ACR10R-D16TE4
Digital
Indirect Connected
Multi-Functional Energy Meter, Watt-Hour Meter, Meter for Industry and Home Use, Standard Electric Energy Meter, Reactive Energy Meter, Multi-rate Watt-hour Meters, Three Phase Meter for Solar Energy Storage
Three-phase Four-wire
Electronic Meter
Terminal
Pulse Peak
Energy Meter
RoHS, ISO, CE
Non-Customized
Three Phase Meter for Solar Energy Storage
OEM ODM
AC 57.7V/100V(100V),220V/380V(400V)
0-200A
45~65Hz
RS485 Port, Modbus-RTU
LCD
AC85-265V or DC100-350V
ACREL
Fob Shanghai
64*85*54mm
China
Product Description
Product Description
3 phasse din rail energy meter with split core open ct clamps is suitable for power monitoring of grid-connected PV power station,power demand side management and other applications.
It is easy to install without removing primary bus bar and cost-effective.
It can measure electrical parameters including current,voltage, active power,reactive power,apparent power,frequency,power factor and so on.
It supports multi-tariff energy metering,4 quadrant energy metering,harmonic analyse and energy monitoring.
Circuit breaker switch 'remote signaling' and 'remote controlling' can be realized with digital input and relay output.
Functions and parameters
Functions and parameters of ACR10R-D16TE4:
*LCD 8 digits
*Parameters measuring:current,voltage,frequeny,power factor,active power,reactive power,apparent power and 4 quadrant energy
*Communication:RS485 modbus-RTU
*Switching value input and relay output
*Optional functions:
refering to below chart
Technical Parameters
Dimension(Unit:mm)
Meter Dimensions

CT Dimensions

Installation


Wiring

Certificate




ACR10R-D16TE4 Three phase energy meter with 3 CTS for solar energy storage system
General3 phasse din rail energy meter with split core open ct clamps is suitable for power monitoring of grid-connected PV power station,power demand side management and other applications.
It is easy to install without removing primary bus bar and cost-effective.
It can measure electrical parameters including current,voltage, active power,reactive power,apparent power,frequency,power factor and so on.
It supports multi-tariff energy metering,4 quadrant energy metering,harmonic analyse and energy monitoring.
Circuit breaker switch 'remote signaling' and 'remote controlling' can be realized with digital input and relay output.
Functions and parameters
Functions and parameters of ACR10R-D16TE4:
*LCD 8 digits
*Parameters measuring:current,voltage,frequeny,power factor,active power,reactive power,apparent power and 4 quadrant energy
*Communication:RS485 modbus-RTU
*Switching value input and relay output
*Optional functions:
refering to below chart
Technical Parameters
ACR10R-D16TE4 3 phase energy meter with 3 CTs clamps 24mm | ||
Network | 3 phase 4 wire LCD display | |
voltage | measuring range | AC 57.7V/100V(100V),220V/380V(400V) |
power consumption | ≤0.2VA | |
current | measuring range | 200A |
power consumption | ≤0.2VA | |
frequency | 45hz-65hz | |
Meauring parameters | Current,voltage,frequeny and power factor | |
active power,reactive power and apparent power | ||
four quadrant energy | ||
Optional functions | Total harmonic distortion(THD) | |
Up to the 31st harmonic | ||
Max demand | ||
Multi-tariff energy metering | ||
SOE record | ||
Alarm | ||
in-built clock | ||
J(2DO) | J,K,2 channel pulse,4DI+2DO or 4DI+EP | |
K(4DI) | ||
Pulse(2 channel) | ||
Accuracy | Frequency:0.05hz ,reactive energy:1 current,voltage:0.5 | |
Power supply | AC85-265V or DC100-350V;DC24V(±10%);DC48V(±10%) power consumption≤10VA | |
switching value input | 4 circuit dry contact | |
relay output | 2 NO contact,capacity:AC 250V/3A,DC 30V/3A | |
environment | working temperature | -10ºC-55ºC |
storage temperature | -20ºC-70ºC | |
relative humudity temperature | ≤93%(non-condensing) | |
altitude | ≤2500m | |
Communication | RS485,Modbus-RTU |
Dimension(Unit:mm)
Meter Dimensions

CT Dimensions

Installation


Wiring

Certificate