600V 1000V 2000V 2500mcm 750mcm Conductor XLPE Insulation Electrical Power PV Solar Cable Aluminium PVC Power Electric Enameled Wire Building UL Standard 4703

Price $50.00 Compare
Min Order 2000 Meters
Shipping From Hebei, China
Popularity 294 people viewed
Quantity
+-
 

Hebei Huatong Wires & Cables Group Co., Ltd.

VIP   Audited Supplier 10 years
Profile Certified by SGS/BV
PV
Insulated
Stranded
Heating, Building
Copper
None
XLPE
Round Wire
Conduit or Recognized Raceways for Services
ISO9001, CE, CCC, RoHS, VDE
Huatong
600V 1000V 2000V
Solar Energy System
90ºC(-40ºC)
as Customer Requirement
Black Red White
HT CABLES
Coils and Drums
1awg-1000mcm
China
8544492100
Product Description
          

Product Description

Features:

Sunlight, ozone, and UV resistant

Moisture resistant

RoHS compliant

REACH compliant

-40°C to +150°C temperature range

 

Standards:
UL-4703, UL-854, UL-44
UL 1685-FT4/IEEE 1202 (70,000 Btu/hr) Flame Test (1/0 AWG and larger)
ICEA T-29-520 (210,000 Btu/hr) Flame Test
NEMA WC70/ICEA S-95-658
NFPA 70: National Electrical Code (NEC)

 

Conductors:
Al alloy  Stranded conductors, or uncoated copper per ASTM-B787 and ASTM-B8


Insulation:
Cross-linked polyethylene (XLP) insulation per UL-854, UL-4703 and UL-44

 

voltage:

600v,1000v,2000v


Applications:
Type Photovoltaic copper conductors are suitable for outdoor rooftop applications without conduit and for use in conduits and raceways installed underground in conduit in wet locations, and where condensation and moisture accumulations within the conduit do not exceed 90ºC. Applications requiring direct burial is permitted for Type Photovoltaic per UL-854. Applications requiring type Photovoltaic conductor, temperatures shall not exceed 90ºC in wet or dry locations.

 
Features:
Available in 600V and 1000V/2000V. All cables comply with UL's VW-1 (Vertical Wire) Flame Test. Insulation compounds are rated for flame and sunlight-resistance in all sizes and colors. Photovoltaic conductors of 1/0 through 1000 KCMIL are rated for CT use. Sequential foot markings located every foot on master reels only for 1 AWG through 1000 KCMIL unless otherwise specified. RoHS compliant. Flexibility at Low Temperature Test. Carries -40 °C  rating.

 
 Insulation Thickness XLPE mmOutside Diameter mmAllowable Ampacity(Amps)Approximate Net Weight(lbs/1000 ft) 
Number of 
Strands 
SizeAWG600V1000V600V1000V600V1000V600V1000V600V1000V 
2000V2000V2000V2000V2000V
1419190.060.0754.895.6125252428
1219190.060.0755.376.0530303338
1019190.060.0755.996.640404752
87*7*0.0750.0857.527.9555557478
67*7*0.0750.0858.488.867575108113
47*7*0.0750.0859.710.069595161166
37*7*0.0750.08510.4110.77110110197203
27*7*0.0750.08511.2311.58130130243249
119190.0950.10513.1613.49150150313320
1/019190.0950.10513.9714.48170170380389
2/019190.0950.10515.0915.6195195476484
3/019190.0950.10516.3616.87225225590599
4/019190.0950.10517.7818.29260260732742
25037370.110.1219.3519.86290290873884
30037370.110.1220.6721.1832032010351047
35037370.110.1221.8722.3835035011981210
40037370.110.1222.9923.538038013581371
50037370.110.1225.0425.5543043016801694
60061610.1250.13529.0329.5447547520572073
75061610.1250.13531.732.2153553525082525
100061610.1250.13535.6136.12615

615

Company Profile

 


 
Message Type
* Message Content
* Name  
* Phone
* Email
* CAPTCHA