60Hz Dx Vertical / Horizontal Air to Air Ducted Split Air Handling Unit with Pre/Medium/HEPA Filter Ahu

Price $18988.00 Compare
Min Order 1 Piece
Shipping From Shandong, China
Popularity 385 people viewed
Quantity
+-
 

Jinan Amrta Air Conditioning Co., Ltd.

VIP   Audited Supplier 8 years
Profile Certified by SGS/BV
AA
Chiller
Galvanized Sheet
General
380-415, 440, 460, 50/60Hz
Ordinary
Supermarket, Hospital, Pharmaceutical and Building
Split
15~20 years
ISO, CE
New
Copeland/Pansonic Brand
World Famous Brand
Commercial/Industrial
Cooling Only or Heat Pump
R22/R407c/R410A/R134A
Pre, Medium and HEPA(Optional)
Vertical and Horizontal Use
AMRTA or OEM
Standard Package Fit for Transportation
Color: white
China
8418612090
Product Description
60Hz DX Vertical / Horizontal Air to Air Ducted Split Air Handling Unit  with Pre/Medium/HEPA Filter AHU

Cooling capacity 20kW ~ 104kW 

Product Description

11 sizes available ranging from 19.5 kW to 103.7 kW cooling capacity.
Cooling only and heat pump version.
Wide application as hotel, apartment, villa, factory, shopping center, office building, school, etc.
Panels and frame are made from metal steel protected with polyester powder painting to ensure total resistance to atmospheric agents.
High efficiency scroll compressor for the whole range, with built-in thermal overload cut-out and crankcase heater, mounted on rubber vibration dampers.
Compact indoor design, long air supply distance.
Outdoor units are equipped with low noise axial fans.
Indoor units are equipped with quiet centrifugal fans.

Split installation, connected by means of flare/welding coupling.

Easy operation line controller:
  • Cooling/Heating/Fan/Auto
  • Timing On/Off
  • Error indication

Multi safety protection
  • High/low pressure protection
  • Time delay and antifreeze switch
  • Phase sequence relay
  • Current overload protection
  • Overheat protection
OPTIONAL
Additional electric heater on indoor unit
Additional heating coil on indoor unit


TECHNICAL DATA 
 
Mod.   202532364248
Nominal cooling capacity*kW19.524.831.235.641.347.4
Nominal heating capacity**kW22.628.935.840.846.954.4
Connection       
Method/FlareFlareFlareWeldingWeldingWelding
Liquid pipe diameter¢mm9.52x212.7x212.7x215.88x115.88/12.715.88/12.7
Gas pipe diameter¢mm15.88x219.05x219.05x228x128/19.0528/19.05
Power supply/230V/3N/60Hz
OUTDOOR UNITCompressor  
Qty/refrigerant circuitNr.2/22/22/21/12/22/2
Cooling power input*kW7.29.311.812.815.117.9
Heating power input**kW7.139.2111.6812.6714.9517.72
Energy adjustment%50-10050-10050-1000-10040-60-10033-66-100
Axial fans   
Quantity  Nr.111122
Airflow m3/h9400940012500142001880018800
Sound pressure level***dB(A)676768707171
Net weightkg170180220280260280
INDOOR UNITCentrifugal fans       
QuantityNr.222222
Airflowm3/h350045005650645074008550
ESPPa120100150130180200
Sound pressure level***dB(A)646466666868
Net weightkg90100150160180200
Additional electric heater****kW2×32×42×52×62×62×8
Additional heating coil****kW22.228.435.140.046.053.3
 
Mod 52627288104
Nominal cooling capacity*kW51.363.371.387.9103.7
Nominal heating capacity**kW58.972.681.9100.0115.8
Connection      
Method/WeldingWeldingWeldingWeldingWelding
Liquid pipe diameter¢mm15.88/12.715.88×215.88×215.88×219.05×2
Gas pipe diameter¢mm28/19.0528×228×228×235×2
Power supply/230V/3N/60Hz
OUTDOOR UNITCompressor 
Qty/refrigerant circuitNr.2/22/22/22/22/2
Cooling power input*kW18.423.126.628.139.3
Heating power input**kW18.2222.8726.3327.8238.91
Energy adjustment%30-70-10050-10050-10050-10050-100
Axial fans 
QuantityNr.22222
Airflowm3/h2150026500298803650043500
Sound pressure level***dB(A)7171717171
Net weightkg330460460780800
INDOOR UNITCentrifugal fans      
QuantityNr.22222
Airflowm3/h925011450129001480017100
ESPPa200300300280500
Sound pressure level***dB(A)6868696970
Net weightkg220230300320400
Additional electric heater****kW2×82×102×102×122×14
Additional heating coil****kW57.871.280.398.0113.5

Performance values refer to the following conditions:
* Cooling capacity is measured under the condition: indoor temperature DB 27°C/ WB 19°C, ambient temperature DB 35°C / WB 24°C.
** Heating capacity is measured under the condition: indoor temperature DB 20°C / WB 15°C, ambient temperature DB 7ºC / WB 6°C.
*** Sound pressure measured at a distance of 1 m and a height of 1.5 m above the ground in a dear field.
**** Optional as request.

Unit Pictures


Some Overseas Simple Projects



Our Products Range




Contact Information

Anne 
 
 
 
----------------------------------------------------------------------------------
JINAN AMRTA AIR CONDITIONING CO.,LTD
 
Website: jinanamrtaac.en.made-in-china.comjinanamrtaac.en.made-in-china.com

Message Type
* Message Content
* Name  
* Phone
* Email
* CAPTCHA