Technical Description
Type: IEEE type1/2
Primary voltage: up to 34.5 kV
Secondary voltage: 120/240V
Rating power: up to 500 kVA
Single Phase Pad Mounts Transformer Specifications:
Design Capacities | |
Primary voltage up to 34.5 kV | Secondary voltage 120/240 V |
Rating power up to 500 kVA | |
Built to customer specifications in accordance with IEEE Std C57.12.00 and DOE | |
Standard | |
Implement ANSI/IEEE C57.12XX; DOE;IEC | |
Service Conditions | |
Design ambient temperature 0°C or 50°C | |
Design altitude less than 1000m above sea level | |
Types: | |
According to ANSI® C57.12.25-1990 standard: | |
ANSI Type-1 | ANSI Type-2 |
Standard Accessories and Features | |
HV & LV Bushings | Pressure relief device |
nameplate engraved | Drain and filling plug |
Parking Stand | Grounding Bracket and X0 strap |
Bay-o-net & current limiting fuse protection | |
Exterior Finish conforming to ANSI C57.12.28 | |
Optional Accessories and Features | |
Transformers may be provided with the following optional items if specified by the purchaser: | |
An anticorrosion skirt for high contaminated areas | |
Load break switches | Thermometer |
Liquid Level Gauge | High voltage off circuit taps |
Provision for padlocking of load break switches | |
Stud type or spade type low voltage bushings | |
Load break inserts complete with dust cap | |
Exterior Finish conforming to ANSI C57.12.28 | |
Customer stock code and stencilling | |
Bail tabs on the bushing well clamps | |
Provision for a remote fault indicator light | |
Alternative protection devices, specified by the pu rchaser | |
Purchaser specified impedance limits | |
FR3 fire resistant bio degradable insulating fluid LNAN | |
A non resettable device that detects internal transformer faults, incorporates pressure relief,and provides an external indication | |
Permanent and/or temporary bar coding label as shown in ANSI/IEEE C57.12.35 | |
Additional tests may be requested by the purchaser and shall be performed in accordance to ANSI/IEEE C57.12.90 |
Single Phase Pad Mounted Transformer General:
• General: KERUN manufactures a complete line of single phase residential pad mounted distribution transformers in its KERUN Power™ series product line. They are available in standard ratings and configurations or can be customized to meet specific needs.
• Single-phase transformers are available as ANSI I & II transformers (shown above in order). All of these distribution transformers are oil-insulated, selfcooled, available in loop or radial feed, and are dead-front.
• All of these transformers meet or exceed ANSI®, IEEE® and NEMA® standards.
• The ANSI® and IEEE® Type-1frontplate arrangement allows vertical feed to the primary and secondary bushings. It is ideal for single-phase industrial and residential applications where a wide range of kVAs or heavy cabling is required.
• KERUN offers KERUN Power™ series poly-pads that are usable with most transformers conforming to ANSI® C57.12.25-1990 standard (Type-1 or Type-2).
Single Phase Pad Mounted Transformer Advantage:
• KERUN utilizes a focus factory concept which leads to a great experience in specific products giving a very high level of consistency in design, manufacture, and test.
• KERUN distribution transformers factories utilize the common design platform giving us best-in-class experience, consistency, and repeatability.
• KERUN utilizes best-in-class manufacturing and quality processes to ensure that our transformers will meet the most stringent requirement.
Single Phase Pad Mounted Transformer Features:
• KERUN oil immersed single phase pad mounted distribution transformer include Loop feed type and Radial feed type. They are mounted ground and under ground. These transformers typically service urban and rural residential and commercial loads.
• KERUN oil filled single phase pad mount transformer are used in underground industrial and residential power distribution systems, for Industrial, Commercial, Institutional and Residential areas, where safety is prime concern.
Single Phase Pad Mounted Transformer Manufacturers:
KERUN engineers have 40 years of experience in the transformer industry and have accumulated a wealth of experience in participating in different projects in various countries. Based on project cooperation cases, KERUN can help you analyze the types of transformers you need in project construction and provide complete power distribution and other solutions.




A:Sourceway is a company in growth. We have reached many of our goals, and established solid marketing foundation in many countries.
Q:Are you a manufacturer or a trading company?
A:We are a professional transformer manufacturer with more than 20 year's experience.Support OEM&ODM.
Q:Which markets do you mostly export to?
A:We are exporting to more than 20 countries in South America, North America, Europe, Middle East, Africa and so on.
Q:What certificates and standards do you have?
A:ISO9001-2008, OHSAS 18001:2007, ISO4001:2004L certificates. A:IEC, ANSI, KEMA, GOST standard.
Q:How long is your delivery time?
A:After determining the plan, we will complete production and shipping within 20 days. It mainly depends on the quantity.
Q:What is the standard of package?
A:Our nomal package are divided into three types:wooden pallets, wooden frames, and wooden boxes.Also it can be customized.
Q:What currencies and payment Type do you support?
A:Payment Currency:USD,CNY.
Payment Type:T/T,L/C.
Q:Why choose KERUN?
A:After comparing the quality, delivery and price of the same products, believe you will choose KERUN.