ECSL0660-L59A
Electronic, Instrument
Current Transformer
Single
Indoor
Measurement
Single Layer & Tightly Wound Type
Insulating Paper
Active Type
Single Stage Type
Electromagnetic Type
ECHUN
200PCS/Box
China
8504500000
Product Description
UL 2808 XOBA 6mm 30A Split core current transformer with 2V output open core sensor
The ECSL06 series are split-core current transformers. The CT can be mounted to existing panels, such as control centers or load centers, to measure or monitor wattage. These CTs can be mounted without removing existing cables for easier installation
Customized current ratio available.
Rated Primary Current(Amp.) 50/60Hz | 60nom(0.1~60A max) |
Turn ratio | Np:Ns=1:3000 |
Output voltage | 60A/2V(Resistor inside the CT) |
Accuracy | 1% |
Phase Error at Rated Current Range | ≤ 2° |
Operating Temperature Range | -40~70ºC |
Storage Temperature Range | -45~85ºC |
Dielectric Withstanding Voltage(Hi-pot) | 3.51KV/1mA/1min(CATIV 250V & CATIII 600V) |
Applications:
Current measurement
Monitoring and protection
Energy and sub-metering products
Network equipment
Instruments and sensors
Control systems
Advantage:
Mount easy.
Excellent linearity over the whole range.