BC-E00031A
Power, Electronic, Instrument, Rectifier
Three
Core-type Transformer
Dry-type Transformer
Multi-winding Transformer
ISO9001, CCC
Rectifier Transformer, Combined Transformer, Power Transformer
Power Frequency
Silicon Steel Sheet
Bc Power
<+/-5%
Thermistor Ntc Temperature Switch
Class H (180 C)
Wooden Case
1500*1200*1800 mm, 220V/400V/480V/540V/600V/800V
Dongguan City, Guangdong Province, China
Product Description
1. The primary side is 4 loops with 6 contactors are configured each to control the output of 220V/400V/480V/540V/600V/800V separately.
2. Push-button switch is used to control the output of the contactor. Each loop contactor interlock can only have one voltage output.
3. Only the same voltage gear can be used when multiple loops work at the same time.
4. The equipment is equipped with temperature monitoring (winding temperature, core temperature) switching, and the fan is started to cool when the internal temperature is higher than 60 degrees Celsius, and the fan is stopped when the internal temperature is lower than 45 degrees Celsius. Alarm sound occurs when the internal winding temperature exceeds135 degrees Celsius. The transformers automatically shuts down the total input power when the temperature is greater than 150 degrees Celsius.
5. Product total weight 2000KG.
Electric Characteristics




2. Push-button switch is used to control the output of the contactor. Each loop contactor interlock can only have one voltage output.
3. Only the same voltage gear can be used when multiple loops work at the same time.
4. The equipment is equipped with temperature monitoring (winding temperature, core temperature) switching, and the fan is started to cool when the internal temperature is higher than 60 degrees Celsius, and the fan is stopped when the internal temperature is lower than 45 degrees Celsius. Alarm sound occurs when the internal winding temperature exceeds135 degrees Celsius. The transformers automatically shuts down the total input power when the temperature is greater than 150 degrees Celsius.
5. Product total weight 2000KG.
Electric Characteristics
1 | Connection Group | Dyn11 |
2 | Rated capacity of primary winding | 350kW |
3 | Rated capacity of sencondary winding | 350kW |
4 | Primary rated line voltage (N1/N2/N3/N4) | (220/400/480/540/600/800) *4 / Y connection, with N At 400V and above to meet the full power, The power of each group shall not exceed 87.5KW; The total power at 220V is 193KW |
5 | Secondary rated line voltage N5 | 380V / D connection |
6 | Primary side impedence | N1=N2=N3=N4, duplex winding |
7 | Mains voltage fluctuation | < +/-5% |
8 | Working frequency | 50~70Hz |
9 | Efficiency | >97.5% (350kW resistive load) |
10 | The load cycle | Continous operation |
11 | Impedence voltage | <6% |
12 | Type of transformer | Dry type |
13 | The temperature sampling | Thermistor (NTC) temperature switch |
14 | Isolation resistance | P,S,E>500MΩ DC2500V/60s |
15 | Dielectric strength | <20mA 3KVAC/60s Coil-Core N1/N2/N3/N4-N5 |
16 | Isolation grade | H(180ºC) |
17 | Allowable temperature rise | 95K (rated current, forced air cooling) |
18 | Noise | <70dB (measured with a sound level meter at 1m) |
19 | Cooling type | AF (Forced air cooling, control panel with independent control switch) |