SF6-110KV
High Voltage Circuit Breakers
Manual Type
Normal Type Circuit Breaker
Vacuum
Fixed
Vacuum
1
Circuit Breaker
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection, OVP(Overvoltage Protection)
VDE, ISO9001-2000, CE, CB
JUNKE
Wooden Package
Wenzhou
Product Description


Main features
Use spring mechanism, its performance is not relevant to temperature, stable performance;
Optimized interrupter structure and movement curve of contact, high reliability on breaking current;
Reignite and restrike cannot occur under breaking capacitive current;
Optimized pole and frame design with higher capability to endure earthquake;
High reliability, long average normal service time, low maintenance cost;
Convenient installation and configuration in field, it takes only one day or two days;
Low operating noise, suit for residential area.:
Environmental conditions
Installation site | outdoor |
Ambient temperature | -25ºC~+40ºC |
Max. daily temperature difference | ≤25ºC |
Height above sea level | 2000m(no limit for specified order) |
Air humidity | Daily average:≤95%; month average:≤90%; |
Wind speed | ≤34m/s |
Solar radiation | ≤0.1W/cm2(fine day, noon) |
Earthquake intensity | horizontal:≤0.3g;vertical:≤0.15g |
Icing thickness | ≤10mm |
Creepage distance | 25mm/kV or 31mm/kV |
Static load on terminal in Y-direction | 1250N |
Static load on terminal in X-direction | 750N |
Static load on terminal in Z-direction | 1000N |
Main Technical data
No. | Items | Unit | Parameter | ||
1 | Rated voltage | kV | 110KV | ||
2 | Rated power frequency withstand voltage(1min) | Phase-to-phase Phase-to-ground | kV | 230 | |
fracture | kV | 230+73* | |||
3 | Rated lightning impulse withstand voltage | Phase-to-phase Phase-to-ground | kV | 550 | |
fracture | kV | 550+103* | |||
4 | Power frequency withstand voltage(5min)under SF6 zero-gauge pressure | kV | 95 | ||
5 | Rated frequency | Hz | 50 | ||
6 | Rated current | A | 3150 | ||
7 | Rated short circuit breaking current | kA | 40 | ||
8 | First-pole-to-clear factor | 1.5 | |||
9 | Rated short circuit breaking current (DC component) | More than 41% | |||
10 | Rated short circuit making current (peak) | kA | 100 | ||
11 | Rated short time withstand current(rms) | kA | 40 | ||
12 | Rated peak withstand current | kA | 100 | ||
13 | Rated short circuit duration | s | 4 | ||
14 | Rated out-of-phase breaking current | kA | 3(OP1) ,10(OP2) | ||
15 | Short range breaking current | kA | 36;30 | ||
16 | Wrong-phase earthing fault breaking current | kA | 34.8 | ||
17 | Rated line charging switching current | A | 31.5 | ||
18 | Full capacity breaking time without check and repair | Times | 20 or rated current breaking times:3000 | ||
19 | Rated operating sequence | O-0.3s-CO-180s-CO | |||
20 | Rated SF6 pressure (20ºC gauge) | MPa | 0.6 | ||
21 | Alarm/Lock pressure(20ºC gauge) | MPa | 0.55/0.50 | ||
22 | SF6 annual leakage rate | %/Y | ≯0.5 | ||
23 | Gas moisture content | Check value after hand over | μL/L | ≯150 | |
Allowed service value | μL/L | ≯300 | |||
24 | Resistance of the main circuit | μΩ | ≤35 | ||
25 | Mechanical life | Time | 6000 | ||
26 | Radio interference level (1.1Ur/) | μV | ≯500 | ||
27 | Allowed partial discharge intensity(1.2Ur) | pC | ≤5 | ||
28 | Noise(distance from sound source:horizontality:2m,height:1.5m) | dB | 90 |