(Embedded pole/cast pole) 40.5kv AC/DC 3poles indoor high voltage vacuum circuit breaker

Price Negotiable Compare
Min Order 1 Piece
Shipping From Hubei, China
Popularity 480 people viewed
Quantity
+-
 

Wuhan Feite Electric Co., Ltd.

VIP   Audited Supplier 5 years
Profile Certified by SGS/BV
ZN85-40.5
High Voltage Circuit Breakers
Electric Type
High-Speed Circuit Breaker
Vacuum
Open Frame
ACB
3
Circuit Breaker
Overcurrent Protection, OVP(Overvoltage Protection)
ISO9001-2000
China
Product Description
VHE-40.5 vacuum circuit breaker with rated voltage 40.5kV, three-phase ac 50HZ indoor distribution device,Is the new product that developed by our company independently.  We have the intellectual property rights, the product can be compatible with the products such as ZN85.VN1.VBD and so on.

VHE-40.5 embedded indoor vacuum circuit breaker (hereinafter referred to as the circuit breaker), Is a type of high voltage switch equipment which appropriate to 40.5kv,50Hz three phase alternating current system.  For points and load current,Overload current,Fault current of industrial and mining enterprises,power plant and substation.  Vacuum circuit breaker pole insulation has experienced air insulation- composite insulation - embedded insulation,It has formed three generations of vacuum circuit breaker. In the first generation -air insulation,live part exposed in air, Its insulation affected by dust,moisture, Insects and so on. In the second generation- composite insulation,The arcing chamber protected by epoxy resin sleeve. But the sleeve does not wrap the high-voltage electric parts wholly,It would be affected by dust,Moisture,Insects and so on.  The third generation of insulation is embedded pole,By the APG process, Using epoxy resin to seal the whole arc extinguish chamber and the upper and lower outlet.  To do this, Not only reduce the arcing chamber size and also completely unaffected by the external environment (dust, moisture, etc.) so that improve the weatherability,Epoxy resin at this time not only as a part of the main insulation,At also be a support for the mechanical,The electric field distribution and the stress distribution is superior to the various shapes of insulating clapboard structure. Vacuum circuit breaker and operating mechanism adopts upper and lower arrangement structure,Effectively reduce the depth of the vacuum circuit breaker.Spring operating mechanism is specifically designed for this new type of vacuum circuit breaker,Installed in the vacuum circuit breaker frame,The structure is more suitable for the upper and lower arrangement structure,And become the integral part of the overall structure of vacuum circuit breaker. The simple mechanism design,The output curve and its performance is more suitable for the characteristics and requirements of 40.5kV vacuum circuit breaker.  The overall layout is reasonable, beautiful,Simple,small volume,Flexible operation, Reliable performance,With electrical characteristics of long service life,Convenient maintenance,Free maintenance machanism.  The vacuum circuit breaker is suitable for frequent operation ,Various occasions and operating conditions which are harsh place.
 

No.

Item

Unit

Value
1Rated voltageKV40.5
2
Rated insulation level

Rated lighting impulse withstand Voltage (peak)
KV185
1min
Short-time power frequency withstand voltage(1min)
KV95
3
Rated short circuit breaking current
KA2531.5
4Rated currentA1250/16001250/1600/2000
5
Rated withstand current(peak)
KA6380
6
Rated operations of short circuit breaking current interruption
 20
7Rated duration of short circuit S4
8
Rated operating sequence
 -0.3S--180S-
Opening-0.3S-closing opening-180S-closing opening
9
Closing and brake device circuit of power supply voltage
VAC,DC220   AC,DC110
10Closing timems50~100
11Opening timems30~60
12
Rated breaking current( a capacitor)
A630
13
Rated breaking current(back to back capacitor)
A400
14Mechanical life 20000
 

No.

Item

Unit

Value
1Contact distancemm18±1
2Contact over travelmm6±1
3Average opening speedm/s1.6±0.2
4Average closing speedm/s0.8±0.2
5
Contact bouncing duration at closing operation
ms2
6Operating mechanism type 3AVSpecial spring mechanism
7Three-pole simultaneityms≤2
8
Conductive circuit resistance  of each phases
μΩ<45