GSM3E series of adjustable Molded Case Circuit Breakers MCCB

Price $200.00 Compare
Min Order 1 Piece
Shipping From Gansu, China
Popularity 212 people viewed
Quantity
+-
 

Gansu A&D Trading Co., Ltd.

VIP   Audited Supplier 15 years
Profile Certified by SGS/BV
GSM3E
Low Voltage Circuit Breakers
Energy-storage Type
Normal Type Circuit Breaker
Air
Vertical, Horizontal
MCCB
3P, or 4P
Circuit Breaker
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection, OVP(Overvoltage Protection)
CE
-25 to 75 centigrade
2000m, if higher than 2000m, derate
3
3
TIANSHUI 213
Carton
IEC60947-2
China
8536200000
Product Description

GSM3E series of adjustable molded case circuit breaker (GSM1 MCCB, adjustable)

General Introduction

GSM3E series of adjustable moulded case circuit breaker is used in the circuit breaker of 50Hz or 60Hz, with rated insulation voltage of 800Vdc, with rated voltage up to 690Vac, with rated current from 16A to 1250A. The circuit breaker is equipped with electronic trip unit, and has long time protection, short time protection, instantaneous protection and ground protection, and also has isolating function. Under-voltage release, shunt release, alarming contact, auxiliary contact, motor-operated mechanism are options.

Product Description
ModelGSM3E-125GSM3E-250GSM3E-400GSM3E-630GSM3E-800GSM3E-1250
Frame Current Inm (A)1252504006308001250
Rated current In (A)32631252504006308001250 (800-1250)
Over-load long delay setting current Ir1 (A)16, 20, 25, 3232, 36, 40, 45, 50, 55, 60, 6363, 65, 70, 75, 80, 85, 90, 100, 125100, 125, 140, 160, 180, 200, 225, 250200, 225, 250, 280, 315, 350, 400400, 420, 440, 460, 480, 500, 530, 560, 600, 630630, 640, 660, 680, 700, 720, 740, 760, 780, 800800, 850, 900, 950, 1000, 1050, 1100, 1250
Rated voltage (V)AC400V/AC690VAC400V/AC690VAC400V/AC690VAC400V/AC690V
AC400V
AC400V/AC690VAC400V/AC690V
Rated insulation voltage (V)100010001000100010001000
Rated impulse withstand voltage Uimp (V)800080008000800080008000
Pole number3P
4P
4P3P
4P
4P3P4P3P4P3P4P3P
Breaking capacity levelMHMHMHMHMHMHMHMHMHMHMH
Ultimate short circuit breaking capacity Icu (KA)AC400V508550855085508575100751007510075100751007510075100
AC690V20/20/20/20/20/20/35/35/35/35/35/
Rated service short circuit breaking capacity Ics (KA)AC400V35503550355035507580758075807580758075807580
AC690V10/10/10/10/15/15/25/25/25/25/25/
Rated short time withstand current Icw (KA)/0.5s55581015
Utilization categoryBBBBBB
Flashover distance (mm)5050100100100100
Electrical life (times)80008000750075007500500
Mechanical life (times)Maintainance-free20000200001000010000100002500
With maintainance40000400002000020000200005000
Outline dimension (mm)W92122107142150198210280210280210
H150165257280280340
D828597103103138.5
Net weight (KG)2.0 2.5 2.43.16.38.310.514.210.514.217.8
StandardIEC60947-2/EN60947-2
Operation ambient temperature-25 to +60 centigrade, +andf the averagetemperature within 24 hours shall benot more than 35 certigrade
Altitude (m)2000m, if higher than 2000m, then derate
Class of pollution3
Installation category3 for main circuit and under-voltage release, 2 for others
 
 