APC Galaxy PX UPS
Three Phase
On-line
Short Circuit
Communication
Lighting/Power
Standard Machine
Sine Wave Output UPS
Medium Type
Decentralized/Centralized Model
APC
APC Galaxy Px UPS
16kVA-160kVA
1
16kw
340 – 477 V @ Full Load
50/60 Hz
380 V/400 V/415 V
50/60 Hz
150% for 60 Seconds, 125% for 10 Min
0 to 40 °c (32 to 104 °f)
APC
China
8504402000
Product Description

Technical specifications | ||
Symmetra PX 48 kW | ||
Input | ||
Gnid system | 3P+N+G | |
Voltage range | 340-477V@full load | |
Frequency | 50 Hz | |
Frequency range | 40-70 Hz with 10 Hz/s slew rate | |
Power factor (PF) | >0.99@load>25%,>0.95@load>15%,>0.90@load>10% | |
THDi (full load) | <5% | |
Nominal input current | 77A@380V,73A@400V,70A@415V | |
Maximum input current | 84.4A@380V,80.2A@400V,77.3A@415V | |
Input current limit | 98.3A@380V/400 V/415 V | |
Maximum input short-circuit level | 30 kA | |
Output | ||
Power rating | 48 kW | |
Grid system | 3P+N+G | |
Voltage (nominal) | 380400/415V L-L | |
Nominal output current | 73A@380V,69A@400V,67A@415V | |
Frequency | 5N60 Hz bypass synchronized,50/60 Hz+/-0.1%free running | |
Synchronized slew rate | Programmable to 0.25,0.5,1,2,4,6 Hz/s | |
Overload (normal and battery operation) | 150%for 60 seconds,125%for 10 min,100%continuous | |
V thd | <2%from 0 to 100%linear load,<5%full nonlinear load according to IEC/EN 62040-3 | |
Load PF | From 0.5 leading to 0.5 lagging without any derating | |
Bypass | ||
V nomina | 380V/400 V/415V | |
Voltage (range) | +/-10%from selected voltage | |
Frequency (nominal) | 50/60 Hz | |
Frequency (range) | +/-0.1 Hz,+/-3 Hz,+/-10 Hz(user selectable) | |
Nominal input current | 73A@380V,69A@400V,67A@415V | |
Fficlen | ||
AC-AC at nominal mains | ≥95%at35%-100%load;≥90%@15%-34%load | |
DC-AC at nominal battery voltage | ≥94%at 25%-100%load;≥90%@15%-24%load | |
Mechanical | ||
Dimensions (HxWxD) | 1,991x600x1,070 mm | |
Weight | 796 kg | |
Environmental | ||
Storage temperature,UPS,and batteries | -15 to 40ºC with batteries,approximately 6-8 months 25 ºC battery self-discharge, 1-2 months@45ºC | |
Operating temperature* | 0 to 40 ºC (32 to 104F) | |
Regulatory compliance | ||
CE, EN/IEC 62040-1-1, EN/IEC/UL 60950-1, EN 50091-2/IEC 62040-2 (class A), FCC15A, EN/IEC 62040-3 |























1. May I take some samples to test before I placing the order?
Yes, we can offer sample testing for you to verify product quality and performance.
2. What is the warranty?
We support 1 years warranty.
3.What can you buy from us?
Eaton, Vertiv, APC, Santak, Vesion & OEM/ODM UPS; Cooling, MDC, PDU and so on.
4. What payment methods does your conmpany support?
We could accept T/T, credit card, Alipay or L/C at sight.
5. What are the terms can you offer for us?
We could offer EXW, FOB, CIF, DDP and so on.