GPE48200E
Single
2 Years
10700W
Full Range
Parallel Switching Power Supply
Separate-excited Switching Power Supply
Width Modulation Type
Terminal Power Distribution Equipment
One-way Transmission
PWM
CE, RoHS, ISO, CCC, CB
Gold Power
GOLD POWER
Carton
19'' 6U
China
8504401990
Product Description
48V/200A telecom Power Supply System with Controller (N+1 redundancy )
GPE48200E Embedded Power System
Input: 90~290Vac Output:-42.5~-58Vdc
Main features
- Wide operating range of AC input voltage: 90~290Vac
- Operating temperature range: -25ºC~+55ºC
- Zero current/voltage switching tech with high efficiency ≥91%
- Perfect battery management, battery temperature compensation, battery capacity test ,LVLD and LVBD protection, anti-reverse connective protection
- Hot-swappable
- Input over/under voltage protection
- Output over voltage protection
- Output over current protection
- Output short circuit protection
- Auto current sharing, parallel operation



GPE48200E System configuration
The system consists of distribution unit, rectifier module (up to 4 sets) and monitoring module. The configuration is optional, see following table:
The system consists of distribution unit, rectifier module (up to 4 sets) and monitoring module. The configuration is optional, see following table:
Configuration | Rectifier Module | Monitoring Module | Distribution | Remark |
Standard | GPR4850DR03 | GPM48P -A (With Ethernet Port) | AC distribution: 1-phase, general supply AC circuit breaker (80A/ 2P) DC distribution: Battery circuit breaker 100A/1P×2; LLVD: 32A×2,63X2, 16A×6 BLVD: 16A×2,10AX2 | For details, please refer to the specifications of modules. |
Input | |||||
Parameters | Min. | Typ. | Max. | Unit | Remark |
Input voltage range | 90 | 220 | 290 | Vac | |
Input frequency | 45 | 50 | 65 | Hz | |
Input current | 67 | A | |||
Power factor | 0.98 | Rated load | |||
Input over voltage protection | 300 | Vac | Auto-recovery | ||
Input over voltage recovery | 290 | Vac | Return difference ≥5V | ||
Input low voltage protection | 85 | Vac | Auto-recovery | ||
Input low voltage recovery | 90 | Vac | Return difference ≥5V | ||
Input over current protection | MCB at AC input side as protection |
Output | |||||
Parameters | Min. | Typ. | Max. | Unit | Remark |
Output voltage range | 42 | 53.5 | 58 | Vdc | Adjusting through monitor ,test with no load |
Output power | 0 | 10700 | W | Input 176-290Vac,18275W output (Rated power including battery charging power and load power ) | |
0 | 5350 | W | Input 90-175Vac | ||
Output over voltage protection | 58.5 | 60.5 | Vdc | Lock up | |
Output current limit protection | Available | ||||
Output short-circuit protection | Long time short-circuit no damage, auto-recovery | ||||
Over temperature protection | Auto-recovery when ambient temperature <65ºC | ||||
Battery low voltage disconnection protection | Available | ||||
Battery anti-pole protection | Battery and power supply no damage | ||||
Voltage regulation | ±1 | % |