6.0 | 16.73 | 3.08 | 0.0070 |
7×0.75 | 11.81 | 24.5 | 0.012 |
7×1.0 | 12.26 | 18.1 | 0.011 |
7×1.5 | 14.21 | 12.1 | 0.011 |
7×2.5 | 16.01 | 7.41 | 0.010 |
7×4.0 | 17.36 | 4.61 | 0.0085 |
7×6.0 | 18.86 | 3.08 | 0.0070 |
9×0.75 | 14.13 | 24.5 | 0.012 |
9×1.0 | 14.7 | 18.1 | 0.011 |
9×1.5 | 16.41 | 12.1 | 0.011 |
9×2.5 | 18.69 | 7.41 | 0.010 |
12×0.75 | 14.9 | 24.5 | 0.012 |
12×1.0 | 15.53 | 18.1 | 0.011 |
12×1.5 | 17.4 | 12.1 | 0.011 |
12×2.5 | 20.3 | 7.41 | 0.010 |