OIP
High-voltage, Insulators
Porcelain
Bushing Insulator
B Type Insulator
High Voltage Power Transmission, Insulation, Electrical Installation
Trough Type
550KN
ISO9001
Brown
Rib
30 Days
Sea
1 Year
Support
Inorganic Insulation
Organic Insulating Material
RIB or OEM
Wooden Pallet
500kg
Jiangsu
8546900
Product Description
Electrical Specifications of OIP Condender Transformer Bushing | |||||||||||
Standard | GB/T 4019-2022 | ||||||||||
Highest Voltage of the Equipment Um | kV | 72.5 | 100 | 126(123) | 145 | 170 | 252(245) | 300 | 363(362) | 420 | 550 |
Rated frequency | Hz | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 |
Power Frequency Withstand Voltage | kV | 155 | 205 | 255 | 305 | 355 | 505 | 505 | 560 | 750 | 870 |
Lightning Impulse Withstand Voltage | kV | 325 | 450 | 550 | 60 | 750 | 1050 | 1050 | 1175 | 1550 | 1800 |
Rated Current | A | 4000 | 4000 | 4000 | 4000 | 4000 | 3150 | 3150 | 3150 | 3150 | 3150 |
Temperature | ºC | Outdoor: -60ºC ~ +55ºC |
Some Information about the OIP Capacitive Bushing of RIB
OIP condenser transformer/reactor bushing is mainly used for power transformer/reactor as current carrier for leading in and out current of high voltage side, middle voltage side and low voltage side of transformer as well as insulate the oil tanks of power transform//reactor.