AMC100-FDK48
2 Years
2 Years
Digital
DIN Rail
Multi-Functional Energy Meter, Watt-Hour Meter, Meter for Industry and Home Use, Standard Electric Energy Meter, Reactive Energy Meter, Multi-rate Watt-hour Meters
Three Phase
Electronic Meter
Terminal
Continuous Wave
Energy Meter
RoHS, ISO, CE
Customized
48VDC,240VDC,336VDC
Voltage, Current, Power, Electric Energy
5V
Voltage/Current Level 0.5
Powered by Amc100-Zd,DC 12-24V Powersupply Alone
RS485/Modbus-RTU
Method DIN35mm Rail or Bottom Plate Installation
Acrel
Carton
170*150*130mm
China
8501109190
Product Description
AMC100 DC Precision Power Distribution Monitoring Device
With the rapid development of data centers, the energy consumption of data centers has become more and more prominent, and the energy management and power supply and distribution design of data centers have become a hot issue. Efficient and reliable power distribution system scheme of data centers is an effective way to improve the power efficiency of data centers and reduce the energy consumption of equipment. In order to realize energy saving in data center, first of all, it is necessary to monitor each power load. However, there are many load loops in data center, and traditional measuring instruments cannot meet the requirements of cost, volume, installation, construction and other aspects. Therefore, it is necessary to adopt multi-loop monitoring device suitable for centralized monitoring requirements in data center.
AMC100 series DC precision power distribution monitor is a measurement device designed specifically for power management of data center servers. The device design exquisite, can for A + B two into line and 192 road for electrical parameters, the input and output parameters of the switch state and the lightning protection device such as real-time monitoring, all alarm threshold measurement channels can be set in A separate, to qualify the limit event trigger system sound and light alarm, immediately on the volume in the traditional instrument, the height of the monitoring circuit integration.


Item | Data |
Measurement parameters | Voltage, current, power, energy, switching status |
Bus voltage rated | 48VDC,240VDC,336VDC |
Current outgoing loop rated | 5V (Hall sensor, external supply required ±12V) |
Measurement accuracy | Voltage/current 0.5 level, power/energy level 1 |
Auxiliary power supply | Powered by AMC100-ZD, DC 12-24V when used alone |
Communication | RS485/Modbus-RTU |
Installation method | DIN35mm rail or baseplate mounting |
Storage temperature | -25°C~ 70°C |
Working temperature | -15°C~55°C |
Relative humidity | ≤ 93% |
Elevation | ≤2500m |
Protection level | IP20 |
Pollution level | 2 |
Security Insulation | The insulation resistance between all terminals and the conductive parts of the housing is not less than 100MΩ |
Antistatic interference | Level 4 |
Resistant to RF electromagnetic field radiation | Level 3 |