BC-E00036A
Power, Electronic, Instrument, Lighting, Rectifier
Three
Core-type Transformer
Dry-type Transformer
Multi-winding Transformer
ISO9001, CCC
Rectifier Transformer, Combined Transformer, Power Transformer
Power Frequency
Silicon Steel Sheet
Bc Power
<+/-5%
Thermistor Ntc Temperature Switch
Class H (180 C)
Dyn11
150kw
150kw
(220/400/480/500/540) *1 / Y Connection, with N
380V / D Connection
>97.5%
Wooden Case
1500*1200*1800 mm, 220V-400V-480V-500V-540V
Dongguan City, Guangdong Province, China
Product Description
1. The primary side is 1 loop with 6 contactors are configured each to control the output of 220V/400V/480V/500V/540V separately.
2. Push-button switch is used to control the output of the contactor. The loop contactor interlock can only have one voltage output.
3. The equipment is equipped with temperature monitoring (winding temperature, core temperature) switching, and the fan is started to cool when the internal temperature is higher than 60 degrees Celsius, and the fan is stopped when the internal temperature is lower than 45 degrees Celsius. Alarm sound occurs when the internal winding temperature exceeds135 degrees Celsius. The transformers automatically shuts down the total input power when the temperature is greater than 150 degrees Celsius.
4. Product total weight nearly 1500KG.
Electric Characteristics




2. Push-button switch is used to control the output of the contactor. The loop contactor interlock can only have one voltage output.
3. The equipment is equipped with temperature monitoring (winding temperature, core temperature) switching, and the fan is started to cool when the internal temperature is higher than 60 degrees Celsius, and the fan is stopped when the internal temperature is lower than 45 degrees Celsius. Alarm sound occurs when the internal winding temperature exceeds135 degrees Celsius. The transformers automatically shuts down the total input power when the temperature is greater than 150 degrees Celsius.
4. Product total weight nearly 1500KG.
Electric Characteristics
1 | Connection Group | Dyn11 |
2 | Rated capacity of primary winding | 150kW |
3 | Rated capacity of sencondary winding | 150kW |
4 | Primary rated line voltage (N1) | (220/400/480/500/540) *1 / Y connection, with N At 400V and above to meet the full power, The total power at 220V is 87KW |
5 | Secondary rated line voltage (N2) | 380V / D connection |
6 | Primary side impedence | / |
7 | Mains voltage fluctuation | < +/-5% |
8 | Working frequency | 50~70Hz |
9 | Efficiency | >97.5% (150kW resistive load) |
10 | The load cycle | Continous operation |
11 | Impedence voltage | <6% |
12 | Type of transformer | Dry type |
13 | The temperature sampling | Thermistor (NTC) temperature switch |
14 | Isolation resistance | P,S,E>500MΩ DC2500V/60s |
15 | Dielectric strength | <20mA 3KVAC/60s Coil-Core N1-N2 |
16 | Isolation grade | H(180ºC) |
17 | Allowable temperature rise | 95K (rated current, forced air cooling) |
18 | Noise | <70dB (measured with a sound level meter at 1m) |
19 | Cooling type | AF (Forced air cooling, control panel with independent control switch) |