RTU-S
Chiller
Galvanized Sheet
General
380-415, 440, 460, 50/60Hz
Ordinary
Supermarket, Hospital, Pharmaceutical and Building
Split
15~20 years
ISO, CE
New
Commercial/Industrial
Cooling Only or Heat Pump
R22/R407c/R410A/R134A
Pre, Medium and HEPA(Optional)
AMRTA or OEM
Standard Package Fit for Transportation
Color: white
China
8418612090
Product Description
20kw-104kw Air Cooled Ducted Split Chiller Central Air Conditioner
11 sizes available ranging from 19.5 kW to 103.7 kW cooling capacity.
Cooling only and heat pump version.
Wide application as hotel, apartment, villa, factory, shopping center, office building, school, etc.
Panels and frame are made from metal steel protected with polyester powder painting to ensure total resistance to atmospheric agents.
High efficiency scroll compressor for the whole range, with built-in thermal overload cut-out and crankcase heater, mounted on rubber vibration dampers.
Compact indoor design, long air supply distance.
Outdoor units are equipped with low noise axial fans.
Indoor units are equipped with quiet centrifugal fans.
Split installation, connected by means of flare/welding coupling.
Easy operation line controller:
Multi safety protection
Additional electric heater on indoor unit
Additional heating coil on indoor unit
TECHNICAL DATA
Performance values refer to the following conditions:
* Cooling capacity is measured under the condition: indoor temperature DB 27°C/ WB 19°C, ambient temperature DB 35°C / WB 24°C.
** Heating capacity is measured under the condition: indoor temperature DB 20°C / WB 15°C, ambient temperature DB 7ºC / WB 6°C.
*** Sound pressure measured at a distance of 1 m and a height of 1.5 m above the ground in a dear field.
**** Optional as request.
Product Description
11 sizes available ranging from 19.5 kW to 103.7 kW cooling capacity.
Cooling only and heat pump version.
Wide application as hotel, apartment, villa, factory, shopping center, office building, school, etc.
Panels and frame are made from metal steel protected with polyester powder painting to ensure total resistance to atmospheric agents.
High efficiency scroll compressor for the whole range, with built-in thermal overload cut-out and crankcase heater, mounted on rubber vibration dampers.
Compact indoor design, long air supply distance.
Outdoor units are equipped with low noise axial fans.
Indoor units are equipped with quiet centrifugal fans.
Split installation, connected by means of flare/welding coupling.
Easy operation line controller:
- Cooling/Heating/Fan/Auto
- Timing On/Off
- Error indication
Multi safety protection
- High/low pressure protection
- Time delay and antifreeze switch
- Phase sequence relay
- Current overload protection
- Overheat protection
Additional electric heater on indoor unit
Additional heating coil on indoor unit
TECHNICAL DATA
Mod. | 20 | 25 | 32 | 36 | 42 | 48 | ||
Nominal cooling capacity* | kW | 19.5 | 24.8 | 31.2 | 35.6 | 41.3 | 47.4 | |
Nominal heating capacity** | kW | 22.6 | 28.9 | 35.8 | 40.8 | 46.9 | 54.4 | |
Connection | ||||||||
Method | / | Flare | Flare | Flare | Welding | Welding | Welding | |
Liquid pipe diameter | ¢mm | 9.52x2 | 12.7x2 | 12.7x2 | 15.88x1 | 15.88/12.7 | 15.88/12.7 | |
Gas pipe diameter | ¢mm | 15.88x2 | 19.05x2 | 19.05x2 | 28x1 | 28/19.05 | 28/19.05 | |
Power supply | / | 230V/3N/60Hz | ||||||
OUTDOOR UNIT | Compressor | |||||||
Qty/refrigerant circuit | Nr. | 2/2 | 2/2 | 2/2 | 1/1 | 2/2 | 2/2 | |
Cooling power input* | kW | 7.2 | 9.3 | 11.8 | 12.8 | 15.1 | 17.9 | |
Heating power input** | kW | 7.13 | 9.21 | 11.68 | 12.67 | 14.95 | 17.72 | |
Energy adjustment | % | 50-100 | 50-100 | 50-100 | 0-100 | 40-60-100 | 33-66-100 | |
Axial fans | ||||||||
Quantity | Nr. | 1 | 1 | 1 | 1 | 2 | 2 | |
Airflow | m3/h | 9400 | 9400 | 12500 | 14200 | 18800 | 18800 | |
Sound pressure level*** | dB(A) | 67 | 67 | 68 | 70 | 71 | 71 | |
Net weight | kg | 170 | 180 | 220 | 280 | 260 | 280 | |
INDOOR UNIT | Centrifugal fans | |||||||
Quantity | Nr. | 2 | 2 | 2 | 2 | 2 | 2 | |
Airflow | m3/h | 3500 | 4500 | 5650 | 6450 | 7400 | 8550 | |
ESP | Pa | 120 | 100 | 150 | 130 | 180 | 200 | |
Sound pressure level*** | dB(A) | 64 | 64 | 66 | 66 | 68 | 68 | |
Net weight | kg | 90 | 100 | 150 | 160 | 180 | 200 | |
Additional electric heater**** | kW | 2×3 | 2×4 | 2×5 | 2×6 | 2×6 | 2×8 | |
Additional heating coil**** | kW | 22.2 | 28.4 | 35.1 | 40.0 | 46.0 | 53.3 |
Mod | 52 | 62 | 72 | 88 | 104 | ||
Nominal cooling capacity* | kW | 51.3 | 63.3 | 71.3 | 87.9 | 103.7 | |
Nominal heating capacity** | kW | 58.9 | 72.6 | 81.9 | 100.0 | 115.8 | |
Connection | |||||||
Method | / | Welding | Welding | Welding | Welding | Welding | |
Liquid pipe diameter | ¢mm | 15.88/12.7 | 15.88×2 | 15.88×2 | 15.88×2 | 19.05×2 | |
Gas pipe diameter | ¢mm | 28/19.05 | 28×2 | 28×2 | 28×2 | 35×2 | |
Power supply | / | 230V/3N/60Hz | |||||
OUTDOOR UNIT | Compressor | ||||||
Qty/refrigerant circuit | Nr. | 2/2 | 2/2 | 2/2 | 2/2 | 2/2 | |
Cooling power input* | kW | 18.4 | 23.1 | 26.6 | 28.1 | 39.3 | |
Heating power input** | kW | 18.22 | 22.87 | 26.33 | 27.82 | 38.91 | |
Energy adjustment | % | 30-70-100 | 50-100 | 50-100 | 50-100 | 50-100 | |
Axial fans | |||||||
Quantity | Nr. | 2 | 2 | 2 | 2 | 2 | |
Airflow | m3/h | 21500 | 26500 | 29880 | 36500 | 43500 | |
Sound pressure level*** | dB(A) | 71 | 71 | 71 | 71 | 71 | |
Net weight | kg | 330 | 460 | 460 | 780 | 800 | |
INDOOR UNIT | Centrifugal fans | ||||||
Quantity | Nr. | 2 | 2 | 2 | 2 | 2 | |
Airflow | m3/h | 9250 | 11450 | 12900 | 14800 | 17100 | |
ESP | Pa | 200 | 300 | 300 | 280 | 500 | |
Sound pressure level*** | dB(A) | 68 | 68 | 69 | 69 | 70 | |
Net weight | kg | 220 | 230 | 300 | 320 | 400 | |
Additional electric heater**** | kW | 2×8 | 2×10 | 2×10 | 2×12 | 2×14 | |
Additional heating coil**** | kW | 57.8 | 71.2 | 80.3 | 98.0 | 113.5 |
Performance values refer to the following conditions:
* Cooling capacity is measured under the condition: indoor temperature DB 27°C/ WB 19°C, ambient temperature DB 35°C / WB 24°C.
** Heating capacity is measured under the condition: indoor temperature DB 20°C / WB 15°C, ambient temperature DB 7ºC / WB 6°C.
*** Sound pressure measured at a distance of 1 m and a height of 1.5 m above the ground in a dear field.
**** Optional as request.