Voltage: 0.6/1KV
Model: YJLV22 YJLV32 YJLV42...
Applications:
- Power transmission
- Electrical systems in buildings
- Industrial control and automation
- Transportation
Product advantage description:
The advantages of aluminum core power cable mainly include low cost, light weight, good corrosion resistance and oxidation resistance.Conductor: Oxygen-free Aluminum
Insulation material: Crosslinked Polyethylene
Insulation color: Natural Color or to be customized
Filling material: Non-hygroscopic Material
Inner sheath: PVC
Reinforcement: Steel Tape Armored (or to be customized)
Outer sheath: PVC/PE
Sheath color: Black
Physical property:
Maximum operating temperature of conductor:
70ºC (PVC insulation), 90ºC (XLPE insulation)
Minimum operating temperature:
-5ºC (PVC or LSZH sheath), -20ºC (PE sheath)
Short-circuit temperature (no more than 5 seconds) :
140ºC-160ºC (PVC insulation), 250ºC (XLPE insulation)
3+1-Core Aluminum Conductor XLPE Insulated Steel Tape Armored PVC Sheathed Power Cable(0.6/1KV) | ||||||||
No. of Cores and Nominal Cross Section | Thickness of Insulation | Thickness of Steel Tape | Thickness of Sheath | Approx. Overall Diameter | Approx. Weight | Max. DC Resistance of Conductor (20ºC) | Current Carrying Capacity(Ω/km) | |
(mm2) | (mm) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air (A) | In Ground (A) |
3×4+1×2.5 | 0.7/0.7 | 0.2 | 1.8 | 15.5 | 318 | 7.41/12.1 | / | 30 |
3×6+1×4 | 0.7/0.7 | 0.2 | 1.8 | 16.8 | 371 | 4.61/7.41 | / | 38 |
3×10+1×6 | 0.7/0.7 | 0.2 | 1.8 | 19.3 | 478 | 3.08/4.61 | 50 | 47 |
3×16+1×10 | 0.7/0.7 | 0.2 | 1.8 | 22.1 | 615 | 1.91/3.08 | 64 | 62 |
3×25+1×16 | 0.9/0.7 | 0.2 | 1.8 | 25.1 | 794 | 1.20/1.91 | 86 | 78 |
3×35+1×16 | 0.9/0.7 | 0.2 | 1.8 | 26.8 | 926 | 0.868/1.91 | 105 | 94 |
3×50+1×25 | 1.0/0.9 | 0.2 | 1.9 | 30.2 | 1175 | 0.641/1.20 | 125 | 110 |
3×70+1×35 | 1.1/0.9 | 0.2 | 2.0 | 35.1 | 1570 | 0.443/0.868 | 165 | 135 |
3×95+1×50 | 1.1/1.0 | 0.5 | 2.2 | 40.4 | 2359 | 0.320/0.641 | 200 | 160 |
3×120+1×70 | 12./1.1 | 0.5 | 2.3 | 45 | 2886 | 0.253/0.443 | 235 | 185 |
3×150+1×70 | 1.4/1.1 | 0.5 | 2.5 | 49.1 | 3396 | 0.206/0.443 | 270 | 205 |
3×185+1×95 | 1.6/1.1 | 0.5 | 2.8 | 54.3 | 4070 | 0.164/0.320 | 310 | 235 |
3×240+1×120 | 1.7/1.2 | 0.5 | 2.8 | 59.1 | 4855 | 0.125/0.253 | 365 | 260 |
3×300+1×150 | 1.8/1.4 | 0.5 | 3.0 | 66.0 | 6028 | 0.100/0.206 | 420 | 290 |
4+1-Core Aluminum Conductor XLPE Insulated Steel Tape Armored PVC Sheathed Power Cable(0.6/1KV) | ||||||||
No. of Cores and Nominal Cross Section | Thickness of Insulation | Thickness of Steel Tape | Thickness of Sheath | Approx. Overall Diameter | Approx. Weight | Max. DC Resistance of Conductor (20ºC) | Current Carrying Capacity(Ω/km) | |
(mm2) | (mm) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air (A) | In Ground (A) |
4×4+1×2.5 | 0.7/0.7 | 0.2 | 1.8 | 16.3 | 365 | 7.41/12.1 | / | 30 |
4×6+1×4 | 0.7/0.7 | 0.2 | 1.8 | 17.7 | 429 | 4.61/7.41 | / | 38 |
4×10+1×6 | 0.7/0.7 | 0.2 | 1.8 | 20.3 | 561 | 3.08/4.61 | 50 | 47 |
4×16+1×10 | 0.7/0.7 | 0.2 | 1.8 | 24 | 728 | 1.91/3.08 | 64 | 62 |
4×25+1×16 | 0.9/0.7 | 0.2 | 1.8 | 28.1 | 974 | 1.20/1.91 | 86 | 78 |
4×35+1×16 | 0.9/0.7 | 0.2 | 1.9 | 29.6 | 1134 | 0.868/1.91 | 105 | 94 |
4×50+1×25 | 1.0/0.9 | 0.2 | 2.0 | 34 | 1505 | 0.641/1.20 | 125 | 110 |
4×70+1×35 | 1.1/0.9 | 0.5 | 2.2 | 40.3 | 2351 | 0.443/0.868 | 165 | 135 |
4×95+1×50 | 1.1/1.0 | 0.5 | 2.3 | 44.8 | 2907 | 0.320/0.641 | 200 | 160 |
4×120+1×70 | 12./1.1 | 0.5 | 2.6 | 50.2 | 3588 | 0.253/0.443 | 235 | 185 |
4×150+1×70 | 1.4/1.1 | 0.5 | 2.8 | 54.6 | 4215 | 0.206/0.443 | 270 | 205 |
4×185+1×95 | 1.6/1.1 | 0.5 | 2.9 | 60.5 | 5133 | 0.164/0.320 | 310 | 235 |
4×240+1×120 | 1.7/1.2 | 0.5 | 3.0 | 67.1 | 6289 | 0.125/0.253 | 365 | 260 |
4×300+1×150 | 1.8/1.4 | 0.5 | 3.2 | 73.7 | 7544 | 0.100/0.206 | 420 | 290 |
3+2-Core Aluminum Conductor XLPE Insulated Steel Tape Armored PVC Sheathed Power Cable(0.6/1KV) | ||||||||
No. of Cores and Nominal Cross Section | Thickness of Insulation | Thickness of Steel Tape | Thickness of Sheath | Approx. Overall Diameter | Approx. Weight | Max. DC Resistance of Conductor (20ºC) | Current Carrying Capacity(Ω/km) | |
(mm2) | (mm) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air (A) | In Ground (A) |
3×4+2×2.5 | 0.7/0.7 | 0.2 | 1.8 | 16.6 | 354 | 7.41/12.1 | / | 30 |
3×6+2×4 | 0.7/0.7 | 0.2 | 1.8 | 18 | 416 | 4.61/7.41 | / | 38 |
3×10+2×6 | 0.7/0.7 | 0.2 | 1.8 | 20.9 | 531 | 3.08/4.61 | 50 | 47 |
3×16+2×10 | 0.7/0.7 | 0.2 | 1.8 | 24 | 694 | 1.91/3.08 | 64 | 62 |
3×25+2×16 | 0.9/0.7 | 0.2 | 1.8 | 28.1 | 920 | 1.20/1.91 | 86 | 78 |
3×35+2×16 | 0.9/0.7 | 0.2 | 1.9 | 29.6 | 1034 | 0.868/1.91 | 105 | 94 |
3×50+2×25 | 1.0/0.9 | 0.2 | 2.0 | 34 | 1400 | 0.641/1.20 | 125 | 110 |
3×70+2×35 | 1.1/0.9 | 0.5 | 2.2 | 40.3 | 2153 | 0.443/0.868 | 165 | 135 |
3×95+2×50 | 1.1/1.0 | 0.5 | 2.3 | 44.8 | 2658 | 0.320/0.641 | 200 | 160 |
3×120+2×70 | 12./1.1 | 0.5 | 2.5 | 50.2 | 3329 | 0.253/0.443 | 235 | 185 |
3×150+2×70 | 1.4/1.1 | 0.5 | 2.6 | 54.6 | 3790 | 0.206/0.443 | 270 | 205 |
3×185+2×95 | 1.6/1.1 | 0.5 | 2.8 | 60.5 | 4575 | 0.164/0.320 | 310 | 235 |
3×240+2×120 | 1.7/1.2 | 0.5 | 3.0 | 67.1 | 5564 | 0.125/0.253 | 365 | 260 |
3×300+2×150 | 1.8/1.4 | 0.5 | 3.2 | 73.7 | 6801 | 0.100/0.206 | 420 | 290 |






2. How does your company conduct quality control?
- We conduct strict control over the use of raw materials
- All details of the production process are closely watched by professional workers
- Quality Control Department monitors the whole process of production
- All products can only be delivered after the pass of the inspection by our own testing equipment
Sample is free and customers only need to pay for its delivery.
4. What is your minimum order quantity?
The minimum order quantity varies by product type, please contact us for confirmation.
5. Can you customize it?
Yes. Please provide the specific requirements.
6. How long is your production cycle?
Usually 7-20 days, depending on order quantity and specifications.