72.5kv-132kv-230kv Capacitor Voltage Transformer (CVT)

Price $100000.00 Compare
Min Order 10 Pieces
Shipping From Zhejiang, China
Popularity 463 people viewed
Quantity
+-
 

Ningbo Hyuan Power Industry Co., Ltd.

VIP   Audited Supplier 8 years
Profile Certified by SGS/BV
CVT
High Frequency Ceramic Capacitor
Power
Through Hole
Fixed Capacitor
High Frequency Coupling
HEMG
Wooden
300KV
China
Product Description




This series of capacitor voltage transformers include the products with the type of TYO 150/\/'3-0.01 H (TYD161/v3-0.01 H), TYD150~13-0.02H (TYD161/v3-0.02H), TYD220~-0.00SH, TYD220~- 0.01 H, TYD330kv/110v-0.00SH, TYD330kv/115v-0.01H, TYD500kv~110v-0.00SH etc., which can be used for electric measurement and relay protection in the electric power system with a voltage of 150~500kV and frequency of 50Hz. The products are in accordance with the requirements of the standard GB 4 703 "Capacitor Voltage Transformers",GB19749 "Coupling capacitors and capacitor voltage dividers" & IEC 60044-5 "Capacitor Voltage Transformers".

 
TECHNICAL DATA SCHEDULE
    CAPACITOR VOLTAGE TRANSFORMER 330 kV
CODE NO: 4132
ITEMDESCRIPTIONUNITSREQUIREDGUARANTEED
1.0Manufacturer   
1.1Type--Capacitive
1.2
1.3
Model no  
Country of Origin
-
-
-
 
TYD330/3-0.0044H
     
2.0Nominal characteristics   
2.1Voltage   
2.1.1Rated voltagekV330330
2.1.2Rated voltage classKV362362
2.2Rated frequencyHz5050
2.3Network neutral grounding-EffectiveEffective
2.4Rated voltage factor for 30 s-1,51.5
2.5Rated lightning impulse withstandkV11751175
2.6Chopped lighting impulse withstand (3 ms)kV12901290
2.7Switching impulse withstand (wet)kV950950
2.8Power frequency withstand voltage (1 min)kV450450
2.9Creepage distancemm/kV3131
2.10Max. radio interference voltage at 0,5 MHz per IEC 694mV25002500
2.11Capacitance C1 and C2pf44004400
2.12Series reactor
- inductance range
- resistance range
 
mH
ohms
 
0.2
-
0.2
 
400
2.13Transformation ratio-  330kV/Ö3
 : 0,11kV/Ö3
 : 0,11kV/Ö3
 (: 0,11kV/Ö3)
330kV/3
: 0,11kV/3
: 0,11kV/3
     
2.14Transformer characteristics
- HV/LV turn ratio range
- Normal operating flux density
 
-
tesla
 
-
-
 
3000:1
0.5T
2.15Primary voltagekV330/Ö3330/Ö3
2.16Secondary voltageV110/Ö3110/Ö3
2.17Winding accuracy:   
 - metering class-0,20,2
 - protection class-3P3P
 - burden ( on each winding)VA5050
2.18Number of secondary winding-2 (3)2
2.19Winding conductor-CuCU
2.20Circuit Diagram-To be enclosed with bidTo be enclosed with bid
2.21HV Terminal connector for-TBA 
     
3.0Weights and Dimensions   
3.1Weight for operationkg-950
3.2Weight for transportkg-1000
3.3Heightm-4370
3.4Shipping dimensions (H x W x D)m-800*700*2600
3.5Outline drawing number-To be enclosed with bidTo be enclosed with bid
4.0Type tests reports N°-To be enclosed with bidTo be enclosed with bid
5.0Standards-IEC 60044-5
IEC 60694
  IEC 60947-1
IEC 60044-5
IEC 60694
IEC 60947-1
6.0Quality control-ISO -----------ISO9001
     
7.0Installation-Outdoor, Substation SwitchyardOutdoor, Substation Switchyard
8.0Installation-Outdoor in substation switchyard 
Message Type