BYD0510ACM/BYD0520ACM
Infrared Range and Communication System
Heat Detectors
Analog Type
Integration
Stainless Type
IP65
CE
Customized
Infrared Temperature Senor
4-20mA
One Year
3-10 Days
0-60 Degree Temperature
-50-200 Degree Temperature
BIEDAS
Box Package
China Jiangsu
9025900010
Product Description
As a integrated transmitter infrared thermometer, BYD0560ACM have the integration of the sensor, the optical system and the electronic circuit inside its stainless steel or aluminium alloy shell. It can be installed very conveniently by making the standard screw thread on the product be joined with the installation position.
The principle of temperature measurement by infrared
Any object transmits the infrared radiation, and the radiation intensity
varies with temperature. Infrared temperature measurement uses thermal radiation within the range of wavelength 8-14um.
The infrared thermometer is a kind of hot-electron sensor which can
receive the infrared radiation and transform it to a measurable electric signal, and itsmain assemblies are as following:
• Lens
• Spectrum filter
• Detector
• Electronic circuit (Amplifier/ linearization/ signal processing)
Light path of the infrared thermometer is determined by the specification
of lens. The spectrum filter can choose the best spectral range for temperature measurement.The power of infrared radiation can be transformed to electric signal by detector and electronic circuit.
The principle of temperature measurement by infrared
Any object transmits the infrared radiation, and the radiation intensity
varies with temperature. Infrared temperature measurement uses thermal radiation within the range of wavelength 8-14um.
The infrared thermometer is a kind of hot-electron sensor which can
receive the infrared radiation and transform it to a measurable electric signal, and itsmain assemblies are as following:
• Lens
• Spectrum filter
• Detector
• Electronic circuit (Amplifier/ linearization/ signal processing)
Light path of the infrared thermometer is determined by the specification
of lens. The spectrum filter can choose the best spectral range for temperature measurement.The power of infrared radiation can be transformed to electric signal by detector and electronic circuit.
Model Rules | For example: BYD0560ACM, Range: -50ºC~600ºC, Output: 4~20mA | |
Temperature Range | BYD0510ACM: -50ºC~100ºC ,BYD0520ACM: -50ºC~200ºC BYD0530ACM: -50ºC~300ºC , BYD0540ACM: -50ºC~400ºC BYD0550ACM: -50ºC~500ºC , BYD0560ACM: -50ºC~600ºC | |
Spectral Response | 8~14um | |
Distance Spot Ratio (D:S) | 20 : 1 | |
Response Time | 500ms | |
Accuracy | ≤100ºC ±2ºC, ≥100ºC ±2% | |
Repeatability | ±1% or ±1ºC | |
Emissivity | 0.95 fixed | |
Power | DC 9~24V | |
The maximum current | 50mA | |
Analog output | RT-A: 4~20mA | |
Isolation: Power, digital output and analog output are isolated and do not interfere with each other. | ||
Protection level | IP54 | |
Environmental temperature | 0~50ºC | |
Storage temperature | -20~50ºC | |
Relative Humidity | 10~95% | |
Shell material | Stainless steel | |
Standard wire length: 2m (or can be 5m or 10m or other length you need) | ||
With CE approval and protection against electromagnetic disturbance for EU standard. | ||
Cautions: . This instrument is not recommended for the measurement of bright or polished metal surfaces (non-ferrous metal objects such as stainless steel, aluminum, etc.); The reflections will affect the accuracy of the measurement. . The temperature can not be measured through the glass , otherwise the temperature value will only be the surface temperature of the glass. . The accuracy of the measurement will be affected by the steam , dust, smoke, etc. | ||