64/110kv Fully Prefabricated Type Straight Through Joint

Price $3000.00 Compare
Min Order 3 Sets
Shipping From Jiangsu, China
Popularity 271 people viewed
Quantity
+-
 

Suzhou Jiuwei Electric Made Co., Ltd.

VIP   Audited Supplier 2 years
Profile Certified by SGS/BV
YJJJI
Termination
Power
38/66kv
Silicone Rubber
Grey
Connect Cable
IEC60502
9V
Wooden Case
240-1600mm2
China
8535900090
Product Description
66-220kV High Voltage Cable Accessories
Our company provides the voltage level of 48/66kV, 64/110kV, 127/220kV and other series of cable accessories are all in accordance with IEC 60502, IEC 60840, IEC 62067, IEC 60859, IEC 62271-209, GB/T 11017, GB/T 18890, GB/T 12706, GB 311, GB 772, DL508, DL509, JB/T8144 and other standards, and have passed the stringent factory test, type test, pre-qualification test.
One piece pre-molded straight joint/sectionalizing joint
Scope of application

For cross linked polyethylene insulated power cables 240-3000mm2.
Suitable for large-scale chemical industry, iron and steel, power substations, coastal areas.
Features
The main body is a monolithic prefabricated structure, i.e. insulation, shielding and stress cone in one piece.
The stress cone is made of imported liquid silicone rubber injection molding, with a long and stable holding force and electric field uniformity.
Compact structure, small size, light weight, easy to install.
The shell is protected by an insulated, magnetically isolated metal protection box with good mechanical properties and good sealing.
Structure & Size

1,glass fiber   
2,copper shell   
3,stress cone
4,insulation of cable  
5,epoxy insulating insulation
6,connecting pipe   
7,shielding tiles
8,prefabricated body  
9,coaxial cable  
10,cable
 
Size / mm38/66kV50/66kV64/110kV76/132kV127/220kV
L13001300150015001800
A19001900210021002400
Test Specification
All test classifications and codes:
No.#Test NameCode
1Routine testR
2Sample testS
3Type testT
4Pre-qualification testP
5Additional testA
The following routine tests are performed on stress cones, epoxy bushings of GIS terminals and prefabricated intermediate joints of each product at 66kV and above.
ItemVoltage
38/66kV50/66kV64/110kV76/132kV127/220kV
Partial discharge54kV, no detectable local discharge over background72kV, no detectable local discharge over background96kV, no detectable local discharge over background114kV, no detectable local discharge over background190kV, no detectable local discharge over background
The power frequency withstand voltage90kV/30min125kV/30min160kV/30min190kV/30min318kV/30min
SealingSeal fittings, porcelain bushings, composite bushings for 0.25±0.01MPa/1h, no leakage
The epoxy casing was subjected to 0.6~0.7MPa/1h with no leakage.
AppearanceThe products are free of damage, cracks, and other defects that may affect the quality and appearance of the products.
66-220kV Main Test Parameters
ItemStandardTest CategoryProduct Category
48/66kV64/110kV127/220kVPorcelain Sleeve TerminalComposite Sleeve TerminalGIS terminalStraight / Insulated Jointflexible terminal
Sealing Fittings, Porcelain, Composite Sleeves0.25±0.01MPa/1h, no leakageRyesyesyes--
Epoxy Sleeve0.6~0.7MPa/1h, no leakage
Partial discharge of prefabricated parts72kV96kV190kVRyesyesyesyesyes
Detects no more than background discharge
Frequency withstand voltage of prefabricated parts 120kV160kV318kVRyesyesyesyesyes
30min,no flashover, no breakdown
Partial discharge at room temperature72kV96kV190kVTyesyesyesyesyes
Detects no more than background discharge
Thermal cycling voltage test96kV128kV254kVTyesyesyesyesyes
20 cycles, no flashover, no breakdown
Partial discharge test at high temperature72kV96kV190kVTyesyesyesyesyes
Detects no more than background discharge
Lightning impact test and subsequent frequency withstand voltage test450kV550kV1050kVTyesyesyesyesyes
10 times for each positive and negative polarity
120kV160kV318kV
15min, no flashover, no breakdown
Directly buried joint outer protective layer immersion voltage testTwo ends impact among the 60/75kV,an end of hit 30/37.5kVTwo ends impact among the 60/95kV,an end of hit 30/47.5kVT---yes-
Sealing test after assembly of accessories0.25±0.01MPa/1h, no leakageTyesyesyesyesyes
Outdoor terminal rain frequency voltage test140kV185kV460kVTyesyes--yes
1min, no flashover, no breakdown
Pillar insulator voltage test20kV/1min, no flashover, no breakdownTyesyes---
Radio interference test for outdoor terminals61kV81kV140kVAyesyes--yes
1MHz radio interference, voltage ≤ 450μV1MHz radio interference, voltage ≤ 500μV
Accessory specimen testVisual inspection of accessory systems containing cables with no signs of deterioration that could affect the normal operation of the systemTyesyesyesyesyes
DC voltage test/No breakdown between conductor and metal shield in connector, 20kV/1min.T---yes-
Performance test of crimped connectors for conductor connecting rodsThe total area after crimping is not more than 1.2 times the resistance of an equal length of conductor of the same cross-section.Tyesyesyesyesyes
 