Cj Intelligence Pid Temperature Controller (XMTA-9000)

Price $25.80 Compare
Min Order 1 Piece
Shipping From Zhejiang, China
Popularity 250 people viewed
Quantity
+-
 

Yuyao Gongyi Meter Co., Ltd.

VIP   Audited Supplier 15 years
Profile Certified by SGS/BV
XMTA-9000
RoHS, CE, ISO
LED
96*96
Digital
Electronic Type
CJ
1PCS/Box
ISO 9001: 2008Others
China
9032900090
Product Description

I.Product characteristic

The core of the product adopts the up-to-date microprocessor chip.
Red and green double-bank nixie tube display the measured value and setting value.
Easy operation in the four keys, & fast setting in the parameter.
Control in high precision's PID intelligent and two or three bit location check program.
Upper-bank display the measured value, & bottom-bank display the setting value under normal working conditions.


II.Primary technical standard
1. Input: Thermocouple: K\E\J\S; Thermal resistance: PT100 CU50
2. Range: K(0~400\0~1300)\E(0~400\0~800)\J(0~1000) S(0~1600)\PT100(-100.0~200.0\0~600)\CU50(-50.0~150.0)
3. Measure error: ± 0.5%F. S± Byte
4. Silicon control trigger signal(over zero): Range≥ 3V, Width≥ 40us
5. The output contact potential of the relay: Impedance load 7A
6. Input power: AC85~242V 50/60Hz
7. Entironment: Temperature: 0 to 50, Humidity: ≤ 85%RH
8. External dimension: 96× 96× 110 hole 92× 92

Size: XMT:80×160×110mm  hole: 76×152;  XMTA:96×96×110mm  hole: 92×92; 
   XMTE:48×96×110mm   hole: 44×92;  XMTF:96×48×110mm   hole: 92×45;
   XMTD:72×72×110mm   hole: 68×68;  XMTG:48×48×110mm   hole: 45×45; 



Name and functions of the sections



(1)PV display

Indicates the process variable (PV) with a red LED.

(2)SV display

Indicates the setting value (SV) with a green LED.

(3)ALM1 indicator
When ALM1 output is ON, a red LED lights.

(4)ALM2 indicator

When ALM2 output is ON, a red LED lights.

(5)AT indicator

When auto tuning function is ON, a green LED lights.

(6)OUT indicator
When OUT is ON, a green LED lights.

(7)Mode key (SET)

Switches the setting mode and registers the setting value and selected value.
(Setting value and selected value are registered by pressing the mode key.)

(8)Data shift key (<)

(9)Decrease key (∨)

Decreases numeric value of the setting value

(10)Increase key (∧)

Increases numeric value of the setting value.

Connection figure(consult)  


 

Message Type
* Message Content
* Name  
* Phone
* Email
* CAPTCHA