GPR4850DR03
Single
2 Years
2900W
Full Range
Parallel Switching Power Supply
Self-excited Switching Power Supply
Width Modulation Type
Terminal Power Distribution Equipment
One-way Transmission
PWM
CE, RoHS, ISO, CCC
Gold Power
GOLD POWER
Carton Package
2U
China
8504401990
Product Description
50A rectifier for 48V telecom power system
Features
• Compact structure, high power density of 30W/in3 ;
• Constant current output available within output voltage 42-54V;
• Constant power output available within output voltage 54-58V ;
• Output voltage adjustable within 42-58Vdc
Default voltage: 53.5V;
• Wide operating temp. range: -33~+55°C
• Extended operating temp. range: +55~+65°C
• Power factor correction: ≥0.99
• RS485 communication port
• Input under-voltage protection
• Input over-voltage protection
• Output over-voltage protection
• Output over-current protection
• Compact structure, high power density of 30W/in3 ;
• Constant current output available within output voltage 42-54V;
• Constant power output available within output voltage 54-58V ;
• Output voltage adjustable within 42-58Vdc
Default voltage: 53.5V;
• Wide operating temp. range: -33~+55°C
• Extended operating temp. range: +55~+65°C
• Power factor correction: ≥0.99
• RS485 communication port
• Input under-voltage protection
• Input over-voltage protection
• Output over-voltage protection
• Output over-current protection
Applications
48V Distributed power system
Ethernet
Exchange
LAN, WAN
Server
Indoor wireless network
Telecom equipment
• Over temperature alarm and protection
• Paralleled work available via current sharing bus
• Remote start up/shutdown
• Hot -swappable
• UL 60950, CSAC22.2 60950-00,
VDE0805 and IEC60950 compliance
• CE mark meets directives of 73/23/EEC
and 93/68/EEC
• High efficiency up to 93%



Input | |||||
Parameter | Min. | Typ | Max. | Unit | Remarks |
Input Voltage Range | 90 | 110/220 | 290 | Vac | |
Input Frequency | 45 | 50/60 | 65 | Hz | Rated load |
Input current | 18.5 | A | |||
Input inrush current | 20 | A | |||
Power Factor | 0.99 | Rated input/rated load |
Output | |||||
Parameter | Min. | Typ. | Max. | Unit | Remarks |
Output Voltage Range | 42 | 53.5 | 58 | Vdc | Adjustable via the monitoring module (No load) |
Output Current Range | 0 | 50 | A | 154~290V ac Input | |
0 | 22 | A | 90~153V ac Input | ||
Output Efficiency | 92 | % | 220V AC Input (220Vac input, rated output voltage, 25% rated load current above, efficiency up to max. 93% ) | ||
86 | % | 110V AC Input | |||
Output Power | 2900 | W | Input: 200-240Vac; Output: 53.5Vdc | ||
1200 | W | Input: 115-130Vac; Output: 53.5Vdc; | |||
Regulation | ±1 | % | |||
Weighted Psophometric Noise | 2 | mV | |||
Wide Frequency Noise Voltage | 50 | mV | (3.4KHz~150KHz) | ||
20 | (150KHz~30MHz) | ||||
Ripple (Vp-p) | 200 | mV | Rated input voltage & load, with 0.1uF film capacitor and 10uF high frequency electrolyte capacitor, oscilloscope band width of 20MHz. |
Environmental Requirements | |||||
Parameters | Min | Typ. | Max | Unit | Remark |
Operating temp | -25 | 55 | °C | ||
Transportation temp | -40 | -70 | °C | ||
Storage temp storage temperature | -40 | 70 | °C | ||
Humidity | 5 | 95 | % | Relative humidity, no condensing | |
Altitude | 0 | 4000 | m | For operation at 3000-4000m, the operation temperature is derated by 1°C per 200m. | |
Acoustic noise | 55 | dB | |||
Cooling | Fan cooling; Front-in & rear-out; the fan locates at front side and have the function of temperature control & speed adjustment |
About us:


