ZJR2-3300
Protection
Combination
Linear
Continuous
Automatic Control, Protection
CCC, ISO: 9001, CE
New
Customized
Plastic
30kw
380V, 440V
50/60Hz
Gray
Squirrel-Cage Three-Phase Asynchronous Motor
It Is Recommended Not to Exceed 20 Times Per Hour.
3kg
4kg
Carton Box
Yes
IP20
CHZIRI, OEM Service Offered
Standard export packing
CCC CE
China
8537101990
Product Description
FROM CHZIRI SOFT STARTER ZJR2-31150

ZIRI STORY

Technical Indications
Soft starter Outline Dimension (Unit:mm)

Guide Model for ZJR2 Soft Starter
ZJR2 Soft Starter Wiring Diagram

CHZIRI Package for Soft Starter 30kW



ZIRI STORY

Technical Indications
Item | Item Description | ||
Input Power Supply | Input Voltage | Three Phase 380V-15% ~ 415+10% | |
Frequency | 50/60Hz | ||
Adaptive Motor | Squirrel-cage three-phase asynchronous motor | ||
Starting Times | It is recommended not to exceed 20 times per hour. | ||
Control Mode | 1) Operation panel control; 2) Operation panel + external control; 3) External control; 4) External control + COM control; 5) Operation panel + external + COM control; 6) Operation panel + COM control; 7) COM control; 8) No start or stop operation. | ||
Start Mode | 1) Current-limiting start; 2) Voltage ramp start; 3) Kick start + current-limiting start; 4) Kick start + voltage ramp start; 5) Current ramp start; 6) Voltage current-limiting double closed-loop start. | ||
Stop Mode | 1) Soft stop; 2) Free stop. | ||
Protective Function | 1) Open loop protection for external instantaneous stop terminals; 2) Over-heat protection for soft starter; 3) Protection for too long starting time; 4) Input open phase protection; 5) Output open phase protection; 6) Unbalanced three-phase protection; 7) starting over current protection; 8) Running overload protection; 9) Under voltage protection for power voltage; 10) Over voltage protection for power voltage; 11) Protection for fault parameter setting; 12) Load short circuit protection; 13) Auto restart or incorrect wiring protection; 14) Incorrect wiring protection of external control stop terminals. | ||
Ambient | Place to be used | Indoor location with good ventilation free from corrosive gas and conductive dust. | |
Altitude | Below 3000M. It have to rise the rate power when the altitude is more than 3000M. | ||
Ambient Temperature | -30~+55ºC | ||
Ambient Humidity | ≤90%RH without dew condensation. | ||
Vibration | <0.5G | ||
Structure | Protection Class | IP20 | |
Cooling Pattern | Natural wind cooling. | ||
Soft starter Outline Dimension (Unit:mm)

Guide Model for ZJR2 Soft Starter
Model | Rated Power(KW) | Rated Current (A) | Outline Size | Install Size | Net Weight (KG) | ||||
H1 | W1 | D | H2 | W2 | d | ||||
ZJR2-3055/4055 | 5.5 | 11 | 270 | 145 | 159 | 245 | 130 | M6 | <3.5 |
ZJR2-3075/4075 | 7.5 | 15 | 270 | 145 | 159 | 245 | 130 | M6 | <3.5 |
ZJR2-3110/4110 | 11 | 22 | 270 | 145 | 159 | 245 | 130 | M6 | <3.5 |
ZJR2-3150/4150 | 15 | 30 | 270 | 145 | 159 | 245 | 130 | M6 | <3.5 |
ZJR2-3185/4185 | 18.5 | 37 | 270 | 145 | 159 | 245 | 130 | M6 | <3.5 |
ZJR2-3220/4220 | 22 | 44 | 270 | 145 | 159 | 245 | 130 | M6 | <3.5 |
ZJR2-3300/4300 | 30 | 60 | 270 | 145 | 159 | 245 | 130 | M6 | <3.5 |
ZJR2-3370/4370 | 37 | 75 | 270 | 145 | 159 | 245 | 130 | M6 | <3.5 |
ZJR2-3450/4450 | 45 | 90 | 270 | 145 | 159 | 245 | 130 | M6 | <3.5 |
ZJR2-Z3550/4450 | 55 | 110 | 270 | 145 | 159 | 245 | 130 | M6 | <3.5 |
ZJR2 Soft Starter Wiring Diagram

CHZIRI Package for Soft Starter 30kW